Search NASA⌕ Search

Engineering topics

Chowdhury, Vikram Roy

Publications and source records attributed to Chowdhury, Vikram Roy.

Use of Grid-Forming Medium-Voltage Power Electronics Hub in a Microgrid Setting

This paper presents the application of a new design of a multiport, modular, medium-voltage power electronics hub (M3PE-HUB) in a microgrid setting. The M3PE-HUB system was modeled in a digital real-time simulator (DRTS) and integrated into the Banshee microgrid test system. This paper presents the preliminary DRTS simulation-based results of the M3PE-HUB system connected in a test microgrid system. Verification and validation of the M3PE-HUB architecture and controls in the test microgrid setting are the primary contributions of this work. The results of the operation during the islanding and resynchronization process indicate the feasibility of the proposed architecture in a microgrid setting. This paper also presents results for a system reconfiguration use case where the M3PE-HUB was used to reconfigure the system under a fault condition.

grid forming↗

A Self-Organizing Nano Grid (SONG) for Energy Access Clusters

In this paper, a bottom-up dc Self-Organizing Nano Grid (SONG) for rural electrification at ultra-low-cost through a flexible and scalable topology is presented. The proposed nano grid requires no communication and uses dc-bus signaling to convey excess energy in the system through the bus voltage, allowing independent agents to conduct energy transactions based on their needs in a decentralized manner. Moreover, this article proposes a concept that uses a novel multi-source, multi-segment droop control strategy with demand coordination, allowing for dynamic self-balancing of the system under fluctuating operating conditions. The unique use of a surplus photovoltaic (PV) power droop mode precisely estimates energy availability to minimize load chattering that helps in stabilizing the dc-bus. In addition, this architecture uses standard dc/dc converters for a low-cost, modular, Plug and Play ( PnP ) solution with highly automated operation, enabling local assembly, operation, and maintenance by non-technical personnel. The proposed SONG concept was validated in simulation and with a 700W, laboratory-scale, custom made nano grid system. The simulation and experimental test cases show the feasibility of the SONG system by demonstrating the proposed multi-source, multi-segment droop control strategy without load chattering under varying operating conditions.

dc-dc converter↗

Adaptive Internal Model Based Current Control with Embedded Active Damping of a Three-Phase Grid-Connected Inverter with LCL Filter for PV Application

This paper presents an internal model based controller with embedded active damping for a three-phase grid-connected inverter with LCL filter. A strategy to control the grid current based on the internal model principle is presented in this paper. It is known that a third-order LCL filter apart from providing better attenuation also poses the problem of initiating unwanted resonance oscillations especially during transients. To address this problem, an active damping strategy based on virtual resistance emulation on the grid side filter is implemented. Also, to ensure effective active damping, an online parameter update strategy is implemented for the filter parameters. The proposed method provides better attenuation to oscillation damping and achieves good tracking performance without adversely affecting the bandwidth. The architecture is verified based on computer simulations via MATLAB/Simulink and PLECS domain and various important case study results are presented.

grid-connected inverter↗

A Nonlinear Direct Power Controller for a Three-Phase Grid-Connected Inverter with Online Parameter Update for PV Application

This work proposes a nonlinear direct power controller for a three-phase grid-connected inverter for photovoltaic application. Grid-connected converters for solar applications require advanced control architectures to ensure optimal operation and extraction of maximum power from the photovoltaic arrays. Therefore, to ensure this, a nonlinear power controller architecture has been proposed to extract the maximum power from the solar arrays and to achieve the most optimal operation. To further improve the performance, a parameter update scheme has been utilized which is based on model reference adaptive system. The latter helps to accomplish not only good dynamic response but also excellent tracking performance. The overall control come estimation architecture is verified based on computer simulations via MATLAB/Simulink and PLECS domain and various important case study results are presented.

direct power control↗

Control and Grid Support Function Evaluation for a Three-Phase Back-to-Back Modular Multilevel Converter System

This paper focuses on the evaluation of advanced inverter controls for a 500kW back-to-back (B2B), silicon carbide, multilevel modular converter (MMC) used as a direct-connected medium-voltage grid intertie. A decentralized hierarchical controller architecture for the MMC system is presented, which uses the main controller to implement higher level grid interconnection functions per the IEEE 1547–2018 standards and the local controllers to execute lower level closed-loop functionality of the MMC stages. This paper presents and elaborates on the grid functionalities are elaborated and presented. The back-to-back converter system is equipped with local controllers and their corresponding functionalities are presented. Case study results for the corresponding functionalities presented show the effectiveness of the proposed architecture. To enhance the operation capabilities of the system, a parameter update scheme has been implemented and utilized in unison with the controller.

decentralized control↗

Operation and Control of Soft Switching Solid State Transformer as a Virtual Synchronous Machine for Photovoltaic Application

Possibility for control and operation of a three-phase solid state soft switching transformer based as a virtual synchronous machine or synchronverter has been investigated in this paper. The soft switching solid state transformer is used as an interface between the ac grid and a photovoltaic power generation unit supported by a battery bank. The control architecture investigated in this paper is that of a synchronverter to achieve inertial support to the grid and local loads. The operation of the soft switching solid state transformer has also been investigated as a V S M during unbalanced/distorted grid voltage condition. Control objective to achieve oscillation free power transfer between the ports (photovoltaic, battery and grid) has been achieved. The presented architecture has been verified for several important case studies via numerical simulations based on MATLAB/Simulink domain.

grid current controller↗

Internal Model-Based Active Damping Strategy for a Back-to-Back Modular Multilevel Converter System for Advanced Grid Support: Preprint

The proposed work focuses on the possibility of achieving the reduction in the size of the interfacing filter for the grid connection for a back-to-back modular multilevel converter system with the use of third order LCL filters. To achieve the same attenuation, it is possible to reduce the size of the interfacing filters by the usage of third order filters. However, this kind of filtering comes with the limitation of having sustained oscillations due to lack of damping especially during transient changes. Therefore, in this work, a methodology has been proposed based on the principle of internal model to cater for this unwanted oscillations. The third order system is modeled inside the microcontroller with the damping enabled. The error between the output from the model and the actual are compared and the error is utilized to accomplish the active damping strategy. The proposed architecture is verified via computer simulations based on MATLAB/Simulink domain and various case study results along with their discussion is presented in this paper.

dq control↗

A Tri-Port Current-Source Soft-Switching Medium-Voltage String Inverter for Large-Scale Solar-Plus-Storage Farms

This article presents a tri-port current-source soft-switching medium-voltage string inverter (TMVSI) to reduce the Levelized cost of energy (LCOE) of large-scale solar-plus-storage (SPS) farms. Throughout this work, the topology, operating principle, circuit simulation, control, and hardware design of the TMVSI are introduced. In addition, three key challenges compromising the performance of the TMVSI are addressed in this article. First, a new feed-forward compensation for model predictive control of the TMVSI is proposed to compensate for sampling and computational delay and high dc-link ripple with low computational cost and high scalability. Second, the use of laminated permanent magnets is proposed to reduce the losses of the MV medium-frequency transformer (MFT) in the TMVSI while increasing its saturation current. Finally, an improved U-shape winding pattern is proposed to decrease the leakage inductance of the MV MFT and reduce the voltage stress across semiconductor switches without adding cost or complexity. Here, the effectiveness of the TMVSI is validated by experiments at up to 20kW/500V in different test cases with custom-built prototypes. The contributions of this work make the TMVSI a viable solution to SPS farms and unleash its potential for LCOE reduction.

14 SOLAR ENERGY↗

Farm-level Interactions Study of a Novel Tri-port Soft-switching Medium-Voltage String Inverter (MVSI) based Large-scale PV-Plus-Storage Farms

A medium-voltage photovoltaic power conversion unit supported by battery based on a novel topology of soft switching solid state transformer is presented in this paper. It can reduce the Levelized Cost of Energy (LCOE) of PVS farm in an extended degree. However, its capability to provide grid-support services, such as frequency response, reactive power support, etc, have not been demonstrated. A series/parallel combination of these modules form a large 20 MVA solar farm. To validate them with reduced computation burden, a small-signal model of MVSI is firstly derived and validated in this paper. The model has been validated to match the full-switch model in both steady-state and dynamic conditions. Next, a farm-level simulation based on the proved small-signal model was implemented to demonstrate grid-support services. Real irradiation date from NREL is used to show the operational capabilities of the system. As a result, the overall farm is simulated based on MATLAB/Simulink domain to check the performance for various cases namely: power transfer from dc-ac side, reactive power support during grid voltage sag and utilization of battery during grid voltage disturbance or partial shading over PV panels.

14 SOLAR ENERGY↗

Solid-State Transformer and Hybrid Transformer With Integrated Energy Storage in Active Distribution Grids: Technical and Economic Comparison, Dispatch, and Control

Solid-state transformer (SST) and hybrid transformer (HT) are promising alternatives to the line-frequency transformer (LFT) in smart grids. The SST features medium-frequency isolation, full controllability for voltage regulation, reactive power compensation, and the capability of battery energy storage system (BESS) integration with multiport configuration. The HT has a partially-rated converter for fractional controllability and can integrate a small BESS. Fast grid-edge voltage fluctuations from increased solar photovoltaic (PV) and electric vehicle (EV) penetration are difficult to manage for mechanical load tap changers. Hence, along with the trend towards more BESS in the grid, the controllability and the storage integration capability of the SST and HT are of strong interest. However, a review of literature shows existing SST and HT research is mostly at converter level, while system-level assessments are scarce. Assessing technical and economic impacts is critical to understanding the benefits and role of the SST and HT to guide future research, which is presented for the first time in this article. Experimental results from medium-voltage (MV) SST and MV HT prototypes are shown to confirm equipment-level feasibility, where the voltage controllability waveforms of a MV HT prototype are reported for the first time. Comparative simulations are performed on a modified IEEE 34-bus system. Here, a grid-model-less decentralized grid-edge voltage control method and a day-ahead BESS dispatch method are proposed for the SST and HT. The simulations show that the SST and HT with integrated storage can host more PV, achieve peak shaving, mitigate voltage fluctuation and reverse power flow, and support energy arbitrage for operational cost reduction, as compared to the LFT. Moreover, comprehensive analyses of net present value (NPV) and internal rate of return (IRR) are performed under different installed PV capacities, HT’s partial converter ratings, and BESS capacities. Sensitivities to future cost reductions of the PV and BESS are studied. Although the NPV and IRR are currently negative, 60% capital cost reduction or 150% revenue increase will make the SST and HT economically viable in the use case studied.

14 SOLAR ENERGY↗

A Multiport DC Transformer to Enable Flexible Scalable DC as a Service

The rapid adoption of new DC loads and sources, including photovoltaic arrays, DC fast charging of electric vehicle, battery energy storage and data centers, requires a large amount of DC power conversion. A majority of new deployments also necessitate the integration of multiple DC loads and sources at one site. The traditional approach to serve these new applications relies on multiple standard power converters, each dedicated to a source or load, and results in highly customized systems, with challenging control coordination, complex protection strategies, and poor scalability. Instead, this paper proposes the concept of a multiport DC transformer (MDCT) as a modular building block for realizing a flexible, scalable DC as a Service system and address this rapidly growing need. The MDCT uses the S4T to achieve very tight control of cycle-by-cycle energy exchange between multiple ports, with high efficiency. A single multiport converter replaces 4-6 distinct converters, integrates all energy flows and manages protection. As a result, a new layered control architecture is introduced to ensure stability and scalability of the MDCT, with multiple S4T power converter building blocks connected in parallel to realize a fully modular system and reach the target power levels.

30 DIRECT ENERGY CONVERSION↗