METSiCloPs in Cooling Tower Water, Final Presentation: Water Treatment at FSI [Slides]
Motivation: According to current projections, FSI could require anywhere from 83-288 MGY of water. Reducing excessive dependence on external water supply by making operations as water-lean as possible in the face of water availability fluctuations seasonally. The amount of Silica occurring naturally in New Mexico is several multiples higher than most of the country, with average values of 90 ppm, but reaching as high as 113 ppm. Since its saturation concentration at ambient temperatures is about 150 ppm, this corresponds to cycles of concentration as low as 1-2 for untreated water in cooling towers (i.e., the water is circulated through the towers only once or twice before they are dumped into the outfall), thereby making operations highly water intensive. There is, therefore, there is a strong need and internal motivation to remove Silica from the water that is circulated in the cooling towers.