Test results from a comparative evaluation of a condensation nuclei fire detector
The fire/smoke alarm response of a condensation nuclei fire detector (CNFD) was compared with photoelectric and ionization detectors. Tests were conducted in a former control room 8.5 m by 8.9 with a 2.7 m ceiling. The room had air supplied from above the ceiling and under the floor with return air exiting from ceiling grills. The environment was varied from 278 to 305 K and relative humidities from 8 to 65%. Four detection zones were located in the room. Each zone contained a sampling head for the CNDF, a photodetector, and an ionization detector so that each detector system had four opportunities to alarm during tests. The particle level in the test room was also monitored during tests with a condensation nuclei particle counter. The CNFD responded to 90% of exposures to smoldering plastic and 84% of exposures to visible fire. The photoelectric response was 43 and 12.5% respectively for the same conditions. The ionization response was 9 and 48 respectively.