Search NASA⌕ Search

Engineering topics

Kurnik, C

Publications and source records attributed to Kurnik, C.

NREL Job Task Analysis: Quality Control Inspector

A summary of job task analyses for the position of quality control inspector when evaluating weatherization work that has been done on a residence.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

NREL Job Task Analysis: Crew Leader

A summary of job task analyses for the position of crew leader when conducting weatherization work on a residence.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Psychrometric Bin Analysis for Alternative Cooling Strategies in Data Centers

Data centers are significant energy users and require continuous cooling to maintain high levels of computing performance. The majority of data centers have direct-expansion cooling which typically accounts for approximately 50% of the energy usage of data centers. However, using typical meteorological year 3 (TMY3) weather data and a simple psychometric bin analysis, alternative cooling strategies using a combination of economizer, evaporative, and supplemental DX cooling have been shown to be applicable in all climate zones in the United States. Average data center cooling energy savings across the U.S. was approximately 80%. Analysis of cooling energy savings is presented for various ASHRAE climate zones. The psychometric bin analysis is conducted for the ASHRAE recommended and allowable operating environment zones, as well as, a modified allowable operating environment. Control strategies are discussed. Finally, examples of energy efficient data centers using alternative cooling strategies are presented.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗