Performance Analysis of High-Temperature Heat Pumps with Two-Phase Ejectors

A two-phase ejector recovers the energy in the refrigerant cycles’ throttling process, improving the coefficient of performance (COP) of high-temperature heat pumps (HTHPs). This study investigated the effects of the mixing pressure on the performance of two-phase ejectors and ejector-assisted HTHPs. A 1D theoretical model of a two-phase ejector was built to predict the internal fluid dynamics and evaluate ejector performance. A thermodynamic model of an ejector-assisted HTHP was built to evaluate the COP of HTHPs and the volumetric heating capacity of low-global warming potential refrigerants. The results demonstrate that an optimum mixing pressure in a two-phase ejector provides the best performance of a two-phase ejector and ejector-assisted HTHP. The optimum mixing pressure was slightly lower than the evaporation pressure. At this pressure, the two-phase flow in the ejector was subsonic. For ejector-assisted HTHPs using low–global warming potential refrigerants at a sink temperature of 120°C, temperature lift of 40°C, and subcooling of 10°C, a two-phase ejector has an average ejector efficiency of 0.334, and the COP and volumetric heating capacity were improved by 7.2% and 7.3%, respectively.

Wang, Pengtao↗

Exploration of Heat-Driven Ejector High-Temperature Heat Pumps

Heat-driven ejector heat pumps use a supersonic ejector as a thermo-compressor to replace the mechanical compressor. Supersonic ejectors have many advantages in high-temperature heat pump (HTHP) applications, including high operating temperature tolerance, no need for lubrication, low maintenance, and low cost. The coefficient of performance of ejector HTHPs could be improved by selecting binary fluids with unique thermodynamic properties. Although supersonic ejectors have been widely used in refrigeration systems, their application in spaces and water heating is limited. This study explores the theoretical potential of ejector HTHPs with a sink temperature of 100°C–130°C and a lift temperature of 10°C–30°C. Ejector HTHPs were evaluated with single-fluid ejectors (SFEs) and binary-fluid ejectors (BFEs). A comprehensive, geometry-free theoretical model of BFEs was developed to predict the theoretical maximum entrainment ratios. HFE7500 and R718 (water) were selected as working fluids for SFEs and BFEs. SFEs operating with R718 provided a higher coefficient of performance of ejector HTHPs than SFEs operating with HFE7500 and BFEs. This study preliminarily demonstrates the technical potential of ejector HTHP applications in recovering moderate-temperature heat sources

Wang, Pengtao↗

A DYNAMIC ENERGY MODEL FOR DISPLAY CASES CONSIDERING FAULTS IN SUPERMARKETS FOR LOW GWP REFRIGERANTION

Display cases are widely used in supermarkets to demonstrate commercial goods for customers, like milk, frozen food, ice-cream, etc. There are two types of display case: open case and closed case. The goods inside display cases need to stay within a stable temperature range to meet the quality standards. However, due to variety of faults (e.g., leaving door opening), it is hard to maintain a stable temperature. The associated energy consumption from display cases is extremely high due to faults. There is a need for a dynamic energy model to accurately predict the good temperature and energy consumption under faults. A dynamic model is developed based on operation data collected through field tests in a low global warming potential (GWP) refrigeration system, at Oak Ridge National Laboratory.