Search NASASearch

Engineering topics

Biswas, Shuchismita

Publications and source records attributed to Biswas, Shuchismita.

A Methodology to Evaluate the Grid Reliability Impact of Oscillations Induced by Large Loads

The rapid growth of hyperscale AI data centers is bringing renewed attention to the reliability risk that sustained forced oscillations pose to bulk power systems, with cyclic computational workloads emerging as a new forcing source. Unlike the broadband, stochastic disturbances from traditional industrial loads such as arc furnaces, AI training and inference facilities can inject large active power swings concentrated at specific frequencies over extended durations - characteristics that existing grid planning practices do not account for. While the North American Electric Reliability Corporation (NERC) has recognized this gap and called for system-level studies of large load interconnections, no standardized methodology exists to screen, simulate, and quantify these risks at the planning stage. This report presents the Risk Assessment Tool for Large Load-induced Events (RATLLE), a Python-based, publicly available script suite developed at the Pacific Northwest National Laboratory to evaluate bulk power system reliability risks from data center-induced oscillations. RATLLE implements a three-module workflow: a screening module that identifies vulnerable interconnection locations and excitable system modes; a simulation module that models cyclic data center load behavior using a commercial positive sequence simulation platform; and an analysis module that computes risk metrics and generates interactive visualization dashboards. The risk metrics, formulated around simulation observables, map oscillation impacts to a three-stage severity scale spanning latent equipment fatigue through imminent cascading failure. The methodology is demonstrated on two Western Electricity Coordinating Council (WECC) system models: a publicly available 240-bus reduced representation and a detailed 2031 Heavy Winter planning case. Case studies illustrate that even modest 50 MW forced oscillations at resonant frequencies can produce wide-area power swings, N-1 security constraint violations, and cascading generator trips through protection actions - outcomes that would not occur under normal operating conditions without oscillations present. The results underscore the need for standardized oscillation impact assessment in large load interconnection studies and provide a reproducible, extensible framework for utilities to adopt or customize within their existing planning workflows.

Biswas, Shuchismita

Cloud-Based Demonstration of the Eastern Interconnection Situational Awareness Monitoring System (ESAMS)

This report describes a cloud-based implementation and field demonstration of the Eastern Interconnection Situational Awareness and Monitoring System (ESAMS). ESAMS was developed to support the detection and source localization of forced oscillations using synchrophasor measurements from tie-lines connecting areas served by different reliability coordinators (RCs), so that RCs could better coordinate their response to wide-area events. A previous effort had identified deployment barriers associated with hosting shared situational awareness tools at a single RC. To address these barriers, ESAMS was migrated to Amazon Web Services and evaluated in a six-month field demonstration. ISO New England (ISO-NE) and PJM streamed data to the platform using AWS Direct Connect and a site-to-site VPN, respectively. The resulting multi-utility measurement footprint enabled regional source localization across major portions of the U.S. Eastern Interconnection and supported routine identification of oscillation events. During the final three months of the trial, 24 events above 2 MW/MVAR were detected. The largest detected oscillation approached a 25 MW peak-to-peak amplitude, and the longest persisted intermittently for more than 11 hours. The demonstration also assessed operational considerations—including data transfer volumes, end-to-end latency, and cloud computing costs—and found that network and compute requirements were modest relative to typical cloud capabilities while providing performance comparable to prior on-premises deployments. Overall, the results indicate that cloud hosting can provide a practical path to shared interconnection-wide oscillation monitoring. The cloud ESAMS demonstration establishes a foundation for broader utility participation and for building future wide-area analytics that leverage measurements across organizational boundaries.

Follum, James D.

An Open-Access Repository of Synchrophasor Data Quality Examples: Curation and Example Applications

Synchrophasor measurements are critical in providing wide-area situational awareness to power system operators. However, data artifacts may be introduced due to various issues such as loss of communication, loss of GPS signal, internal clock error, and vendor-specific implementation of phasor estimation algorithms. Tools designed to provide actionable insights from synchrophasor data, hence, must be designed to be robust to these data quality issues. In this work, two years of synchrophasor data sourced from multiple electric utilities in the United States were analyzed to identify examples of data quality problems. These examples were then labeled and published in the Grid Event Signature Library, a publicly available repository of power system measurements hosted by the Oak Ridge National Laboratory. This paper describes the data curation process, and illustrates two application use cases where the dataset can be valuable to the research community. In the first use case, a random forest classifier is trained to distinguish power system disturbance signatures from data anomalies introduced in synchrophasor measurements due to clock errors. The second use case studies the impact of data quality issues on an example synchrophasor application (specifically, event start time determination). The choice of data quality problems investigated is informed by the examples in the repository curated in this work.

24 POWER TRANSMISSION AND DISTRIBUTION

Modeling and Automation Framework for High IBR Integration in Large-Scale Power Systems

The increasing prevalence of power electronics- interfaced renewable generation sources is leading to a gradual replacement of traditional thermal generation-based synchronous machines. In this context, the modeling of a large-scale power grid that incorporates a significant number of inverter-based resources is crucial for understanding the dynamics and effects of these resources on the power system. This study investigates the positive sequence model of grid-following and grid-forming inverters. Additionally, this work explores the integration of distributed energy resources using population as an indicator of their relative geographic locations. To address challenge to integrate these inverter based resources into a realistic grid of the US Western interconnection, automation scripts are developed to streamline the process of replacing conventional generators with grid-following and grid-forming inverters, as well as allocating distributed energy resources. Different penetration levels of these inverters are considered, and their frequency regulation support following a disturbance is compared through dynamic simulations.

Lyu, Xue

A Stochastic Framework for Estimating Load Profiles at EV Fast Charging Stations

This paper formulates a methodology for estimating the average daily load profiles of EV fast charging stations over a planning horizon of five to ten years. The developed methodology uses historic vehicle registration data, state-level EV adoption targets, seasonal driving patterns, local demographics, competition, and traffic volume information to predict average station usage. Through Monte Carlo simulations, an average daily load profile is obtained for each month in the planning horizon, and prediction uncertainty is quantified. The proposed framework will facilitate the accurate estimation of energy and demand costs incurred by the charging station over the planning period, thereby informing return-on-investment calculations.

Biswas, Shuchismita

Evaluating a Commercial Dynamic Line Rating Software with the National PMU Dataset

To accelerate the development of data-driven applications for power systems, the Department of Energy (DOE) supported the collection and curation of a synchrophasor dataset spanning two years of observations from transmission utilities across the US. This National PMU Dataset (NPDS) was anonymized and distributed to awardees of a DOE research grant under nondisclosure agreements (NDAs) but has also been retained at PNNL to enable further research. Agreements with data contributors prevent the data from being shared outside the organization. However, establishing a blind research validation methodology is envisioned to maximize the value proposition of the NPDS. In this validation strategy, researchers may share algorithms/software (potentially as executables to protect intellectual property) with PNNL, and PNNL will share feedback about the software’s performance on subsets of the NPDS. Such a blind methodology ensures that sensitive information about critical infrastructure remains protected, but the value of the NPDS can be extended to research beyond PNNL. Through iterative feedback, the algorithms may be tweaked to address real-world artifacts. As the NPDS data is temporally and geographically diverse, it may capture features absent in smaller datasets used during the development of the algorithm under test. This report presents lessons learned from applying the blind validation methodology to LineID™, a synchrophasor-based dynamic line rating software developed by Topolonet Corporation. Improvements made to the software through iterative feedback, limitations of the validation methodology, as well as how the limitations of the NPDS affected the evaluation process are discussed. Observations indicate that the proposed validation methodology can be valuable for evaluating other tools in the future.

97 MATHEMATICS AND COMPUTING

Statistical Performance of Forced Oscillation Detectors in the Presence of Missing Measurements

In bulk power systems, measurement-based monitoring for large oscillations can help maintain system reliability. One of the challenges encountered in a recent field demonstration was the unavailability of measurements due to underlying measurement quality or communication problems. During the demonstration, the oscillation detector ignored a measurement location if even 10 seconds of data was missing. To extend the detector's ability to operate in these conditions, this paper evaluates the impact of three methods for addressing missing data. The strengths and weaknesses of each approach are evaluated using theoretical expressions for the probability of detection along with results from simulated data and publicly available field measurements. Based on these results, a suitable approach is identified that can extend the oscillation detector's performance when large segments of data are missing.

Follum, James D.

Inverter Model Validation and Calibration Using Phasor Measurement Unit Data

As the penetration of inverter-based renewable energy resources increases in the power grid, especially at the distribution and microgrid levels, the need to accurately represent them in planning studies increases as well. However, due to the lack of well-established standard procedures, and vendor reluctance towards the detailed sharing of proprietary models, automated dynamic model validation and parameter calibration tools for inverter based resources (IBRs) remain scarce. This work presents a model validation and parameter calibration platform for representing IBRs with generic phasor-domain models. Phasor measurements of power system events are used for continuous validation using the data playback method, and model parameters are re-calibrated if a significant mismatch between measurements and model response is observed. Unique features of the proposed platform include- (a) an iterative Bayesian optimization approach towards parameter calibration to address a possible mismatch between the structures of generic models implemented in simulation softwares and actual commercial inverters, (b) error metrics designed to account for a possible mismatch between the time resolution of simulation and measurements, and (c) analysis of the measurement-simulation mismatch to provide guidance to engineering personnel regarding model shortcomings. The performance of the platform has been illustrated using both simulated data and field measurements to validate/calibrate inverter models in GridLAB-D.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI

Open Source Synergy: Developing and Validating PMU Data Analysis Techniques Using Open Source Tools and Datasets

This paper presents an exploration into the development and validation of data analysis approaches for Phasor Measurement Units (PMUs) using open-source datasets and tools. Various methods for event detection, event classification, frequency response, and oscillation analysis were tested. We leverage the capabilities of Archive Walker (AW), the Frequency Response Analysis Tool (FRAT), and the Oscillation Baselining and Analysis Tool (OBAT), all open-source tools, for efficient processing and analysis of synchrophasor data. The open-source Transmission Signature Library (TSL) dataset was employed as a dataset for a comprehensive evaluation to assess the performance and reliability of the proposed methods.

PMU, event analysis, oscillation, Frequency Respon

A Data-Driven Exploration of the Impact of Renewable Energy on Inter-Area Oscillations in the U.S. Eastern Interconnection

As increasing amounts of renewable energy (RE) resources are incorporated into the bulk-power grid, power system oscillations are expected to change. This work investigates how RE generation impacts the frequency and damping ratio (DR) of two dominant inter-area modes in the U.S. Eastern Interconnection (EI) using regularly updated estimates collected over a 12-month period. Quantile regression is used to derive the correlation between operating conditions and mode properties, and a bootstrap method is used to quantify the uncertainty associated with the correlation estimates. Results show that with an increase in system load, the frequency of a mode decreases and DR increases. Evidence that increasing RE generation results in an increase in frequency and decline in DR was found for one of the two modes studied. This work shows that increasing RE levels will impact the properties of inter-area oscillations in the EI, but it does not indicate the presence of immediate threats to grid stability. The outlined approach can be used to periodically assess changing mode properties as RE levels continue to grow and flag stability concerns before they become serious reliability threats.

Inter-area oscillation, mode meters, quantile regr