Control system development for an organic Ranking cycle engine

An organic Rankine cycle engine is used as part of a solar thermal power conversion assembly (PCA). The PCA, including a direct-heated cavity receiver and a shaft-mounted alternator, is mounted at the focal point of a parabolic dish concentrator. The engine controls are required to maintain approximately constant values of turbine inlet temperature and shaft speed, despite variation in the concentrated solar power input to the receiver. The controls design approach, system models, and initial stability and performance analysis results are presented herein.

Bergthold, F. M., Jr.↗

Control system development for a 1 MW/e/ solar thermal power plant

The point-focusing distributed receiver power plant considered consists of a number of power modules delivering power to a central collection point. Each power module contains a parabolic dish concentrator with a closed-cycle receiver/turbine/alternator assembly. Currently, a single-module prototype plant is under construction. The major control system tasks required are related to concentrator pointing control, receiver temperature control, and turbine speed control. Attention is given to operational control details, control hardware and software, and aspects of CRT output display.

Daubert, E. R.↗

Control system development for an organic Rankine cycle engine

The development of a control logic to govern the toluene throttle valve and verify the stability of the speed control approach for multiple engines connected to a 1 MWe point focus solar generator installation for distributed applications is presented. The toluene is is pumped by booster and main feed pumps through a regenerator to the parabolic focus receiver, with the flow rate controlled by a valve to remain at critical level of 4.1 MPa. The valve changes the inlet pressure at the turbine nozzle block. Each concentrator would produce 76 kWth and 20 kWe. Dynamic variables in the logic account for insolation variation, fluid temperature, ac grid voltage, the thermal dynamics of the regenerator, and variations in the head supplied by the feed pump. Separate analyses are presented for the turbine shaft speed and toluene loop dynamics. The resulting logic is considered preliminary and suitable only in full insolation conditions. Extension of the model to nonlinear perturbations is indicated.

Bergthold, F. M., Jr.↗