Search NASA⌕ Search

Engineering topics

Blum, David

Publications and source records attributed to Blum, David.

At least 19 records

Optimizing Heat Recovery with Storage: Control Validation and Sensitivity Analysis of the Time-Independent Energy Recovery Plant Using Modelica

Heat recovery in large building central plants saves energy but traditionally requires simultaneous heating and cooling. The Time-Independent Energy Recovery (TIER) plant shifts this paradigm by integrating thermal energy storage (TES) to enable heat recovery regardless of concurrent demand, offering a highly efficient, space-saving solution to achieve California’s energy goals. However, its integration of heat recovery chillers, cooling-only chillers, cooling towers, and trim air-source heat pumps (ASHPs) creates growing control and sizing complexity. To overcome this, this study employs high-fidelity Modelica dynamic simulation to validate TIER control sequences and optimize equipment sizing. We translated the written Sequences of Operation into executable Control Description Language (CDL) to test logic against sub-hourly loads. This verification workflow successfully identified and resolved critical vulnerabilities, such as thermal storage freezing and equipment short-cycling, in a virtual environment prior to physical deployment. Then, the study analyzes TIER plant performance across three simulated building types in three locations, and a real building load profile, ensuring variety in heating and cooling loads, and simultaneity factors and explores sizing rules for the TES and ASHP capacity. The analysis shows that the TIER plant operates equipment efficiently leading to a plant SCOP of around 7.5 across all scenarios, higher than a traditional ASHP plant, and a viable pathway to de-risk complex system design and control through simulation to identify optimal designs that maximize energy efficiency, minimize operational costs, and ensure robust operation in varied environmental conditions, thereby facilitating the broader adoption of such a solution for large buildings.

Zanetti, Ettore↗

Digitizing Today’s Buildings in the Real World: Lessons from Field Demonstrations

Digital twins, created by generating a virtual replica of a building, enable safe evaluation of operational scenarios and applications like fault detection and diagnosis and advanced controls. However, a prerequisite is the creation of a machine-readable digital representation of a building, currently hindered by fragmented information scattered across mechanical drawings, point lists, and natural language sequences. As a result, digital twin development remains labor-intensive, error-prone, and difficult to validate. To address these challenges, two efforts from ASHRAE aim to support the digitalization of buildings. ASHRAE s223 establishes a semantic model of buildings, representing system components, configuration, and data sources. ASHRAE s231 defines a vendor-neutral programming language for expressing their control logic. As the industry evaluates implementing them in their products, understanding the challenges that vendors and implementers may face is crucial. In this paper, we present findings and lessons learned from field demonstrations in five buildings that implemented control applications using ASHRAE s223 and s231. The demonstrations highlight how semantic modeling and formalized control descriptions can significantly reduce software development time, manual point mapping, and hard-coding. Beyond time efficiency, they enable reliable automation by minimizing human interpretation and providing a means for consistency across projects. We describe the processes and best practices for model creation and model usage, from translating heterogeneous building documentation into semantic representations to implementing control logic in real-world systems. Finally, we discuss the challenges that persist, including integration with legacy software environments, gaps in interoperability, and the level of expertise still required to effectively leverage semantic models.

Prakash, Anand Krishnan↗

Prime Time for Model-Predictive Control? Assessing the Technical and Market Readiness of Advanced Controls in Buildings

Despite three decades of extensive research and field testing that have consistently validated the benefits of Model Predictive Control (MPC) in building applications, the technology has seen limited market adoption. This paper evaluates the readiness of MPC for widespread deployment, showcases recent demonstrations and field tests across diverse building types, including residential, small commercial, large commercial, and campus settings. Our results demonstrate that MPC can optimize system operations to achieve load shifting, minimize curtailment of on-site generation, and reduce energy costs by up to 80 %, while maintaining or improving occupant comfort. We also show that MPC can effectively control large assets, such as MW-sized thermal storage systems, and respond to dynamic pricing signals. However, achieving scale remains difficult due to labor-intensive workflows, reliance on a “PhD-in-the-loop” for MPC design and maintenance, susceptibility to fragile data infrastructure, and persistent workforce education and acceptance barriers. To bridge this gap, we outline a transition from bespoke, labor intensive prototypes toward streamlined, segment-targeted deployment strategies that leverage model templates, semantic tools, and generative AI. By automating control configuration and reducing engineering effort, these recommendations provide a pathway for transforming successful research demonstrations into scalable, market ready solutions for MPC-based controls.

Pritoni, Marco↗

Commercial building HVAC demand flexibility with model predictive control: Field demonstration and literature insights

Model Predictive Control (MPC) for building Heating Ventilation and Air Conditioning (HVAC) systems is beginning to gain traction in the market, with a few controls companies incorporating it into their product offerings. However, it remains difficult to assess whether the energy cost savings are enough to justify the cost of MPC implementation for a particular building, given the limited number of reported demonstrations. For small commercial and residential buildings with relatively uniform systems, standardized approaches can help lower implementation costs. In contrast, for large buildings or district systems, the potential magnitude of cost savings could justify more customized solutions. Estimating the cost-effectiveness of MPC becomes more challenging for medium and large commercial buildings, where a one-size-fits-all solution may not be suitable, and the potential energy cost savings may be insufficient to justify a customized solution. To make MPC technology more appealing, incorporating additional value streams beyond energy efficiency alone can significantly increase its attractiveness. One such revenue stream is demand flexibility, in response to dynamic electricity prices, where MPC can leverage the thermal mass of the building to shift the load and support the grid. Building on an extensive literature review of MPC field studies focused on cost savings and demand flexibility, this paper presents the results of implementing MPC control in a large office building HVAC system in Berkeley, CA. Four different dynamic electricity price profiles were integrated into the MPC objective function to shift building demand while maintaining comfort, and field testing was performed with each price profile across four seasons. The results show potential for 40–65 % demand decrease percentage and up to 61 % annual cost savings compared to the existing rule-based control strategy, under the tested dynamic price scenarios. This paper also presents a sensitivity analysis on the cost savings with respect to the price profile variability, discusses the implementation effort for the price-responsive MPC, and compares the cost savings found in this study to those found in literature on the basis of dynamic price variability, or so-called Electricity Price Relative Standard Deviation.

Zanetti, Ettore↗

IBPSA Project 2 BOPTEST: An update on the test cases available in the framework for testing advanced control strategies in buildings

Project 2 develops software infrastructure, test cases, and extensions for the Building Optimization Testing Framework (BOPTEST) to address the expanding needs of building and urban energy system controls through open international collaboration. This paper provides an overview of the new test cases available as of BOPTEST version 0.7.1. Each test case is developed using open-source Modelica libraries and Spawn of EnergyPlus, enabling the creation of high-fidelity building models that incorporate envelope dynamics, Heating Ventilation and Air Conditioning (HVAC) systems, and explicit control representations. Currently, eight test cases are available, with five additional cases under development. These test cases cover a wide range of climates, building types, and HVAC systems. This paper compiles and summarizes test case descriptions, cites original manuscripts that developed them for a more detailed description, and reports baseline control performance metrics. Furthermore, two example applications are presented: one illustrating different levels of control, from supervisory to low-level, and another demonstrating how Model Predictive Control (MPC) solutions must be adapted from continuous to integer to control some building actuators.

Zanetti, Ettore↗

BOPTEST as a Platform for Building Controls and Grid-Interactive Buildings Workforce Training

Building automation and controls are becoming increasingly complex with the emergence of Grid Integrated Efficient Buildings (GEBs) as well as new highly efficient sequences of operation and data-driven control schemes. However, there remains a significant gap in hands-on training opportunities for building operators and technicians to gain practical experience with advanced control systems in a low-risk environment. This paper presents BOPTEST (Building Optimization Performance Test) as a suitable platform for workforce training in building controls and GEB technologies. BOPTEST provides a suite of standardized building simulation test cases with a REST API, real-time control interfaces through BACnet, semantic models connecting users to building data, and built-in calculation of control metrics and performance indicators. The platform enables trainees to interact with virtual buildings using industry-standard protocols while learning how to implement and innovate control strategies. The training platform is designed to offer a structured and interactive learning experience for building engineers, helping them effectively develop, learn, and retain skills in fault identification, troubleshooting, and correction. The workflow is divided into three main phases: 1) Setup, 2) Exercise, and 3) Review, each comprising specific activities performed by either the instructor or the student. Initial pilot training sessions have yielded positive feedback from instructors and participants and demonstrates that BOPTEST effectively fills an industry need for a low-risk training resource via simulation of real building control systems, allowing trainees to gain practical experience before working in the field. The platform's ability to provide immediate performance feedback while maintaining familiar industry interfaces makes it particularly suitable for workforce development programs. This work provides a replicable model for leveraging building simulation in control education and training.

Paul, Lazlo↗

BOPTest As a Platform for Building Controls and Grid-Interactive Buildings Workforce Training

Building automation and controls are becoming increasingly complex with the emergence of Grid Integrated Efficient Buildings (GEBs) as well as new highly efficient sequences of operation and data-driven control schemes. However, there remains a significant gap in hands-on training opportunities for building operators and technicians to gain practical experience with advanced control systems in a low-risk environment. This paper presents BOPTEST (Building Optimization Performance Test) as a suitable platform for workforce training in building controls and GEB technologies. BOPTEST provides a suite of standardized building simulation test cases with a REST API, real-time control interfaces through BACnet, semantic models connecting users to building data, and built-in calculation of control metrics and performance indicators. The platform enables trainees to interact with virtual buildings using industry-standard protocols while learning how to implement and innovate control strategies. The training platform is designed to offer a structured and interactive learning experience for building engineers, helping them effectively develop, learn, and retain skills in fault identification, troubleshooting, and correction. The workflow is divided into three main phases: 1) Setup, 2) Exercise, and 3) Review, each comprising specific activities performed by either the instructor or the student. Initial pilot training sessions have yielded positive feedback from instructors and participants and demonstrates that BOPTEST effectively fills an industry need for a low-risk training resource via simulation of real building control systems, allowing trainees to gain practical experience before working in the field. The platform's ability to provide immediate performance feedback while maintaining familiar industry interfaces makes it particularly suitable for workforce development programs. This work provides a replicable model for leveraging building simulation in control education and training.

Paul, Lazlo↗

Field Performance of Commercial Building Load Flexibility Using Model Predictive Control

Model Predictive Control (MPC) applied to buildings is starting to see some commercial adoption by companies. However, it is hard to estimate if relative energy cost savings are enough to justify the cost of MPC implementation with few reported demonstrations. In small commercial and residential buildings, a one size-fits-all solution can help reduce implementation costs, while in very large buildings or districts the potential energy cost savings magnitude can cover more tailored solutions. This estimation becomes harder for medium to large commercial buildings, where a one-size-fits-all solution cannot be adopted and potential energy cost savings might not be sufficient to cover a tailored solution. Therefore, value propositions in addition to energy efficiency alone can make MPC technology more attractive through additional energy cost savings. One such value proposition is load shifting in response to dynamic electricity prices. On this aspect, MPC is a key technology to unlock building thermal mass for energy flexibility in response to electric grid conditions. This study shows the experimental results of MPC control of an office building in Berkeley, where different dynamic electricity price profiles were used in the MPC objective function to shift the building load and to calculate hypothetical electricity costs. Results show potential 50% cost savings with respect to the existing controller with the dynamic price scenario.

Zanetti, Ettore↗

Control development and sizing analysis for a 5th generation district heating and cooling network using Modelica

5th generation district heating and cooling system (5GDHC) are a relatively new concept. They use a single district loop near ambient temperature to provide heating and cooling. This paper improves on the modelling and control of a 5GDHC system called the reservoir network. The study updates the sewage heat exchanger plant model to more realistically represent seasonal changes, uses refined pump models with variable efficiency, introduces a ground coupled district pipe model to consider the inertia of the district network and implements a new control strategy for geothermal storage and sewage heat exchanger. The new approach reduced operating costs, mainly due to pumping cost for storage, sewage heat exchanger plant and distribution pump, while increasing the overall robustness of the approach in different sizing conditions. Thanks to the new controller, the pumping consumption was reduced by 21% with respect to the original baseline. Furthermore, the new control makes the system take better advantage of design changes, when reducing borehole field size and increasing the sewage heat exchanger size, the pumping energy savings become 29% with respect to the original baseline. Lastly, borehole field temperature stability was analyzed through 40 years of simulation.

Zanetti, Ettore↗

Fan and Pump Efficiency in Modelica based on the Euler Number

Simulation programs often assume constant hydraulic efficiency for fan or pump models when performance curves are unavailable. This is inaccurate because the hydraulic efficiency varies with the operation condition. It therefore consistently underestimates the power draw at off-design conditions at which the hydraulic efficiency drops. Use of a modified Euler number allows computing the hydraulic efficiency and shaft power with limited data. Others showed the validity of the modified Euler number for fan efficiency calculations. We show that it is also applicable for pumps, and present its implementation in Modelica for a fan or pump model. Here, the only input required from the user is one data point at which the hydraulic efficiency is at its maximum. The reported method is applicable regardless of the type, size, or operational region of the fan or pump. Across a sample of eighteen sets of pump data and seven sets of fan data, the errors of the computed power from interpolated data were within 15% for the range of 20% - 70% of maximum flow rate and 40% - 90% of maximum pressure rise, excluding outliers.

component model↗

SolarPlus-Optimizer v0.1

With the falling costs of solar arrays and battery storage and reduced reliability of the grid due to natural disasters, small-scale local generation and storage resources are beginning to proliferate. However, very few software options exist for integrated control of building loads, batteries and other distributed energy resources. The available software solutions on the market can force customers to adopt one particular ecosystem of products, thus limiting consumer choice, and are often incapable of operating independently of the grid during blackouts. In this software package, we present the "Solar+ Optimizer" (SPO), a control platform that provides demand flexibility, resiliency and reduced utility bills, built using open-source software. SPO employs Model Predictive Control (MPC) to produce real time optimal control strategies for the building loads and the distributed energy resources on site. SPO is designed to be vendor-agnostic, protocol-independent and resilient to loss of wide-area network connectivity. The software was evaluated in a real convenience store in northern California with on-site solar generation, battery storage and control of HVAC and commercial refrigeration loads. Preliminary tests showed price responsiveness of the building and cost savings of more than 10% in energy costs alone.

Prakash, AnandKrishnan↗

Towards Digital and Performance-Based Supervisory HVAC Control Delivery

Upgrading supervisory HVAC control in commercial buildings is one of the most attractive decarbonization tools at our disposal. Modern controls are software programs and can in theory be deployed at scale and with a low up-front carbon "pulse". In practice, however, control delivery is a disjointed and inefficient process, dominated by manual handoffs of imprecise English language documents. A particularly high barrier exists between control implementation and building energy modeling (BEM) which results in control sequences typically not being tested for correctness or performance before implementation. Together with industry partners, DOE and the national labs are developing an ecosystem of tools and standards that can support fully digital performance-based control delivery workflows. This paper describes this ecosystem, which consists of three mutually supportive efforts. Semantic models of buildings and their systems enable automatic configuration and installation of control software. Platform-neutral control descriptions separate control algorithms from control platforms and enable the creation of libraries of reference control implementations. Dynamic whole-building energy-control simulation that can execute physically realistic control sequences makes it possible to test and evaluate the performance of control sequences and then directly compile them for installation and execution in control systems. In addition to digitizing and streamlining project-level control delivery, these standards and related software support benchmarking of control algorithms, both rule-based and optimization-based, and help to both advance the state of the art and to implement ratings and programs that encourage the adoption of high-performance control.

building controls↗

Heat Pumps with Phase Change Thermal Storage: Flexible, Efficient, and Electrification Friendly

As we continue to electrify space- and water-heating, the electricity demand profile of many buildings will change significantly, and periods of high electricity demand will likely not align with renewable energy generation. We expect electricity demands will increase substantially in the winter, annual maximum electricity demands will increase, and more regions will experience annual peak electrical demands – and higher wholesale electricity prices – in the winter. This is especially important for cold climates where 60% of site energy use in buildings is for heating, and where heat pumps perform least efficiently. This paper focuses on one promising solution among the many paths to electrification: the use of phase change materials (PCM) for compact low-cost thermal energy storage (TES). We present the design and simulation of a combi heat pump and phase change thermal storage system used for space- and water-heating in a multifamily residence in a cold climate. To assess the benefits of this technology, we compare its annual performance to that of a current state-of-the-art air-to-air heat pump and separate heat pump water heater. Simulation results for IECC Climate Zone 6A reveal that the combi heat pump with phase change thermal storage can reduce the design size for heat pumps by 40-60%, reduce maximum electric demand by 30-50%, reduce electricity use during 4-12-hour load shed periods by 50%, and avoid the need for auxiliary electric resistance for both space- and water-heating. Tariff structures are highly varied between different utilities and currently reflect higher wholesale market prices for electricity during summer days. Consequently, although this system design provides large electric demand reductions during hypothetical 4-12-hour load shed periods, it does not provide energy cost reductions with current winter residential time-of-use tariffs.

Helmns, Dre↗

Model predictive control for demand flexibility: Real-world operation of a commercial building with photovoltaic and battery systems

Hundreds of studies have investigated Model Predictive Control (MPC) for the optimal operation of building energy systems in the past two decades. However, MPC field tests are still uncommon, especially for small- and medium-sized commercial buildings and for buildings integrated with onsite renewables. This paper describes the implementation and the long-term performance evaluation of an MPC controller in a small commercial building equipped with behind-the-meter photovoltaics and electrochemical batteries. MPC controls space conditioning, commercial refrigeration, and the battery system. We tested two types of demand flexibility applications in the field: electricity bill minimization under time-of-use tariffs and responses to grid flexibility events. Results show that the proposed controller achieves 12% of annual electricity cost savings and 34% peak demand reduction against the baseline, while respecting thermal comfort and food safety. The field tests also demonstrate the ability of the MPC controller to provide a multitude of grid services including real-time pricing, demand limiting, load shedding, load shifting, and load tracking, using the same optimization framework.

29 ENERGY PLANNING, POLICY, AND ECONOMY↗

Field demonstration and implementation analysis of model predictive control in an office HVAC system

Model Predictive Control (MPC) is a promising technique to address growing needs for heating, ventilation, and air-conditioning (HVAC) systems to operate more efficiently and with greater flexibility. However, due to a number of factors, including the required implementation expertise, lack of high quality data, and a risk-adverse industry, MPC has yet to gain widespread adoption. While many previous studies have shown the advantages of MPC, few analyzed the implementation effort and associated practical challenges. In addition, previous work has developed an open-source, Modelica-based tool-chain that automatically generates optimal control, parameter estimation, and state estimation problems aimed at facilitating MPC implementation. Therefore, this study demonstrates usage of this tool-chain to implement MPC in a real office building, discusses practical challenges of implementing MPC, and estimates the implementation effort associated with various tasks in order to inform the development of future workflows and serve as an initial benchmark for their impact on reducing implementation effort. This study finds that the implemented MPC saves approximately 40% of HVAC energy over the existing control during a two-month trial period and that tasks related to data collection and controller deployment activities can each require as much effort as model generation.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Site demonstration and performance evaluation of MPC for a large chiller plant with TES for renewable energy integration and grid decarbonization

Thermal energy storage (TES) for a cooling plant is a crucial resource for load flexibility. Traditionally, simple, heuristic control approaches, such as the storage priority control which charges TES during the nighttime and discharges during the daytime, have been widely used in practice, and shown reasonable performance in the past benefiting both the grid and the end-users such as buildings and district energy systems. However, the increasing penetration of renewables changes the situation, exposing the grid to a growing duck curve, which encourages the consumption of more energy in the daytime, and volatile renewable generation which requires dynamic planning. The growing pressure of diminishing greenhouse gas emissions also increases the complexity of cooling TES plant operations as different control strategies may apply to optimize operations for energy cost or carbon emissions. This paper presents a model predictive control (MPC), site demonstration and evaluation results of optimal operation of a chiller plant, TES and behind-meter photovoltaics for a campus-level district cooling system. The MPC was formulated as a mixed-integer linear program for better numerical and control properties. Compared with baseline rule-based controls, the MPC results show reductions of the excess PV power by around 25%, of the greenhouse gas emission by 10%, and of peak electricity demand by 10%.

29 ENERGY PLANNING, POLICY, AND ECONOMY↗

A three-year dataset supporting research on building energy management and occupancy analytics

Abstract This paper presents the curation of a monitored dataset from an office building constructed in 2015 in Berkeley, California. The dataset includes whole-building and end-use energy consumption, HVAC system operating conditions, indoor and outdoor environmental parameters, as well as occupant counts. The data were collected during a period of three years from more than 300 sensors and meters on two office floors (each 2,325 m 2 ) of the building. A three-step data curation strategy is applied to transform the raw data into research-grade data: (1) cleaning the raw data to detect and adjust the outlier values and fill the data gaps; (2) creating the metadata model of the building systems and data points using the Brick schema; and (3) representing the metadata of the dataset using a semantic JSON schema. This dataset can be used in various applications—building energy benchmarking, load shape analysis, energy prediction, occupancy prediction and analytics, and HVAC controls—to improve the understanding and efficiency of building operations for reducing energy use, energy costs, and carbon emissions.

24 POWER TRANSMISSION AND DISTRIBUTION↗