Increasing Multilayer Ceramic Capacitor Lifetime With Bipolar Voltage Cycling

Enhancing the lifetime of multilayer ceramic capacitors (MLCCs) is critical in many aerospace, naval, or electrical grid applications, where device failure could lead to catastrophic consequences. The migration of oxygen vacancies from the ceramic to the electrode interface under constant bias is known to reduce the lifetime of oxide-based MLCCs. Bias cycling presents an opportunity to enhance MLCC lifetime by reducing oxygen vacancy migration. The ideal frequency range is expected to lie between frequencies low enough to avoid self-heating but high enough to avoid interfacial defect formation. However, the impact of low-frequency bipolar voltage cycling (BVC) on MLCC degradation mechanisms has not been well studied. This work investigates the impact of periodic BVC on the degradation of MLCCs through highly accelerated lifetime testing (HALT) on X7R capacitors. HALT tests were conducted at 255 °C and 60 V using different switching frequencies: 0 (dc), 0.1, 2.5, and 10 Hz. BVC was found to improve the lifetime of MLCCs compared to dc test conditions. MLCCs tested at 10-Hz BVC showed a 311% increase in average time to failure compared to the dc case. Impedance spectroscopy shows that BVC decreases the rate of resistance degradation within MLCCs, indicating that oxygen vacancy migration to the electrodes is mitigated. The impedance spectra taken on BVC samples highlight how grain boundaries play a vital role in trapping oxygen vacancies. Periodic cycling causes oxygen vacancies to become trapped at grain boundaries, resulting in oxygen vacancies taking longer to reach the electrode interface and thus increasing MLCC lifetime. This work highlights not only how BVC can be used to increase MLCC lifetime but also how periodically cycling MLCCs could increase lifetime in extreme environments, such as at elevated temperatures and electric fields.

Chuong, Kayla Y.↗

7.2 kV Three-Port SiC Single-Stage Current-Source Solid-State Transformer With 90 kV Lightning Protection

This article proposes a multiport modular single-stage current-source solid-state transformer (SST) for applications like photovoltaic, energy storage integration, electric vehicle fast charging, data center, etc. The 7.2 kV 50 kVA current-source SST consists of five input-series output-parallel modules, each based on 3.3 kV SiC reverse-blocking MOSFET-plus-diode modules. The proposed SST has some unique features. First, compared to the voltage-source or matrix converter-based SSTs, the current-source SST has a unique advantage of single-stage isolated AC/DC or AC/AC conversion with an inductive DC link, but no medium-voltage (MV) AC experiments have been reported. This article for the first time demonstrates MV AC current-source SST up to 7.5 kV peak. Second, the multiport SST has a buffer port for active power decoupling (APD) or energy storage integration. The double-line-frequency power ripple from single-phase AC grid normally results in a large capacitor size in MV SSTs. The APD scheme is proposed in MV applications for the first time to enable a reduced DC link and the electrolytic capacitor-less SST with high reliability. Third, as a direct grid-connected converter without line-frequency transformer, insulation and protection are critical. A medium-frequency transformer design passes 55 kV basic-insulation level (BIL) and 60 kV high potential dielectrics withstand test with only 0.09% leakage inductance. Importantly, a lightning protection scheme is presented to protect the SST itself from 90 kV BIL impulse. Fourth, the proposed current-source SST topology is a modular soft-switching solid-state transformer (M-S4T) with full-range zero-voltage switching and controlled dv/dt for low electromagnetic interference. Furthermore, these concepts are verified in a three-port M-S4T prototype with forced oil cooling under single-module, stacked-module, steady-state, and dynamic operations.

14 SOLAR ENERGY↗

Insulation Coordination Design for Grid-Connected Solid-State Transformers

The deployment of solid-state transformers (SSTs) in medium-voltage (MV) distribution systems is facing various challenges, especially the challenge of insulation coordination design against grid-originated lightning impulses. In this article, two challenges in existing insulation coordination designs for grid-connected SSTs are identified. One challenge is the mismatch between metal-oxide varistor (MOV) protective levels and SST insulation strength, the other challenge is the incompatibility of standard impulse test on SST protective structures. To address the MOV selection challenge, a novel lightning protection scheme is designed to protect a single-stage SST where the semiconductor modules are directly exposed to external lightning impulses. Here, the in-lab lightning impulse tests are performed to verify the overvoltage attenuation performance of the prototyped lightning protection scheme. To address the impulse test challenge, the surge withstand capability of the protected SST is comprehensively evaluated with a complete set of insulation coordination design procedures beyond the basic insulation level (BIL) test. After these two challenges are addressed, a discussion is presented on substituting conventional transformers with the protected SSTs into insulation-coordinated distribution systems to facilitate the field deployment of SSTs.