Publications and source records attributed to Huang, Pengxiang.

DC Microgrid Reliability Enhancement with Adaptive Converter Thermal Management

Due to the different device selections, aging levels, and thermal dissipation performance, some converters may take additional thermal stress on switching devices than others in paralleled converter systems, which will reduce system reliability. To address this problem, this paper proposes a power-sharing strategy with adaptive thermal management. First, the temperature-based power loss model and electrical-thermal model are established. Based on that, a high-accuracy IGBT junction temperature estimate considering the power loss-temperature coupling can be achieved. Further, the thermal-sharing for all the switching devices in paralleled converters can be achieved with the proposed adaptive thermal management strategy. The proposed strategy can change the power-sharing ratio adaptively according to the system operation conditions, which will contribute to the system reliability enhancement. The effectiveness of the proposed strategy is verified through PLECS thermal simulation and joint real-time simulation with Dspace and RT-box.

DC microgrid↗

Adaptive Fault Current-Limiting Control of MMC for Protection of Multiterminal HVDC Systems: Preprint

For the development of multi-terminal high voltage DC (MTDC) transmission, it is critical to design the protection system that can selectively isolate the faulty area from the healthy part of the dc grid using DC circuit breakers (DCCBs) while ensuring continuous operation of converter stations in the healthy part. However, because of the lack of fault current blocking capability in half-bridge (HB) modular multilevel converters (MMCs), when a dc fault occurs, the rising fault currents can quickly reach the blocking threshold within a few milliseconds and disrupt the operation of MMCs in the healthy part. Large DC reactors are often considered in series with DCCBs to reduce the rate of rise of fault currents and prevent blocking of MMCs in the healthy part of the grid. However, large DC reactors can prohibitively increase the cost of the system, particularly when they are considered in an offshore environment, for instance in offshore wind projects. Large dc reactors can also introduce stability issues and create post-fault oscillations. This paper presents an adaptive fault current limiting control method for MMCs to avoid their blocking and enable continuous operation of MTDC systems. It contains two parts: The first part is based on circulating current feedforward control that emulates virtual reactors in each arm of an MMC, which is immediately activated when the fault current starts to increase, to reduce the rate of rise of the fault current; the second part is triggered when the fault current exceeds a preset threshold by temporarily bypassing the SMs, serving as a complement to the fault current limiting effect of the first part. Both parts do not require fault detection signal and they are activated automatically during faults. Simulation case studies of a four-terminal bipolar MMC-HVDC system are presented to demonstrate the effectiveness of the proposed control methods.

active fault current limiting↗

Adaptive Narrowband Damping for Improving Harmonic Stability of Modular Multilevel Converter: Preprint

Harmonic instability events between modular multilevel converter (MMC) and ac systems have been widely reported in recent years. To resolve it, this paper proposes an adaptive narrowband damping control that automatically programs, adds and adjusts damping around the oscillation frequency when detect the oscillation. The paper first presents a low-pass filter design for MMC control loops, which pushes all negative damping of MMC impedance down to the medium frequency range (< approximately 1000 Hz). This makes narrowband damping can be more targeted and easier to design because multiple harmonic oscillations are avoided. An adaptive damping control that uses online oscillation detection is then proposed, which can automatically configure the narrowband damper to provide damping to the MMC at the detected oscillation frequency. In contrast to existing narrowband damping methods, the proposed adaptive narrowband damper adjusts the damping gain (e.g., to zero when system resonance disappears) and the width of the damping range automatically based on continuous monitoring of system resonance conditions. Electromagnetic transient (EMT) simulation results validate the efficacy of the proposed method in two typical MMC-based power systems.

active damping↗

Adaptive Fault Current-Limiting Control of MMC for Protection of Multiterminal HVDC Systems

A crucial requirement of the protection system for multi-terminal high-voltage DC (MTDC) transmission is that it is capable of selectively isolating the faulty area from the healthy part of the network using DC circuit breakers (DCCBs), while ensuring continuous operation of converter stations in the healthy part of the network. But in the half-bridge modular multilevel converters (HB-MMCs) based MTDC system, since HB-MMCs do not have fault current absorption capability, when a DC fault occurs, the rising fault currents can quickly reach the blocking threshold within a few milliseconds and disrupt the operation of the MMCs in the healthy part. To facilitate fault-ride-through capability of MTDC system, large DC reactors are often considered in series with DCCBs to reduce the rate of rise of the fault current and prevent blocking the MMCs in the healthy part of the DC networks; however, large DC reactors prohibitively increase the cost of the system, introduce stability issues and can create post-fault oscillations. This paper presents an adaptive fault current-limiting control method for MMCs to avoid their blocking and enable the continuous operation of the healthy part of MTDC systems. The method contains two parts: The first part is based on circulating current feedforward control, which emulates virtual reactors in each arm of an MMC, and is immediately activated when the fault current starts to increase to reduce the rate of rise of the fault current. The second part temporarily bypasses all the submodules when the fault current exceeds a preset threshold, complementing the fault current-limiting effect of the first part. Neither part requires fault detection signals, and they are automatically activated during faults. Simulation case studies of a four-terminal bipolar MMC-based high-voltage DC system are presented to demonstrate the effectiveness of the proposed control methods.

active fault current limiting↗

Adaptive Narrowband Damping for Improving Harmonic Stability of Modular Multilevel Converter

Harmonic instability events between modular multilevel converter (MMC) and ac systems have been widely reported in recent years. To damp harmonic resonance, this paper proposes an adaptive narrowband damping control that automatically programs, adds, and adjusts the damping around the oscillation frequency when an oscillation is detected. First, the paper presents a low-pass filter design for MMC control loops that pushes all negative damping of the MMC impedance down to the medium-frequency range (< ~ 1000 Hz). Then, an adaptive damping control that uses online oscillation detection is proposed, which can automatically configure the narrowband damper to provide positive damping to the MMC around the detected oscillation frequency. In contrast to existing narrowband damping methods, the proposed adaptive narrowband damper dynamically adjusts the damping gain and the width of the damping range based on continuous monitoring of system resonance conditions (e.g., adjust damping gain to zero when the system resonance disappears). Electromagnetic transient simulation results validate the efficacy of the proposed method in two typical MMC-based power systems.

active damping↗

Wideband Impedance Passivation of MMCs for Suppressing Harmonic Oscillations

Harmonic instability and associated oscillation events have become one of the main concerns in MMC-based HVdc systems. These oscillations can appear in the range from a few hundred hertz to several kilohertz, and the root cause is identified as delay-induced negative damping of MMC impedance appearing at the system resonance frequency. Here, this paper introduces a wideband impedance reshaping method through MMC control to eliminate such negative damping for both grid-following (GFL) and grid-forming (GFM) MMCs, which makes the MMC impedance completely passive from the second harmonic frequency upward, thus preventing all harmonic oscillations. First, simplified impedance models of MMCs are derived for the harmonic stability analysis and the impedance reshaping control design. Next, a passivity-based impedance reshaping method is presented, as well as practical considerations for its implementation. In addition, to maintain the MMC's disturbance ride-through capability, an adaptive activation scheme is developed, which enables the wideband impedance reshaping control only in the presence of harmonic oscillation events. The effectiveness of the proposed method is validated by frequency domain analysis and by electromagnetic transient (EMT) simulations of two typical MMC-based power systems.

17 WIND ENERGY↗

Active Fault Current Limiting Control for Half-Bridge MMC in HVDC Systems

DC faults of MMC can result in a significantly large fault current due to the discharge of submodule capacitors. The fault current not only risks damaging the MMC but also demands a considerable breaking capacity from the dc circuit breaker (DCCBs). This paper introduces two novel active fault current limiting methods (AFCLs), namely virtual impedance-based and energy control-based AFCL. The first method utilizes circulating current feedforward, which introduces a virtual arm impedance to suppress the rate of rise of the fault current. Meanwhile, the second method relies on the control of the internally stored energy of the MMC to automatically minimize the number of submodules that discharge during a dc-side fault. Therefore, both the dc-side current and the MMC arm current can be effectively suppressed after the occurrence of the fault. The proposed methods do not require fault detection and their response is proportional to the rate of rise in the fault current. Simulation case studies are presented to demonstrate the proposed methods.

active current limiting control↗