Side-by-Side Comparison of Subhourly Clipping Models

Over the past several years there have been numerous attempts at quantifying the inherent power clipping of inverters due to subhourly irradiance variability that is not captured in hourly PV performance models. Different models have been proposed to correct for these clipping losses in PV performance estimates, including matrix lookup models, distribution modeling of the PV power performance within a given hour, and machine learning methods. To date, there have been few comprehensive quantitative comparisons of these inverter clipping correction modeling approaches to evaluate the effectiveness of these approaches in predicting the actual behavior of PV system inverter clipping. In this study, we perform such a comparison, evaluating the Allen and Walker correction loss modeling approaches recently implemented in the System Advisor Model (SAM) against clipping losses modeled with 1-minute climate data. These comparisons were performed across a variety of climate locations and inverter loading ratios to thoroughly analyze the effectiveness of these modeling approaches relative to each other. Results from this analysis reveal that both clipping correction approaches improve annual energy accuracy to within 2% of 1-minute modeled energy yield. The two models predict annual clipping loss more accurately than simple hourly power limit clipping, with the Allen method typically being slightly more accurate at typical ILR values and the Walker method often being slightly more accurate at high ILR values The models can improve accuracy over the status quo clipping approach up to 3 percentage points in systems with ILR of 2.0, showing the importance of this modeling factor in energy yield estimates.

accuracy↗

Side-by-Side Comparison of Subhourly Clipping Models: Preprint

Over the past several years there have been numerous attempts at quantifying the inherent power clipping of inverters due to inter-hourly irradiance variability that is not captured in hourly PV performance models. Different models have been proposed to correct for these clipping losses in PV performance estimates, including matrix lookup models, distribution modeling of the PV power performance within a given hour, and machine learning methods. To date, there have been few comprehensive quantitative comparisons of these inverter clipping correction modeling approaches to evaluate the effectiveness of said approaches in predicting the actual behavior of PV system inverter clipping. In this study, we perform such a comparison, evaluating two different clipping correction loss modeling approaches recently implemented in the System Advisor Model (SAM) against clipping losses modeled with 1-minute climate data. These comparisons will be performed across a variety of climate locations and inverter loading ratios to thoroughly analyze the effectiveness of these modeling approaches relative to each other. Results from this analysis reveal that both clipping correction approaches improve annual energy accuracy to within 2% of 1-minute modeled energy yield. The models can improve accuracy up to 3% in systems with ILR of 2.0, showing the importance of this modeling factor in energy yield estimates.

clipping↗

Side-by-Side Comparison of Subhourly Clipping Models

Over the past several years there have been numerous attempts at quantifying the inherent power clipping of inverters due to sub-hourly irradiance variability that is not captured in hourly PV performance models. Different models have been proposed to correct for these clipping losses in PV performance estimates, including matrix lookup models, distribution modeling of the PV power performance within a given hour, and machine learning methods. To date, there have been few comprehensive quantitative comparisons of these inverter clipping correction modeling approaches to evaluate the effectiveness of these approaches in predicting the actual behavior of PV system inverter clipping. In this study, we perform such a comparison, evaluating the Allen and Walker correction loss modeling approaches recently implemented in the System Advisor Model (SAM) against clipping losses modeled with 1-minute climate data. These comparisons were performed across a variety of climate locations and inverter loading ratios to thoroughly analyze the effectiveness of these modeling approaches relative to each other. Results from this analysis reveal that both clipping correction approaches improve annual energy accuracy to within 2% of 1-minute modeled energy yield. The two models predict annual clipping loss more accurately than simple hourly power limit clipping, with the Allen method typically being slightly more accurate at typical ILR values and the Walker method often being slightly more accurate at high ILR values The models can improve accuracy over the status quo clipping approach up to 3 percentage points in systems with ILR of 2.0, showing the importance of this modeling factor in energy yield estimates.

ENERGY PLANNING, POLICY, AND ECONOMY,MATHEMATICS A↗

Regional Real-Time PV Spinning Reserve Estimator

Curtailed photovoltaic (PV) generation is a zero-marginal-cost spinning reserve that can be used for a number of active power control services. Unlike traditional spinning reserve providers, however, i.e., fossil-fueled generators, which have well-defined operating characteristics, e.g., available headroom or potential high limit (PHL), PV plants have by nature variable and uncertain operating characteristics. To ensure the effective coordination between PV plants and the system operator during an active power control event, accurate knowledge of the PV PHL is essential. It ensures that enough headroom is reserved by the PV plants to deliver the award services in real time and informs feasible dispatch decisions made by the market operator. To tackle this challenge, a novel reference-control grouping-based PV plant reserve estimation method has been proposed by the National Renewable Energy Laboratory under past projects funded by the U.S. Department of Energy Office of Energy Efficiency and Renewable Energy Solar Energy Technologies Office. The estimation method separates inverters within a plant into two groups: a control group and a reference group. While the reference group is reserved to operate at its PHL, the control group can be curtailed to provide the grid services. Real-time outputs from the reference inverters are used to estimate the PHL for the whole plant based on the ratio between capacities of the reference group and of the plant. This work further enhances the methodology by (1) improving the model accuracy through machine learning; (2) automating the reference inverter selection through correlation analysis; (3) considering estimation look-ahead windows; and (4) applying to regional spinning reserve estimation. Significant performance improvement has been observed based on real-world data collected by CAISO, Southern Company, and Terabase Energy. Compared with the original scaling method, the newly proposed machine learning-based approach reduces the estimation errors by 30% and 13% at the plant level and region level, respectively. Results obtained from this project are intended to be used by grid operators, market operators, balancing authorities, and PV plant owners and operators to facilitate PV participation in ancillary service markets. Regulators, policymakers, and system planners can also consider the results of this work in their decision-making processes. In addition to the performance improvement on the existing reference-control based grouping method, we also investigated how the variability of PV generation from a single PV inverter can be used to represent the variability of PV generation at the plant level.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Blind photovoltaic modeling intercomparison: A multidimensional data analysis and lessons learned

The Photovoltaic (PV) Performance Modeling Collaborative (PVPMC) organized a blind PV performance modeling intercomparison to allow PV modelers to blindly test their models and modeling ability against real system data. Measured weather and irradiance data were provided along with detailed descriptions of PV systems from two locations (Albuquerque, New Mexico, USA, and Roskilde, Denmark). Participants were asked to simulate the plane-of-array irradiance, module temperature, and DC power output from six systems and submit their results to Sandia for processing. The results showed overall median mean bias (i.e., the average error per participant) of 0.6% in annual irradiation and –3.3% in annual energy yield. While most PV performance modeling results seem to exhibit higher precision and accuracy as compared to an earlier blind PV modeling study in 2010, human errors, modeling skills, and derates were found to still cause significant errors in the estimates.

14 SOLAR ENERGY↗

Perspective: Performance Loss Rate in Photovoltaic Systems

Photovoltaic systems may underperform expectations for several reasons, including inaccurate initial estimates, suboptimal operations and maintenance, or component degradation. Accurate assessment of these loss factors aids in addressing root causes of underperformance and in realizing accurate expectations and models. The performance loss rate (PLR) is a commonly cited high‐level metric for the change in system output over time, but there is no precise, standard definition. Herein, an annualized definition of PLR that is inclusive of all loss factors and that can capture nonlinear changes to performance over time is proposed. The importance of distinguishing between recoverable and nonrecoverable losses which underly PLR is highlighted.

14 SOLAR ENERGY↗

International Photovoltaic Modeling Intercomparison [Slides]

Irradiance transposition models seem to perform well, except the Isotropic with -11.25 W/m 2 underestimation. Most temperature models could not capture behavior when ΔΤ between module and ambient is negative. Uncertainties due to derate factors: modelers overbudgeted resulting in significant power underestimation; maybe ~10% is appropriate for commercial systems but not lab-scale? Most software and models cluster together showing good reproducibility among participants. Modeler’s skills seem to be more important than the PV model itself (flat efficiency with irradiance, positive power temperature coefficients, etc.). Results and best practices will be communicated in a journal article.

14 SOLAR ENERGY↗

Validation of Subhourly Clipping Loss Error Corrections: Preprint

Under-performance of solar PV systems is an important issue that increases risks for stakeholders, including developers, investors and operators. Recently some attention has focused on underestimation of inverter clipping losses as a possible source of over-prediction where sub-hourly solar variability is high. Several models and data sets have been analyzed over the past few years, with the aim of quantifying, predicting, and correcting underestimated clipping loss errors for systems with high DC/AC ratio and solar variability. In this research, we apply a machine learning model developed at NREL to two physical PV systems, to correct for subhourly clipping losses. For each system, we compare overall AC power output for the model taken at 1-minute intervals to AC power output taken at 1-hour intervals with the addition of the subhourly clipping correction. Our findings consistently show that the addition of the clipping loss correction lead to a reduction in mean bias error of 0.6\% and 1.1\% for systems A and B, respectively, with no additional filtering applied. When examining high solar variability periods where clipping is more pronounced, system A and B experienced a 1.4\% and 2.5\% reduction in mean bias error, respectively, when the clipping correction was applied.

machine learning↗

Validation of Subhourly Clipping Loss Error Corrections

Under-performance of solar PV systems is an important issue that increases risks for stakeholders, including developers, investors and operators. Recently some attention has focused on underestimation of inverter clipping losses as a possible source of over-prediction where sub-hourly solar variability is high. Several models and data sets have been analyzed over the past few years, with the aim of quantifying, predicting, and correcting underestimated clipping loss errors for systems with high DC/AC ratio and solar variability. In this research, we apply a machine learning model developed at NREL to two physical PV systems, to correct for subhourly clipping losses. For each system, we compare overall AC power output for the model taken at 1-minute intervals to AC power output taken at 1-hour intervals with the addition of the subhourly clipping correction. Our findings consistently show that the addition of the clipping loss correction lead to a reduction in mean bias error of 0.8% and 1.2% for systems A and B, respectively, with no additional filtering applied. When examining high solar variability periods where clipping is more pronounced, system A and B experienced a 1.8% and 2.7% reduction in mean bias error, respectively, when the clipping correction was applied.

machine learning↗

Ultraviolet Fluorescence Bleaching Rates for New Cell Cracks

Ultraviolet Fluorescence (UVF) is an inspection tool that can be used to identify cell cracks in some photovoltaic (PV) modules. Cell cracks can also be identified with electroluminescence (EL) and similar techniques, but it is generally not possible to differentiate new cracks from old ones with EL. UVF has a unique property of taking time for the cracks to show up, which could be used to differentiate new cracks (e.g., from a recent storm) from old ones (e.g., from installation damage). We perform tests on several different modules, some the same make and model but with different bill of materials (BOMs), to characterize the amount of time that it takes for crack signatures to progress in UVF.

41 EE - Solar Energy Technologies Office (EE-4S)↗

A Model for Evaluating the Configuration and Dispatch of PV Plus Battery Power Plants

An open-source model was developed to optimize energy storage operation for photovoltaic- (PV-) plus-battery systems with AC-coupled and DC-coupled configurations. It includes the ability to use forecast energy prices to optimize battery charge and discharge on a rolling time horizon. The model allows for exploration of different configurations, including capital costs, inverter performance, dispatch flexibility, and capturing otherwise clipped energy for the DC-coupled system. The model can run 20 full years of hourly data in approximately two seconds, allowing comparison of a large number of configurations. We applied the model in a test case demonstrating reduced inverter clipping for DC-coupled systems and yielded slightly higher overall value than AC-coupled systems, with an approximately 2 percent increase in internal rate of return or benefit/cost ratio. Our results show that at current estimated prices for lithium-ion battery systems, large-scale PV-plus-battery plants are economically viable under the right conditions, with the configuration playing a role in system flexibility and performance. This model provides the ability for project developers, industry professionals, and researchers to use readily available software to quickly evaluate and design these systems.

41 EE - Solar Energy Technologies Office (EE-4S)↗

Hybrid Systems to Enable High Penetration PV

A model for PV plus energy storage and fuel cells was developed in the System Advisor Model (SAM). This model was used to evaluate the ramp rate and interconnection capacity factor for a hypothetical utility-scale plant for several configuration options. For PV only, the plant experienced 3345 violations of a 10%/minute ramp up limitation and a interconnection capacity factor of 17.6%. Adding a battery reduced the violations to 154 per year and the magnitude of the average violation to 2%. Adding a fuel cell to the PV system increased the capacity factor to 78% without improving ramp violations. Using a combined PV plus storage plus fuel cell arrangement maintained the improved capacity factor while reducing ramp up violations to 23, illustrating the potential to operate a hybrid system both to enable grid integration requirements and increase utilization of the interconnection.

14 SOLAR ENERGY↗