Data Collection and Analysis [Slides]
The report summarizes the ongoing data collection as well as selection and analysis of field events based on measurement data from project partners.
Engineering topics
Publications and source records attributed to Boemer, J..
The report summarizes the ongoing data collection as well as selection and analysis of field events based on measurement data from project partners.
This report presents the success merits, logic design details, and test plans for adaptive protection schemes for microgrids, secondary distribution networks, and radial distribution feeders. Success merits are presented in terms of challenges and issues which should be mitigated. The challenges and issues were identified during site-specific simulations and analysis presented in a prior report. The adaptive protection logic designs are presented in a vendor-neutral manner to make them readily adaptable to site--specific protection relays and controllers which support custom logic design. Vendor-specific implementations of the logic for the adaptive protection laboratory tests are also presented. The final section of the report presents details of the testing methodology, plans, and documentation for each of the three adaptive protection schemes.
This report investigates the response of the inverter under different terminal voltage and operating conditions. The goal is to understand the control objective of the inverter (e.g., injection of reactive current for voltage dips) based on the inverter’s response. No attempt is made to determine the exact control algorithms implemented in the inverter.
This report proposes a generic model specification of a photovoltaic inverter applied in transmission-connected plants for implementation in an electromagnetic transients simulator. The model specification contains the necessary control loops to meet the fault ride-through performance requirements in the IEEE 2800-2022 standard. The report details the implementation and example parameterization of the model in PSCAD™. Simulation results verify the model meets the performance requirements. Comparisons of the model’s response to laboratory test measurements of a commercial 2.2 MVA storage inverter show the model can reasonably predict the response of commercial equipment.
The report summarizes the ongoing data collection as well as selection and analysis of field events based on measurement data from project partners.
The report summarizes the laboratory testing results of a 33kW string inverter. The inverter is a legacy inverter and does not have the capabilities required in IEEE 1547 2018.
EPRI formed a working group of utilities and software vendors called the Distribution Advanced PV Model Working Group (DAWG). The working group has been focused on building consensus regarding the models that represent the reactive power capabilities outlined in Section 5 of IEEE Std 1547™-2018. This report provides an overview of the reactive and active power capabilities specified in IEEE Std 1547™-2018 and outlines a specification of key functions for usage during steady state snapshot and time series power flow analysis. Additionally, it presents a framework for performing tests to verify the correct operation of functions during power flow analysis.
This report provides a comprehensive overview of adaptive protection schemes in use by distribution systems for protection, switching and control on their systems. A significant focus is placed on how existing schemes can be impacted by increasing penetrations of DER as well as how these schemes can enable DER penetrations to increase. EPRI have conducted a survey of member utilities and performed a comprehensive literature review with the goal of baselining the research and identifying gaps with a focus on the issues that were encountered with adaptive protection on real systems. The five adaptive protection applications that are most prevalent on systems today are discussed in detail. These are weather-based fuse-saving, adaptive protection to reduce short-circuit current, adaptive protection for DER, adaptive protection for microgrids, and distribution automation. A broad overview of the technology is given for each scheme. Issues that have been encountered by utilities are highlighted and the safety and reliability impacts are also examined. As distribution systems, intelligent electronic devices, grid equipment and distribution management systems are rapidly evolving, adaptive protection techniques and technologies will become more widely adopted. This report proposes a framework for a conceptual automatic adaptive protection system. EPRI have ongoing research, development and demonstration projects in all of the constituent elements, however challenges remain to link the elements together in a secure and reliable way. EPRI will continue research into automated adaptive protection applications and challenges for the systems of today and future applications to assist system operators in managing the evolving system.
This report identifies the needed parameters and dynamic characteristics that will determine the test plan.
This report documents the PV and dynamic load modeling update for transient stability, EMT, harmonics, and short circuit analyses during budget period one of the DOE PV-MOD research.
This report develops guidance for monitoring, collection, and selection of field measurements for model validation.
This report identifies the needed parameters and dynamic characteristics that will determine the test plan.