Small-Signal Angle Stability-Oriented False Data Injection Cyber-Attacks on Power Systems

The small-signal angle stability (SSAS) of a power system is determined by the property of operation points. The widely applied false data injection (FDI) cyber-attack, however, is able to stealthily mislead the optimal power flow (OPF) and thus compromise operation points, leading to damages to the SSAS margin. Here, to provide insights for cyber defenders, this paper proposes and investigates a stealthy SSAS-oriented FDI cyber-attack focusing on two attacking purposes, i.e., the SSAS margin and operation cost, with higher priority on the former one. First, this paper establishes a novel bi-level model with an implicit SSAS constraint based on a structure preserving model to compromise operation points. Then, for the SSAS interarea mode in a typical two-area system, this paper formulates closed-form expressions of how the SSAS margin and operation cost behave with respect to stealthy injections. By comparison, for the SSAS local mode in general power systems, this paper proposes a moving target cyber-attack-based hierarchical solution algorithm. Simulation results on a two-area system, a Kundur 11 bus system, and a modified IEEE 14 bus system demonstrate the significant damaging effects of the proposed SSAS-oriented FDI cyber-attack and the conflict between the two attacking purposes.

Benders decomposition↗

The Cost and Benefit of Enhancing Cybersecurity for Hybrid AC/DC Grids

As critical interfaces of AC grids and DC grids inside a hybrid AC/DC grid, the voltage-sourced-converter (VSC) has been demonstrated to be vulnerable to false data injection (FDI) cyber-attacks. As a result, the cyber-attack-induced AC grid frequency deviations and DC grid voltage deviations threaten the secure operation. Here, to enhance cybersecurity in a not only feasible but also cost-effective manner, this paper proposes a cost-benefit-based cyber-defense strategy for a hybrid AC/DC grid. First, this paper establishes a spatial-temporal dual cyber-attack evaluation model, in which the cyber-attack-induced frequency and voltage deviations are modelled in both a spatially and temporally dual manner. Then, the proposed cost-benefit-based cyber-defense strategy is modelled as a VSC commitment problem to achieve the trade-off between maximizing the cyber-defense benefits and minimizing the cyber-defense costs. The VSC commitment problem is then mathematically convexified into a mixed-integer second-order cone programming (MISOCP) problem, which could be efficiently solved in an event-triggered manner against unfolding cyber-attack events. Simulation results on a test hybrid AC/DC grid verified the feasibility and the cost-effectiveness of the proposed cyber-defense strategy.

cost-benefit analysis↗

Cybersecurity Enhancement for Multi-Infeed High-Voltage DC Systems

Composed of multiple two-terminal high-voltage DC (HVDC) transmission systems, a multi-infeed HVDC (MIDC) system exchanges massive power among multiple asynchronous AC systems. However, as an intrinsically cyber-physical system, an MIDC system could suffer from cyber-attacks, leading to massive power mismatches in multiple AC systems, and resulting in catastrophic consequences. Since the sequential responses of an MIDC system and interconnected AC systems are in different timescales, this paper first establishes a two-timescale model to evaluate the sequential impacts caused by cyber-attacks. Then, an event-triggered cyber-defense strategy is proposed to enhance the cybersecurity of an MIDC system by mitigating multiple non-simultaneous cyber-attacks. Whenever new cyber-attack events occur, the proposed cyber-defense strategy, which is mathematically modeled as a mixed-integer quadratic programming problem, is executed on-line and updated in an event-triggered manner. Here, simulation results on an MIDC system demonstrate that the low-cost and almost blind cyber-attacks can cause severe frequency deviations, and the proposed strategy can mitigate multi-cyber-attacks effectively.

24 POWER TRANSMISSION AND DISTRIBUTION↗