Test and Validate Distributed Coaxial Cable Sensors for in situ Condition Monitoring of Coal-Fired Boiler Tubes

This project aims to test, validate, and advance the technology readiness level (from TRL5 to TRL7) of a novel low-cost distributed stainless-steel/ceramic coaxial cable sensing (SSC-CCS) technology for in situ monitoring of the boiler tube temperature in existing coal-fired power plants. The novel SSC-CCS sensing technology and associated condition-based monitoring (CBM) software to be demonstrated in this project will lead to an improved understanding of the boiler tube failure mechanisms and a prognostic system to improve the overall performance, reliability, and flexibility of the nation’s coal-fired power plant fleet. A boiler tube monitoring system with distributed coaxial cable temperature sensors and a sensor acquisition system was constructed. The high-temperature coaxial cable sensor with a length of 1.3m was made by using a quartz tube (1mm inner diameter (ID) and 6mm outer diameter (OD)) to concentrically separate a 304 stainless-steel (SS) rod (1mm OD) and SS tube (7.94mm OD and 6.16mm ID). The sensor acquisition system includes a vector network analyzer (VNA), a radio frequency (RF) power amplifier, multiple switches and a USB hub. The distributed stainless-steel quartz coaxial cable sensor (SSQ-CCS) had a linear response to temperature with a resolution uncertainty of σ = 0.77℃. To withstand the harsh conditions of 3,300 steam pressures and 800℃ high temperatures, the sensor was shielded by a protective tube made of the same material as the boiler tube. The protection tube had an OD of 1.5 inches and a thickness of 0.25 inches. In the laboratory tests, the sensor showed good sensitivity and fast response. The drift was bounded between +0.33% and -0.67% during a test at 600℃ for 350 hours, indicating good stability of the sensor. A field test was conducted where four sensors were welded on four superheat tubes (SH-Ts) at a coal-fired power station over 400 days. Conventional thermocouples were welded to the superheater tubes alongside the coaxial cable sensors for the purpose of comparison. Two sensors were capable of distributed sensing, with three multiplexed sensing sections. The other two sensors were single section. During the 400-day test period, the power plant experienced startups and shutdowns. At the steady state operations, the temperature of the boiler tube is about 600℃ (1112°F). The sensors recorded the entire coal-firing processes (start-up, steady state, and shut-down) and the glitch event. A GSM modem and a Watchdog were added to the system to ensure reliable data recording. The GSM modem sent daily messages to plant managers and Clemson team to inform the status of the sensor system. If the system was not normally working, the Watchdog would reboot the system automatically. The new coaxial cable based distributed sensing technology has been proven to be successful in both laboratory and field tests. A comprehensive four-stage multi-physics computational framework has been developed to assist the design, optimization, installation, and operation of SSQ-CCS. With the consideration of various operation conditions, we predict the distributions of flue gas temperatures within coal-fired boilers, the temperature correlation between the boiler tube and SSQ-CCS, and the safety of SSQ-CCS. A conditional-based monitoring system is implemented as well. The computational framework developed in this work can guide the future operation of coal-fired plants and other power plants for the safety prediction of boiler operations.

01 COAL, LIGNITE, AND PEAT↗

Fabrication and Testing of a Stainless Steel Quartz Coaxial Cable Structure for High Temperature Measurement

This paper presents a stainless-steel quartz coaxial cable structure for distributed sensing of high temperatures. The coaxial cable sensor uses stainless steel as the inner and outer conductors and quartz as the insulator in order to achieve mechanical strength and temperature resilience. Girdle-shaped reflectors are fabricated on the quartz tubing by CNC grinding and CO 2 laser resurfacing. The sensor operates by measuring the temperature dependent change in the effective electromagnetic length between the two adjacent reflectors on the quartz tubing. A retaining collar is fabricated at the tip of the quartz tubing by 3D printing and laser resurfacing to secure the connection between the sensor and the signal cable. The prototype sensor was tested for high temperature measurements up to 600°C, and the performance characteristics of the sensor such as sensitivity, resolution uncertainty, repeatability, and stability were estimated based on the test results.

Jiao, Xinyu↗

Conductive Spray Paint Fabricated Cylindrical Coplanar Waveguide for Noncontact Liquid-Level Sensing

A noncontact liquid-level sensor using a cylindrical coplanar waveguide (CCPW) is proposed. The concept is demonstrated using a prototype device made by directly spraying conductive paint on the outer surface of a glass cylinder. The position of the air–liquid interface is measured using the time-domain reflection (TDR) signal from the CCPW. The geometric parameters of the prototype sensor were optimized using a full-wave simulation tool. The experimental results show that the prototype CCPW-based liquid-level sensor has a resolution of 29.8μm over a range of 210 mm at the sweeping frequency bandwidth of 500 MHz–4 GHz. The tradeoff between the resolution and the measurement range was discussed. The proposed sensor provides a low-cost, easy-to-fabricate, and noncontact method for liquid-level measurement, which has potential applications in fuel storage, chemical production, and wastewater treatment.

42 ENGINEERING↗

Four-Stage Multi-Physics Simulations to Assist Temperature Sensor Design for Industrial-Scale Coal-Fired Boiler

The growth of renewable energy sources presents a pressing challenge to the operation and maintenance of existing fossil fuel power plants, given that fossil fuel remains the predominant fuel source, responsible for over 60% of electricity generation in the United States. One of the main concerns within these fossil fuel power plants is the unpredictable failure of boiler tubes, resulting in emergency maintenance with significant economic and societal consequences. A reliable high-temperature sensor is necessary for in situ monitoring of boiler tubes and the safety of fossil fuel power plants. In this study, a comprehensive four-stage multi-physics computational framework is developed to assist the design, optimization installation, and operation of the high-temperature stainless-steel and quartz coaxial cable sensor (SSQ-CCS) for coal-fired boiler applications. With the consideration of various operation conditions, we predict the distributions of flue gas temperatures within coal-fired boilers, the temperature correlation between the boiler tube and SSQ-CCS, and the safety of SSQ-CCS. With the simulation-guided sensor installation plan, the newly designed SSQ-CCSs have been employed for field testing for more than 430 days. The computational framework developed in this work can guide the future operation of coal-fired plants and other power plants for the safety prediction of boiler operations.

42 ENGINEERING↗

Distributed Coaxial Cable Sensors for In-Situ Condition Based Monitoring of Coal-Fired Boiler Tubes

The increasing contributions of renewable energy sources present new challenges to the operation and maintenance of the existing coal-fired power plants. One of the major operational risks is the unexpected failure of superheater boiler tubes, leading to the most unplanned power plant outrages. The boiler tube failure is difficult to predict due to the harsh operating environments. Therefore, condition-based monitoring (CBM) with a reliable high temperature sensor becomes necessary to produce a meaningful assessment of the health condition of boiler tubes and their remaining lifetime. In this work, the stainless-steel and quartz coaxial cable sensor (SSQ-CCS) is proposed for in-situ distributed monitoring of the boiler tube temperatures in existing coal-fired power plants. Comprehensive tests have been conducted with an in-house testing facility at Clemson University to study and evaluate the sensors’ performance in the temperature range of 100℃ to 600℃. The results indicated that the measurement resolution of the SSQ-CCS sensor is better than 1℃, and the drift is less than 2% over long-period testing. Meanwhile, multi-physics finite element analysis has been conducted to optimize the design and evaluate the safety of the SSQ-CCS temperature sensor under various operational conditions. Based on the performance obtained in the laboratory-scale testing, a field test has been implemented at a power plant. Four SSQ-CCS temperature sensors were installed for in-situ monitoring of the temperatures of a power plant’s superheat tube assembles. The data acquisition system has been successfully set up and collected sensing signals for more than three months. The sensing signals have been post-processed, and the monitored temperature history through the SSQ-CCS temperature sensor has been validated and compared with the conventional high temperature thermal couple data.

Jiao, Xinyu↗

Glass Additive and Subtractive Manufacturing of a Fiber Optic Rotary Encoder for Downhole Pressure Sensing

This article presents a fiber optic rotary encoder-based pressure sensor for downhole applications. The rotary encoder, which is composed of an encoding pad and an all-glass optical fiber sensing head, converts the rotation angles of a pressure transducer to digital codes. The optical fiber only serves as the telemetry channel to directly transmit the data in digital format such that the environmental temperature influence and the long-time drift are minimized. The glass additive and subtractive manufacturing (ASM) techniques are used to embed the multichannel optical fibers into a bulk-fused silica glass substrate. Because the fused silica glass shares a similar material property to the optical fiber (e.g., thermal expansion coefficient), the optical fiber sensing head is well sealed and fixed even at an elevated temperature. The picosecond laser blackening technique is used to fabricate the high reflectivity contrast encoding pad with high accuracy. Here, the proposed pressure sensor was manufactured and experimentally verified to have a signal-to-noise ratio (SNR) of 23 dB and a linear pressure response with a root-mean-square error (RMSE) of 0.37. During the 400-h 250 °C long-term stability test, there was no digital code variation. In addition, a mathematical model to study the relationships between the sensor’s performances and design parameters was established. According to the model, a 12-bit encoder (0.02% pressure sensitivity) can be achieved with a radius of 20 mm.