Control and Simulation of a Grid-Forming Inverter for Hybrid PV-Battery Plants in Power System Black Start

Power system restoration is an important part of system planning. Power utilities are required to maintain black start capable generators that can energize the transmission system and provide cranking power to non-blackstart capable generators. Traditionally, hydro and diesel units are used as black start capable generators. With the increased penetration of bulk size solar farms, inverter based generation can play an important role in faster and parallel black start thus ensuring system can be brought back into service without the conventional delays that can be expected with limited black start generators. Inverter-based photovoltaic (PV) power plants have advantages that are suitable for black start. This paper proposes the modeling, control, and simulation of a grid-forming inverter-based PV-battery power plant that can be used as a black start unit. The inverter control includes both primary and secondary control loops to imitate the control of a conventional synchronous machine. The proposed approach is verified using a test system modified from the IEEE 9-bus system in the time-domain electromagnetic transient simulation tool PSCAD. The simulation results shows voltage and frequency stability during a multi-step black-start and network energization process.

Nguyen, Quan H.↗

Analysis of Weather and Climate Extremes Impact on Power System Outage

This paper provides statistical analysis of the characteristics of power system outages to gain a better understanding of the impacts of the increasing severe weather conditions on the outages. 10-year historical power system outage data from the Bonneville Power Administration (BPA) were gathered together with co-located weather attributes and recorded extreme weather events in the service area, which are paired in comparable spatial and temporal scales, with a focus on each outage transmission line. Statistical frequency analysis and cross-tabular evaluation are performed to investigate the occurring frequency and duration of outages associated with extreme weather in this area of study. The study reveals that the weather-related outages can be mainly attributed to hail and thunderstorm events which correspond to up to 60% out of all failures in several transmission line types.

Ren, Huiying↗

Optimal Power System Black start using Inverter-Based Generation

Power system black start readiness is part of the system planning. Utility planners perform periodic studies to assess if their power system is capable of total restoration following a black out. Hydro and diesel generators are the most commonly used black start capable resources by power utilities. However, with increasing penetration of solar generation, inverter-based resources can be considered to provide black start capability. Since the solar inverters can be located at multiple locations throughout the power system, and in view of their unique characteristics, an optimal real-time capable plan is helpful for system operators for faster black start. Black start optimization is a multi stage mixed-integer non-linear optimization which is extremely hard to solve. In this paper, we propose an optimal black start methodology that is easier to solve and scalable in real-time. We demonstrate the proposed methodology on two test systems and illustrate how inverter-based resources can contribute and improve power system restoration.

power system restoration, blackstart, Inverter-bas↗

EMS and DMS Integration of the Coordinative Real-time Sub-Transmission Volt-Var Control Tool under High DER Penetration

This paper proposes an applicable approach to deploy the Coordinative Real-time Sub-Transmission Volt-Var Control Tool (CReST-VCT), and a holistic system integration framework considering both the energy management system (EMS) and distribution system management system (DMS). This provides an architectural basis and can serve as the implementation guideline of CReST-VCT and other advanced grid support tools, to co-optimize the operation benefits of DERs and assets in both transmission and distribution networks. Potential communication protocols for different physical domains of a real application is included. Performance and security issues are also discussed, along with specific considerations for field deployment. Finally, the paper presents a viable pathway for CReST-VCT and other advanced grid support tools, which could be integrated in an open-source standardized-based platform that supports distribution utilities.

Nguyen, Quan H.↗

Networked HIL Simulation System for Modeling Large-scale Power Systems

This paper presents a networked hardware-in-the-loop (HIL) simulation system for modeling large-scale power systems. Researchers have developed many HIL test systems for power systems in recent years. Those test systems can model both microsecond-level dynamic responses of power electronic systems and millisecond-level transients of transmission and distribution grids. By integrating individual HIL test systems into a network of HIL test systems, we can create large-scale power grid digital twins with flexible structures at required modeling resolution that fits for a wide range of system operating conditions. This will not only significantly reduce the need for field tests when developing new technologies but also greatly shorten the model development cycle. In this paper, we present a networked OPAL-RT based HIL test system for developing transmission-distribution coordinative Volt-VAr regulation technologies as an example to illustrate system setups, communication requirements among different HIL simulation systems, and system connection mechanisms. Impacts of communication delays, information exchange cycles, and computing delays are illustrated. Simulation results show that the performance of a networked HIL test system is satisfactory.

Xie, Fuhong↗

Networked HIL Simulation System for Modeling Large-scale Power Systems

This paper presents a network hardware-in-the-loop (HIL) simulation system for modeling large-scale power systems. Researchers have developed many HIL test systems for power systems in recent years. Those test systems can model both microsecond-level dynamic responses of power electronic systems and millisecond-level transients of transmission and distribution grids. By integrating individual HIL test systems into a network of HIL test systems, we can create large-scale power grid digital twins with flexible structures at required modeling resolution that fits for a wide range of system operating conditions. This will not only significantly reduce the need for field tests when developing new technologies but also greatly shorten the model development cycle. In this paper, we present a networked OPAL-RT based HIL test system for developing transmission-distribution coordinative Volt-VAR regulation technologies as an example to illustrate system setups, communication requirements among different HIL test systems, and connection mechanisms. Impacts of communication delays, information exchange cycles, and computing delays are illustrated. Simulation results show that the performance of a networked HIL test system is satisfactory.

digital twin, distribution system, co-simulation, ↗

Pumped Storage Hydropower Valuation Guidebook: A Cost-Benefit and Decision Analysis Valuation Framework

As an energy storage technology, pumped storage hydropower (PSH) supports various aspects of power system operations. However, determining the value of PSH plants and their many services and contributions to the system has been a challenge. While there is a general understanding that PSH resources provide many services and benefits for the operation of power systems, estimating the value of these services—and especially the monetary value of some of those services—has been a challenge. The objective of this project, funded by the U.S. Department of Energy’s (DOE’s) Water Power Technologies Office (WPTO), is to advance the state of the art in assessing the value of PSH plants and their contributions to the power system. The specific goal is to develop detailed, step-by-step valuation guidance that PSH developers, plant owners or operators, and other stakeholders can use to assess the value of existing or potential new PSH plants and their services. The specific goals of this project are: (1) to develop comprehensive and transparent valuation guidance that will support consistent valuation assessments and comparisons of PSH projects or project design alternatives, (2) to test the PSH valuation guidance and its underlying methodology by applying it to two selected PSH projects, and (3) to transfer and disseminate the PSH valuation guidance to the hydropower industry, PSH developers, and other stakeholders. The authors believe that the application of a consistent, transparent, and repeatable valuation process will advance valuation assessments and allow stakeholders to compare valuation analyses performed for different PSH projects or design alternatives. It will also increase the acceptance of valuation results and enable better understanding of the true value that PSH technology brings to the grid.

13 HYDRO ENERGY↗

Data Requirements for Application of Risk-Based Dynamic Contingency Analysis to Evaluate Hurricane Impact to Electrical Infrastructure in Puerto Rico

This paper presents a risk-based dynamic contingency analysis framework that was used to evaluate the hurricane impact to electrical infrastructure in Puerto Rico. PNNL developed a scalable risk-based framework for identifying high-voltage transmission resilience improvements by classifying and prioritizing high-risk power grid contingencies (system failures) under hurricane impact. The risk-based framework is founded on grid outage definitions with their associated probabilities of occurrence from hurricane events, in combination with an impact assessment derived from detailed dynamic cascading failure analysis. This paper focuses on a discussion around data requirements for transmission resilience planning for hurricane events, derived from the development of the risk-based framework and its application to Puerto Rico. This paper launches an important first step in encouraging the engineering community and power system industry to move towards establishing resilience planning as a routine practice. Since actual results for Puerto Rico contain sensitive information, sample simulation results will be used to illustrate the data requirements and risk-based dynamic cascading framework on the Puerto Rico power grid, as well as demonstrate the potential for such a simulation framework. The paper includes a discussion on the lessons learned, importance and need for improved datasets that are not usually considered in traditional power system planning. The paper will also elaborate on how the scalable simulation framework and datasets might be expanded to larger footprints and leveraged for modelling other types of natural disasters.

DCAT, Puerto Rico, hurricane, Power System Stabili↗

Risk-Based Dynamic Contingency Analysis Applied to Puerto Rico Electric Infrastructure

The U.S. Department of Energy’s (DOE) Office of Electricity and Office of Energy Efficiency & Renewable Energy have funded DOE National Laboratories to perform modeling, analysis, and high-level design of resilience-enhancement options for the power grid of the Commonwealth of Puerto Rico. The Pacific Northwest National Laboratory (PNNL) is one of the national laboratories contributing to the DOE effort. Under this funding, PNNL completed Phase I of their analysis in 2018, which identified high-priority transmission enhancements derived from detailed dynamic cascading analysis of severe contingencies, including a hurricane scenario example. This report describes additional analysis completed under Phase II, which was performed over 2019. The PNNL team applied decades of experience making complex power systems more resilient, reliable, secure, flexible, affordable and sustainable, with partners in government and industry. In this report, PNNL presents the Phase II analysis, in which a risk-based dynamic contingency analysis approach to evaluate impact of several hurricane scenarios was developed. This approach was used to identify high-priority enhancements and test resilience mitigation actions, including the evaluation of high-solar scenarios developed as a result of the 2019 Puerto Rico Integrated Resource Plan (IRP).

24 POWER TRANSMISSION AND DISTRIBUTION↗

Real-time Simulation of Coordinated Sub-Transmission Volt-Var Control Tool under High Distributed PV Penetration

With the rapid penetration of intermittent solar photovoltaic (PV) and other distributed energy resources (DER) into the grid, and subsequent changes in power flow patterns in both distribution and sub-transmission, voltage regulation is becoming a major challenge. It is prudent to leverage PV and DER to provide ancillary services to the grid, such as voltage regulation. Recently, a quasi-static, coordinated real-time sub transmission volt-var control algorithm (CReST-VCT) was developed for voltage regulation under high PV penetration by dispatching the reactive power settings of the shunt devices and PV inverters. The algorithm was validated offline, on a quasistatic study. Such quasi-static dispatching algorithms cannot guarantee its performance for highly nonlinear dynamical power systems. In this paper the performance of the algorithm is validated with a real time nonlinear dynamic simulation of a modified IEEE 118 bus system in Opal-RT. The real time simulation is used to emulate the actual system operation, providing a more realistic testing environment for CReST-VCT. The dispatch and control signals are communicated between the power system (Opal solver) and the control center (GAMS solver) in real-time with a MODBUS bridge. The results demonstrate i) system is stable with the new dispatch points ii) significant improvement in system-wide voltage profiles compared to an uncontrolled scenario. Another significant contribution of the work is developing a framework for dispatchable, long duration dynamic simulations that can be leveraged for market/dispatch studies.

CReST-VCT, Opal-RT, Volt/Var Control, renewable in↗

Risk-Oriented PMU Placement Approach in Electric Power Systems

The objective of traditional PMU placement approaches is to use the minimal number of PMUs to cover system complete observability. Very few consider the probability and the consequence severity of observability loss. For example, following line trip, grid topology changes, which may results in observability loss and overloaded lines. As long as the overloaded lines are still observable, then we can take action in time to correct the system; and the consequence of the observability loss is not severe, although some parts of the system is not observable. Otherwise, if the overloaded lines become unobservable, then we lose the situation awareness of the system and the consequence of the observability loss is severe. To address the above points in PMU placement, this paper proposes a risk-oriented PMU placement approach. The proposed approach uses two indices, namely the probability of observability loss and its corresponding consequence of severity to design the optimal PMU placement strategy. We show that our proposed approach is able to capture the critical events while the traditional approaches fail to do so. Extensive simulation results carried out on the IEEE 39-bus and 118-bus systems demonstrate its effectiveness.

observability, risk of observability loss, PMUs pl↗

Coordinated PEV Charging for Distribution System Management

Plug-in electric vehicles (PEVs) can help to reduce worldwide dependence on petroleum and carbon emissions. In the past a few years, PEVs have received considerable attention as an eco-friendly and cost-effective alternative to conventional gasoline vehicles. PEVs consume higher power from the grid during charging compared to conventional residential loads. Therefore, the emerging fleet of PEVs will introduce a considerable amount of additional load on power system. On the other hand, majority of PEVs are parked for more than 90% of the time, making them ideal for providing various services through Electric Vehicle Supply Equipment (EVSE), a.k.a. charging stations which are PEVs’ connection points to the power system. In this project, coordinated PEV charging are developed to provide distribution system services, considering PEV characteristics, realistic travel pattern, charging behaviors, and EVSE power rating and availability. The main efforts and contributions are summarized as follows. • Mobility models and EVSE charging capability/availability are indispensable for evaluating PEV charging coordination strategies and developing PEV charging control. Many existing studies utilize simplified mobility models assuming that the entire vehicle fleet returns home in the evening and is parked at home until the next morning. Some other PEV models better represent diversified home arrival and departure time, but cannot capture varying charging flexibility and capability at different locations, and therefore are not appropriate to study the impacts of public EVSE on PEV load and utilization. In this work, a mobility and charging flexibility model is proposed to better represent the temporal availability and varying charging capability from PEV onboard charger and EVSE. • Based on the mobility model, a generalized optimization method is proposed to evaluate different PEV charging coordination strategies. In existing literature, different algorithms and methods need to be designed to evaluate each charging strategy from both vehicle owners’ and system’s perspective. With the optimization method proposed in this work, different charging control strategies can be studied and compared by only updating objective functions. Moreover, optimization tricks are provided to convert the optimization problems to equivalent linear programming problems, which can be efficiently solved with existing solvers. • An innovative scheduling and control framework is proposed to enable smart PEV charging for grid services while meeting PEV owners’ travel needs. In the proposed framework, each set of EVSE is equipped with a controller that estimates charging power and energy flexibility based on vehicle characteristics, EVSE power rating, battery energy state, and upcoming trip information. With the simplified charging flexibility model received from each EVSE controller, the central coordinator determines the optimal power allocation for a look-ahead time window for the given grid services. The proposed charging control can help reduce the computational complexity and communication requirement compared with existing methods. It is also scalable to the expanding PEV fleet and robust to uncertainties in upcoming vehicle trips and future system condition. • The proposed charging strategy evaluation and smart charging control methods are applied to one of the prototypical feeders developed by the Pacific Northwest National Laboratory (PNNL) for case studies. Detailed trip information extracted from the National Household Travel Survey (NHTS) is used to represent travel and parking patterns. Different scenarios are simulated to evaluate the performance of the proposed methods and understand how PEV mobility and public EVSE availability affect PEV load and potential grid services.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Coordinative Real-time Sub-Transmission Volt-VAr Control for Reactive Power Regulation between Transmission and Distribution Systems

This paper introduces an integrated voltage regulation approach to coordinate the Volt-VAr control between transmission and distribution systems. Distributed photovoltaic (PV) systems are aggregated as a virtual power plant (VPP). At the sub-transmission level, a Coordinated Real-time Sub-Transmission Volt-VAr Control Tool (CReST-VCT) is introduced to coordinate the operation of the shunt devices and the reactive power provided by the VPPs. The CReST-VCT uses an enhanced Volt-VAr control algorithm with weighted voltage control objects that include minimizing losses, maintaining the voltage within desirable levels, and minimizing the number of mechanical switching of shunt elements. The algorithm runs every 5 minutes and is solved using AC optimal power flow (OPF) solution technique. The outputs include the settings for each sub-transmission-level Volt-VAr control devices and the reactive power generation requirements for each VPP. Then, each VPP will run a distribution Volt-VAr control algorithm to select the PV inverters that provide the Volt-VAr control services considering the distribution network topology. The goal of the VPP reactive power control is to meet the transmission level service requirements while maintaining the voltage and line flow in the distribution system within limits. Each VPP will update its voltage regulation capacity every 5 minutes to allow the CReST-VCT to formulate the optimization problem for the next dispatch interval. The proposed tool is simulated on Duke Energy Carolina system to demonstrate the capability of providing voltage support service by dispatching of reactive power of distributed PV as VPP.

Ke, Xinda↗

Exact Optimal Power Dispatch in Unbalanced Distribution Systems With High PV Penetration

Smart inverters provide additional control capability to help optimize the operation of distribution systems. This paper proposes a framework for exact optimal active and reactive power dispatch of distributed photovoltaic (PV) generation, switched capacitors, and tap changers in large multi-phase unbalanced distribution systems. The objectives of the optimal dispatch are minimization of the energy loss, PV active power curtailment, and capacitor and tap changer switching operations, in addition to elimination of voltage violations and reverse power flow. The optimization problem is formulated in rectangular coordinates as a nonlinear, nonconvex problem. Effective computational strategies are proposed to allow the application of predictorcorrector primal-dual interior point method to solve optimization problems in real-time with a large number of constraints and variables, including discrete variables corresponding to switched capacitors and tap changers. The accuracy of the numerical solution and the ability to implement the proposed framework are validated using the unbalanced multi-phase IEEE 34-bus and EPRI 2,998-bus distribution systems with 15-minute load and PV data. The results show a significant loss reduction and complete removal of both voltage violations and reverse power flow.

Nguyen, Quan (ORCID:0000000347769557)↗

Optimization Methods for Evaluating PEV Charging Considering Customer Behavior

Plug-in electric vehicles (PEVs) can be connected to grid through electrical vehicle supply equipment (EVSE) to provide various grid services in addition to battery charging. This paper evaluates loading condition of a distribution system with a medium penetration of PEVs considering different charging strategies and public EVSE availability. A mobility and charging flexibility model is proposed to capture PEVs’ temporal availability and varying charging capability at different parking locations. Detailed trip information extracted from the National Household Travel Survey is used to represent travel and parking patterns. An optimization method is then proposed to coordinate PEV charging to effectively shift load from peak to off-peak hours. One of the prototypical feeders developed by the Pacific Northwest National Laboratory is studied in different scenarios.

Wu, Di↗

A Hierarchical VLSM-Based Demand Response Strategy for Coordinative Voltage Control between Transmission and Distribution Systems

This paper presents a two-stage hierarchical voltage-load sensitivity matrix (VLSM)-based demand response (DR) algorithm for regulating the voltage at distribution feeders while fulfilling the transmission system DR requests. This allows distributed energy resources be aggregated to provide transmission-level services without causing operational issues in the distribution grids. At the beginning of each operation interval, a transmission system controller will issue DR commands to distribution system controllers. In the first stage, the distribution system controller uses a VLSM-based dispatch algorithm to dispatch the available DR resources on the distribution feeder with an objective to minimize the total voltage deviations at the lowest cost. Then, power flow studies are conducted assuming that the DR commands have been executed. If voltage violations are detected, a second-stage VLSM-based DR dispatch will be performed to remove those violations. After that, the upper and lower DR limits calculated for the next operation interval are sent back to the transmission system controller so the transmission optimization algorithm can use them as operational constraints to make subsequent decisions. The DR resources include smart photovoltaic (PV) inverters that can curtail real power and provide reactive power support, controllable loads and capacitor banks. In conclusion, the IEEE 123-bus test system with 5-minute PV and load data is used to evaluate the performance of the algorithm. In conclusion, simulation results show that the proposed algorithm can fulfill the transmission-level DR requests while maintaining the voltage in the distribution system within limits.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Combined Transmission and Distribution Test System to Study High Penetration of Distributed Solar Generation

Transmission and distribution (T&D) standard test systems are currently defined separately, and are critical for researchers and engineers to test new solutions. Growing installation of energy resources in distribution and sub-transmission systems is creating higher interactions between T&D systems. This paper proposes a standard test system to study T&D interactions for high penetration of solar photovoltaic (PV) generation. The proposed test system can be used to study and propose solutions to problems such as reverse power flows and voltage control affected by PV variability. The proposed test system combines the transmission IEEE 118 bus system, with the distribution IEEE 123-node feeder. The original test systems are significantly enhanced by adding high penetration of solar PV generation with corresponding full-year minute-resolution chronological data. Conventional generation chronology is achieved by adding dispatch and unit commitment data for AC optimal power flow solutions. And chronological load data is added in both aggregated and disaggregated fashions. Sample applications of the data are provided highlighting voltage control challenges, and the proposed system is made available openly online.

Samaan, Nader A.↗