Search NASA⌕ Search

Engineering topics

Huang, Sen

Publications and source records attributed to Huang, Sen.

At least 37 records · Page 2

An experimental study on round-trip efficiency of a preheating control with a medium office building

The interactions between building energy efficiency and demand response (DR) with buildings may complicate their impacts on the electricity grid and buildings, yet those interactions are not well understood. This work fills this gap by presenting an experimental study that quantifies the effects of DR on building energy efficiency. Unlike existing studies, this work 1) investigates the uncertainty levels when assessing the effects of DR; 2) studies the impact of rooftop heat pumps with direct expansion refrigerant-to-air coils on the round-trip efficiency. Specifically, we considered a medium office building (~1860 m 2 ), which is served by rooftop units, located in eastern Washington State. We performed preheating control tests during typical heating days in the year 2022 and compared the building’s energy consumption during the testing days to that during normal operation days under similar weather conditions. To understand how well those normal operation days represent the baseline for the assessment, the relationship between the energy performance of this building and weather conditions was also studied. Experimental results reveal that the round-trip efficiency (i.e., the ratio of discharging energy output from the building to charging energy input into the building) was between 0.16 and 0.92. The results show that significant energy loss may occur during the preheating process. Finally, it also suggests a significant correlation between the energy efficiency of the studied building under the preheating control and the outdoor temperature; and a highly nonlinear relationship between the zone temperature changing rate and the weather condition.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Modeling Air Handling Units to Create a Diverse Fault Dataset for FDD Innovation: Lessons Learned and Recommendations

As energy management and information systems (e.g., automated fault detection and diagnostics [AFDD] tools) become more prevalent in the commercial building stock, it is important to determine the effectiveness of these technologies by benchmarking their performance. The authors have been working to develop the largest publicly available dataset of HVAC fault datasets for performance benchmarking applications, covering the most common HVAC systems and designs including chiller plants, rooftop packaged units, dual duct air handling unit and single duct air handling units. This study covers the development, modeling, and validation of a synthetic fault dataset for the air handling unit (AHU), one of the most common HVAC configurations found in the commercial building stock. Despite this being a common system, real-world time series data are scarce and usually do not span a wide range of weather conditions. Due to this limitation, two detailed AHU models, which included the single duct AHU and dual duct AHU developed in the Modelica language and HVACSIM+ were employed to carry out annual simulations of numerous common sensor faults, mechanical faults, and control sequence faults. The fault inclusive data were then validated by comparing fault effects on system performance to expected symptoms. We summarize the nature of each fault and their impacts under different weather and operation conditions. We report some lessons learnt during the efforts of validating the high volumes of the FDD data sets. Finally, we highlight considerations for FDD developers that may want to use this dataset to assess their algorithms’ performance and their improvement over time.

Casillas, Armando↗

On-policy learning-based deep reinforcement learning assessment for building control efficiency and stability

Artificial intelligence technologies have emerged as a game changer not only in specific applications such as image recognition and machine translation but also in many scientific domains. In particular, as deep reinforcement learning (DRL) has shown great success in complex control problems, DRL-based control has been considered as a potential solution to efficiently control and manage building systems. However, broad assessment of DRL-based building control is still required to characterize their pros and cons in comparison with conventional building control methods (e.g., rule-based feedback controls). In this paper, we assessed DRL-based controls with on-policy learning-based algorithms and continuous control actions for cooling control of large office buildings in the summer season to minimize whole-building energy use and occupant discomfort. We compared DRL-based control methods with two baseline control methods: (1) a pre-determined schedule with supply temperature and static pressure setpoints, and (2) advanced reset method that adjusts setpoints based on heuristic rules, i.e., ASHRAE Guideline 36. We also tested the DRL algorithms to evaluate their performances in multiple climate locations. We found that DRL-based control methods outperformed the baseline control methods in terms of energy savings while maintaining a thermal comfort. DRL reduced energy use between ~4%–22% on average compared to the baseline methods, depending on climate location. We also evaluated DRL-based control in terms of control stability and showed that DRL-based methods should address the span of hardware lifetimes in practical operations.

control stability↗

Development of a Annual Air Handling Unit Fault Dataset for FDD Tools: Lessons Learned and Considerations for FDD Developers

As energy management and information systems (e.g., automated fault detection and diagnostics [AFDD] tools) become more prevalent in the commercial building stock, it is important to determine the effectiveness of these technologies by benchmarking their performance. The authors have been working to develop the largest publicly available dataset of HVAC fault data for performance benchmarking applications, covering the most common HVAC systems and designs including chiller plants, rooftop packaged units, dual duct air handling units and single duct air handling units. This study covers the development, modeling, and validation of a synthetic fault dataset for a single duct air handling unit (AHU), one of the most common HVAC configurations found in the commercial building stock. Despite this being a common system, real-world time series data are scarce and usually do not span a wide range of weather conditions. Due to this limitation, a detailed AHU model was employed to carry out annual simulations of numerous common sensor and mechanical faults, which were then validated by comparing their effects on system performance to expected symptoms. We summarize the nature of each fault and their impacts under different weather and operation conditions. Finally, we highlight considerations for FDD developers that may want to use this dataset to assess their algorithms’ performance and their improvement over time.

Casillas, Armando↗

LBNL Fault Detection and Diagnostics Datasets

These datasets can be used to evaluate and benchmark the performance accuracy of Fault Detection and Diagnostics (FDD) algorithms or tools. It contains operational data from simulation, laboratory experiments, and field measurements from real buildings for seven HVAC systems/equipment (rooftop unit, single-duct air handler unit, dual-duct air handler unit, variable air volume box, fan coil unit, chiller plant, and boiler plant). Each dataset includes a .pdf file to document key information necessary to understand the content and scope, multiple csv files containing all the time-series data for faults at different severity levels and one fault-free case, and a ttl file to visualize the data according to BRICK schema. The dataset was created by LBNL, PNNL, NREL, ORNL and Drexel University.

AC↗

Avista’s Shared Energy Economy Model Pilot: A Techno-economic Assessment

As part of the second round of the Washington Clean Energy Fund, Avista Corp received a $3.5 million matching grant in support of a shared energy economy project to test the integration of energy assets–from rooftop solar and battery storage to building energy management systems–that can be shared and used for multiple purposes. The goal of this project is to demonstrate how both the customer and the utility can benefit from this shared energy economy model and demonstrate that the electric grid can become more reliable, efficient, resilient, and flexible. Pacific Northwest National Laboratory was engaged by the U.S. Department of Energy and the Washington State Department of Commerce to work with Avista in assessing the benefits of the shared energy economy model. This report documents the techno-economic assessment of the shared energy economy model, including the definition of use cases and applications, collection and preparation of data and input parameters, development of modeling and optimization methods, and case studies and analysis results.

29 ENERGY PLANNING, POLICY, AND ECONOMY↗

Transactive Campus Energy Systems: An R&D Testbed for Renewables, Integration, Efficiency, and Grid Services (CRADA 356 / Amendment 1)

The Clean Energy and Transactive Campus (CETC) work described in this report was done as part of Amendment 1 to Campus Cooperative Research and Development Agreement (CRADA) 356, the Transactive Campus CRADA with the Washington State Department of Commerce (Commerce) between the U.S. Department of Energy’s (DOE’s), Pacific Northwest National Laboratory (PNNL) and the Commerce through the Clean Energy Fund (CEF). The original project team consisted of PNNL, the University of Washington (UW) and Washington State University (WSU), to connect the PNNL, UW, and WSU campuses to construct and operate the testbed as both a regional flexibility resource and as a platform for research and development (R&D) for buildings/grid integration. Building on the foundational transactive system established by the Pacific Northwest Smart Grid Demonstration (PNWSGD), the purpose of the project was to construct the testbed as both a regional flexibility resource and as a platform for R&D on buildings/grid integration and information-based energy efficiency. The testbed supports the integration of renewables and other regional needs, using the flexibility provided by building loads, energy storage, and smart inverters for batteries and photovoltaic (PV) solar systems, at four physical scales: multiple campuses, campus, microgrid and building.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Occupant Preference-Aware Load Scheduling for Resilient Communities

The load scheduling of resilient communities in the islanded mode is subject to many uncertainties such as weather forecast errors and occupant behavior stochasticity. To date, it remains unclear how occupant preferences affect the effectiveness of the load scheduling of resilient communities. This paper proposes an occupant thermal preference-aware load scheduler for resilient communities operating in the islanded mode. First, key resilience indicators are selected to quantify its impacts on the load scheduling of a resilient community. A deterministic model predictive control-based load scheduling framework is adopted as the baseline. Then, a chance-constrained controller is proposed to address the occupant-induced uncertainty in room temperature setpoints. Finally, the chance-constrained controller is compared with the deterministic controller on a virtual community testbed based on a real-world net-zero energy community in Florida, U.S. Results have shown that the proposed chance-constrained controller performs better in terms of serving occupants’ thermal preference and the required battery sizes compared to the deterministic controller with the presence of the assumed stochastic occupant behavior. This work indicates that it is necessary to consider the stochasticity of the occupant behavior when designing optimal load schedulers for resilient communities.

Wang, Jing↗

Modelica-based system modeling for studying control-related faults in chiller plants and boiler plants serving large office buildings

System modeling is critical when studying operation faults in chiller plants and boiler plants. However, current fault models have difficulties faithfully representing the operation of chiller plants and boiler plants under the effects of those faults, especially the control-related ones. In this study, we present a systematic method to develop high-fidelity models for approximating the behaviors of chiller plants and boiler plants under faulty conditions. Compared to existing ones, the resulting fault models have two advantages: first, they better characterize the dynamic patterns in the system operation. In those models, control architecture and control logic are faithfully implemented. Thus, they can be used to study control-related faults, such as incorrect staging control due to sensor bias and mistuned feedback control. Second, they are readily extensible and can support large-scale investigations to explore different faulty conditions/scenarios. Those models are established in a hierarchical structure while modules in each layer can be redeclared and parameterized at upper layers. In such a case, modifications to the models can be realized through model modifiers and the process can be easily streamlined with scripts. We applied the proposed models in a comprehensive fault impact evaluation of the 13 control-related faults of chiller and boiler plants. In this evaluation, the proposed plant model is coupled with the EnergyPlus thermal load model to study the impact of various faulty scenarios. Based on the evaluation results, we identified the faults that have the most significant impacts on the operation of the chiller and boiler plants, respectively. We also found that the relationship between the impacts of the studied faults and the severity level of the faults are highly non-linear

Huang, Sen↗

An Open-Source Virtual Testbed for a Real Net-Zero Energy Community

Net zero energy communities (NZECs) are critical to ensure sustainability and resilience of modernized power systems. System modeling helps overcome technical challenges in designing and operating NZECs. In this paper, we present the modeling work based on a real NZEC. Two sets of models are developed: higher-fidelity physics-based models considering the interaction between subsystems of the studied NZEC and capturing fast-dynamics; and lower-fidelity data-driven models requiring less resource to establish and/or run. All models are validated against measurements from this real NZEC. In addition, we create a simulation framework which streamlines the processes for simulation and thus allows using developed models to form a virtual testbed. To demonstrate the usage of the virtual testbed, a case study is conducted where a building-to-grid integration control is evaluated via simulation. The evaluation results suggest that the tested control significantly smooths the power draw of the studied community and doesn’t sacrifice the thermal comfort to a great extent.

Huang, Sen↗

Experimental investigation on thermal inertia characterization of commercial buildings for demand response

Characterizing the thermal inertia of commercial buildings is of great importance in quantifying demand flexibility. Experimental tests can be used to investigate the thermal inertia of commercial buildings. However, existing studies tend to be qualitative and have limited scope. In this study, a comprehensive field test has been performed to assess the thermal inertia of commercial buildings. In this field test, six buildings are selected with different sizes, vintages, and types of heating, ventilation, and air conditioning (HVAC) systems to represent the majority of the U.S. commercial building stock. We quantify the thermal inertia with building operation data collected under various thermostat excitation signals. We then studied the relationship between thermal inertia and intrinsic properties, such as floor area, HVAC system, etc., as well as the operation condition indicators such as outdoor air temperature, zone temperature, and occupancy. The testing results indicate that the median values of the normalized charge response time and the normalized discharge response time of the five buildings are 1~5 hr/ °C and -5~-1 hr/ °C, respectively. The results also show that the thermal inertia of commercial buildings may be sensitive to the HVAC system type but not the floor area or location of zones, i.e., core vs. perimeter. Finally, our results suggest that the relationships between the charging/discharging normalized response time and the zone/outdoor temperature may vary among zones and be highly nonlinear.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Occupancy-Driven Stochastic Decision Framework for Ranking Commercial Building Loads

For effective integration of building operations into the evolving demand response programs of the power grid, real-time decisions concerning the use of building appliances for grid services must excel on multiple criteria, ranging from the added value to occupants' comfort to the quality of the grid services. In this paper, we present a data-driven stochastic decision-support framework to dynamically rank load control alternatives in a commercial building, addressing the needs of multiple decision criteria (e.g. occupant comfort, grid service quality) under uncertainties in occupancy patterns. We adopt a stochastic multi-criteria decision algorithm recently applied to prioritize residential on/off loads, and extend it to i) consider complex load control decisions (e.g. dimming of lights, changing zone temperature set-points) in a commercial building; and ii) systematically integrate zonal occupancy patterns to better identify short-term (and time-varying) opportunities for grid service participation. We evaluate the performance of the proposed framework for curtailment of air-conditioning, lighting, and plug-loads in a multi-zone commercial office building for a range of design choices. With the help of a prototype system that integrates an interactive \textit{Data Analytics and Visualization} frontend we demonstrate a way for the building operators to monitor and change in real-time the available flexibility in energy consumption and to develop trust in the decision recommendations by interpreting the rationale behind the ranking.

Jain, Milan↗

An assessment of power flexibility from commercial building cooling systems in the United States

Understanding varying characteristics and aggregate potential of power flexibility from different building types considering regional diversity is critically important to actively engaging building resources in future eco-friendly, low-cost, and sustainable power systems. This paper presents a comprehensive characteristics analysis and potential assessment of the power flexibility from heating, ventilation, and air conditioning (HVAC) loads in commercial buildings in the U.S. using a simulation-based method. In this method, commercial buildings are first grouped by building types and climate regions. The U.S. Department of Energy Commercial Prototype Building Models are used to represent an average building in each group and are simulated to characterize corresponding power flexibility. Based on building survey data, the number of commercial buildings in each group is estimated and used to calculate aggregate power flexibility. It is found that HVAC loads in commercial buildings offer more flexibility for increasing power consumption than for decreasing it. The power consumption of commercial buildings in the U.S. can be increased by 46 GW and decreased by 40 GW on peak summer days. Among all commercial building types, standalone retail buildings provide the most absolute flexibility while the medium office buildings have the most flexibility as a percentage of the rated power consumption.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Simulation-based Performance Evaluation of Model Predictive Control for Building Energy Systems

The performance of model predictive control (MPC) can be significantly affected by different choices of controller parameters such as the time intervals for model discretization and control sampling. Due to the lack of a systematic understanding on how these parameters affect control performance, they are usually selected arbitrarily in practice.In this paper, the combined impacts of selected time intervals for model discretization and control sampling on the performance of MPC are comprehensively investigated for the first time through detailed simulations. Specifically, a typical MPC strategy is first designed to improve building operations based on a reduced-order model of building dynamics. Then, the performance of the designed MPC is evaluated against different choices of time intervals for model discretization and control sampling on a simulated office building. The detailed simulation results reveal that the time interval for model discretization has a much greater influence on the performance of MPC than the time interval for control sampling. Although the time interval for control sampling usually receives more attentions in practice, it turns out that the time interval for model discretization affects the prediction performance, cost saving, and computation time simultaneously and more significantly. Therefore, the simulation-based performance evaluation presented here sheds light on the impacts of different time intervals and facilitates their selection for practical applications of MPC to building operations

Huang, Sen↗

Operating a commercial building HVAC load as a virtual battery through airflow control

Virtual battery (VB) is an innovative method to model flexibility of building loads and effectively coordinate them with other resources at a system level. Unlike a real battery with a dedicated power conversion system for charging control, methods are required for operating building loads to deviate from the baseline to respond to grid signals. This paper presents a VB control for a commercial heating, ventilation, and air conditioning (HVAC) system to follow the desired power consumption in real-time by adjusting zonal airflow rates. The proposed method consists of two parts. At the system level, a mixed feedforward and feedback control is used to estimate the desired total airflow rate. At the zone level, two priority-based algorithms are then proposed to distribute the total airflow rate to individual zones. In particular, a zonal airflow limit estimation method is proposed using machine-learning techniques, in contrast to physics-based thermal models in existing studies, to more accurately capture zonal thermal dynamics and improve temperature control performance. An office building on the Pacific Northwest National Laboratory campus is implemented in EnergyPlus, and used to illustrate and validate the proposed control.

Wang, Jiyu↗