An evaluation of the demand response potential of integrated dynamic window and HVAC systems

Demand response (DR) increases the flexibility and reliability of the electricity grid as use of intermittent renewable energy sources increases. HVAC and envelope DR measures present the largest aggregate energy and peak demand savings potential of all commercial building end uses because their net demand savings occur during critical peak demand periods. Controllable envelope measures include switchable electrochromic windows, operable window attachments such as outdoor louvers, roller shades, and awnings, as well as other innovative facade technologies that can modulate both solar heat gain and daylight admission over a broad solar-optical range. This study evaluated the technical potential of DR-enabled dynamic windows to reduce critical peak demand for a prototypical medium office building situated in all 16 U.S. climates. Model predictive control (MPC) algorithms were designed to minimize electricity cost in daylit perimeter office zones through control of an electrochromic window with and without HVAC thermostat setpoint control. Conventional and time-of-use rates were used to shape the degree of DR. Median annual peak demand savings with window and thermostat control across all climate zones were 24.3 kW (4.4 W/m 2 ) per building or 15.9 W/m 2 for non-north perimeter zones. Resource adequacy at the whole building level was estimated to be 13.1 to 43.4 $/kW per year over the 30-year life of the installation. Co-benefits were increased energy efficiency, and reduced electricity cost and emissions. Visual and thermal comfort requirements were met at all times. Dynamic facades controlled by MPC have substantial technical potential for DR across all U.S. climates and warrant serious consideration for inclusion in DR portfolios.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Field validation of isotropic analytical models for simulating fabric shades

Fabric roller shades are common shading materials used in commercial and residential buildings. Accurately characterizing and modeling shades helps practitioners select the appropriate product and its control strategy based on climate and occupants' priorities, such as visual comfort and view to outdoors. Previous studies established a generalized method for modeling complex fenestration systems using data-driven tabulated bidirectional scattering distribution functions. However, deploying such a method at scale to all fabric shading products on the market is too costly and time-consuming. Analytical models that are based on a limited set of measurements (e.g., normal-normal and normal-hemispherical visible transmittance and reflectance, and directional cut-off angles) can be used to model the wide variety of shading products on the market. This study evaluates the performance of two isotropic analytical models, Roos-Wienold and Modified-Kotey, for modeling fabric roller shades, with a focus on the model's ability to predict occupant visual comfort. The performance evaluation was conducted through laboratory and field measurements and simulations. The results showed that both models are sufficient for predicting vertical illuminance at seated eye-level. Roos-Wienold model was able to predict binary visual comfort classification (glare/no-glare) under a wide range of luminance conditions, while Modified-Kotey model did not perform as well under high-contrast low-adaptation conditions. Both models are insufficient in predicting visual comfort at a four-point scale (e.g., imperceptible, perceptible, disturbing, intolerable). The two isotropic models become less accurate when the fabric exhibits high anisotropy.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Evaluation of integrated daylighting and electric lighting design projects: Lessons learned from international case studies

This article presents and discusses the lessons learned from the monitoring of 25 integrated daylighting and electric lighting international case study projects. The case studies consist of real occupied buildings that have been monitored as part of the International Energy Agency (IEA) SHC Task 61/EBC Annex 77 Programme. The general goal of the case studies was to balance lighting energy use with occupants’ visual and non-visual requirements. This was achieved using innovative solutions for daylighting and electric lighting with advanced controls, but also implementing simple and out-of-the-box strategies. The findings suggest that energy demands for lighting can significantly be reduced by combining sensible daylight provision, efficient lighting sources, and advances in controls. Yet, the effective achievement of project goals requires adequate monitoring, fine-tuning, and verification. The findings also suggest that the adoption of “integrative” lighting – that is, lighting systems that address both visual and non-visual responses – is getting increasingly popular. Catering to non-visual requirements will likely drive further innovation in lighting technology. Currently, there is limited investment available for developing daylighting systems for integrative lighting, and the current related electric strategies often come at the risk of energy rebound effects. Overall, providing daylighting and understanding user requirements are fundamental steps towards achieving quality projects, with potential benefits beyond saving energy.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Automated Production of Optimization-Based Control Logics for Dynamic Facade Systems, with Experimental Application to Two-Zone External Venetian Blinds

The primary goal of this research is to devise a system that produces controllers for complex fenestration systems that perform nearly as well as Model Predictive Control but at a level of cost and implementation complexity that rivals simple heuristic controls. To this end, a cloud-based automated controller production system has been set up for a motorized external Venetian blind device, with a simple web interface that can be used by non-experts. The computation cost per controller is in the range of a few dollars, and the control logic is simple enough to be implemented on small and cheap distributed controllers. The web interface allows the user to specify some details of their particular building and window configuration, including orientation, latitude, interior geometries, and lighting and HVAC system parameters. Upon submittal, a cloud-based system configures the necessary files and commands, and then runs thousands of optimizations with them. Once the calculations are finished, the system produces a lookup table and interpolation-based controller scripts that can be used on a simple and cheap distributed controller. This paper describes the underlying models and optimization processes. It also describes the resulting control logics for two cases tested at Lawrence Berkeley National Laboratory’s Advanced Windows Testbed Facility: illuminance maximization subject to glare constraints; and lighting + HVAC energy minimization. The performance of the model-based controllers produced by the automated web-based system are compared to a heuristic ‘block beam’ controller in physical experiments at the Testbed. The experimental results are supplemented by simulation experiments with the same configuration as the Testbed. The results show the illuminance maximizing controller significantly outperforms the heuristic controller in terms of glare avoidance, and also outperforms it in terms of hours of daylight autonomy. The energy minimizing controller also outperforms the heuristic controller. This paper also discusses how the web-based system may be extended to consider other configurations, such as electrochromic windows and thermally massive HVAC systems. Potential roles for this type of system within the building design and construction industry are discussed.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Advocating for view and daylight in buildings: Next steps

With the exponential growth in population and commensurate increased density in urban cities, access to daylight and views to nature is being severely curtailed in buildings. In parallel, increasingly urgent demands to sharply reduce building energy use and associated greenhouse gas emissions are being made to mitigate climate change. There are many challenges and performance tradeoffs associated with the building facade (i.e., daylight and view versus solar and glare control); increased prioritization of health and well-being as a fundamental human requirement could adversely affect building energy-efficiency. Given the current state of knowledge on the effects of daylight and view on health and well-being in buildings, we identify critical needs in research, tools and technologies that if satisfied may enable more effective use of daylight and view in buildings within the constraints of climate change. Lack of knowledge regarding the complex causal mechanisms of window views on human factors is a severely limiting factor in forward progress. Current models and methods to derive bidirectional scattering distribution functions (BSDFs) will need to be modified. Developers of energy-efficient window technologies will need more guidance to shape product development. Advanced window technologies and integrated design can enable attainment of both health and well-being and net zero energy goals, but considerable work will be needed to make such options turnkey and broadly available.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Field validation of data-driven BSDF and peak extraction models for light-scattering fabric shades

Shading and daylighting systems affect cooling, heating, and lighting energy use by modulating solar radiation through the building façade. Characterizing shading systems holistically and accurately helps designers and engineers evaluate shading systems to achieve energy and non-energy performance goals. These complex fenestration systems can be modeled using Bidirectional Scattering Distribution Functions (BSDF), which map incident radiation to hemispherical distributions of outgoing radiation. Data-driven, tabulated BSDFs are derived from interpolated goniophotometer measured data, then sampled during the raytracing calculation. A peak extraction (PE) algorithm was developed to circumvent limits in BSDF angular resolution, where the specular peak is extracted during simulation by evaluating the BSDF in the through direction and surrounding region. The objective of this study was to validate this measurement and modeling workflow using field monitored data from a full scale testbed with eleven installed fabrics of different weaves, openness factors, and colors and assess the accuracy of the workflow under different adaptation and contrast conditions. Test conditions were limited to clear sky conditions with the sun in the field of view. Results showed that, for tensor tree datasets, vertical illuminance, solar luminance (2.5° apex), and daylight glare probability (DGP) were predicted to within a mean bias error (MBE) error of -456 lx (-12.3%), -3.46e5 (-38.4%), and -0.042 (-7.8%) when full PE occurred. With a binary classification of glare/ no glare, DGP was predicted accurately with a true positive rate of 0.98 and true negative rate of 1.0 using tensor tree data and less accurately with Klems BSDF data, particularly for cases of no glare. The workflow may be of insufficient accuracy to distinguish borderline performance between fabrics using the four-point glare scale, particularly under low adaptation, high contrast daylit conditions. Errors were due to reductions in peak shape and intensity across the BSDF interpolation and data reduction workflow. Future work is needed to better preserve measurement fidelity during interpolation and sampling, which in turn will improve PE performance.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Daylight simulation workflows incorporating measured bidirectional scattering distribution functions

Daylight predictions of architectural spaces depend on good estimates of light transfer through skylights, windows and other fenestration systems. For clear glazing and painted surfaces, parametric transmission and reflection models have proven adequate, but there are many cases where light-scattering, semi-specular shading and daylighting materials defy simple characterization. Something as commonplace as fabric roller shades and venetian blinds may turn daylight prediction into guesswork, and numerous advanced systems on the market tuned specifically to enhance daylight are not sufficiently characterized to distinguish their performance. In this paper, we describe new tools available to handle novel and specialized fabrics, materials, and devices using data-driven modelling of bi-directional scattering distribution functions (BSDFs). These representations are usually tabulated at constant or adjustable angular resolution for efficient point-in-time and annual daylight simulations. We describe a variety of BSDF simulation workflows, including some of the tools and methods that make advanced analysis possible, and highlight some of the current challenges. We conclude with a discussion of future work and how such data might be created and shared worldwide.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Comparative study on the overall energy performance between photovoltaic and Low-E insulated glass units

In this report a novel semi-transparent building integrated photovoltaic (BIPV) laminate was developed and introduced in this paper. It was produced by cutting standard mono-crystalline silicon solar cells into small strips and then making electrical connections between each strip before laminating the cells between two layers of glass. The overall energy performance and energy saving potential of the BIPV insulated glass unit (IGU) under real world conditions were identified through a side by side comparative study. Compared to the reference IGU, the BIPV IGU had lower solar heat gain coefficient (SHGC) but much higher U-factor. The average HVAC electricity saving of the BIPV IGU was about 10% relative to the reference IGU. Daylighting measurement and analysis were carried out to evaluate the trade-offs associated with the BIPV IGU between daylight, glare, and lighting energy use. The results indicated that the BIPV IGU is better than the reference IGU in reducing discomfort glare. However, if the most conservative viewpoint near the window is used for the assessment, a lower transmittance BIPV IGU is required to bring the overall discomfort levels below the perceptible level. Lastly, the net energy saving potential associated with the novel BIPV IGU was identified based on the power, thermal and daylighting performance. On average, the BIPV IGU saved 16.8% of the total electricity use of the room. Further studies and improvement on the energy conversion efficiency of solar cells, the optimal transmittance as well as the thermal properties would make this technology more energy-efficient and affordable.

14 SOLAR ENERGY↗

Potential annual daylighting performance of a high-efficiency daylight redirecting slat system

While the primary role of window attachments is often to moderate glare and solar heat gains, they are also able to provide additional daylight to interior spaces. For this purpose, a variety of daylight-redirecting window systems have been developed over the past 150 years. Fixed reflective systems (slats/light shelves) or prismatic systems that rely on total internal reflection work well under specific solar conditions, but generally sacrifice performance over a much wider range of incident solar angles and sky conditions. Dynamic systems - typically reflective slats - are more responsive to sun angles but have not been able to achieve optimal performance for glare and daylight redirection efficiency. A previous investigation into an adjustable, reflective blind concept first conceived of in the late 1970s showed promise but was not reduced to practice due to lack of adequate simulation and analysis tools. In this paper, this concept is further developed and its energy and visual comfort performance evaluated for four mid-latitude, temperate climates using ray-tracing simulation techniques. Overall, results indicate significant potential lighting energy savings when compared with conventional automated reflective blinds (2.1–4.9 kWh/(m 2 ·a), or 14%–42%, depending on climate and orientation) or, especially, manually-operated matte white venetian blinds (1.4–7.9 kWh/(m 2 ·a), or 9%–54%, depending on climate and orientation), while maintaining acceptable or better visual comfort conditions throughout the interior space.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Solar Energy Integration in Buildings

Energy consumption in buildings has been steadily increasing and contributing up to 40% of the total energy use in developed countries [1]. In developing countries, the share of building energy consumption is smaller, but given population growth, urbanization, and rising demands for building services and comfort, the sharp rise of building energy use is probably inevitable. Thus, reducing building energy consumption plays a very important role in controlling global energy demand and mitigating climate change, so as to develop a sustainable environment. Solar energy, as the most important source of renewable energy, features the characteristics of clean, renewable, inexhaustible, and widely distributed energy, relative to other kinds of energy sources. Solar energy systems can now generate electricity at a cost equal to or lower than local grid-supplied electricity [2]. More importantly, solar energy can provide almost all forms of energy needed by buildings, through active or passive methods.

buildings↗

Integrated Dynamic Facade Control with an Agent-based Architecture for Commercial Buildings

Dynamic façades have significant technical potential to minimize heating, cooling, and lighting energy use and peak electric demand in the perimeter zone of commercial buildings, but the performance of these systems is reliant on being able to balance complex trade-offs between solar control, daylight admission, comfort, and view over the life of the installation. As the context for controllable energy-efficiency technologies grows more complex with the increased use of intermittent renewable energy resources on the grid, it has become increasingly important to look ahead towards more advanced approaches to integrated systems control in order to achieve optimum life-cycle performance at a lower cost. This study examines the feasibility of a model predictive control system for low-cost autonomous dynamic façades. A system architecture designed around lightweight, simple agents is proposed. The architecture accommodates whole building and grid level demands through its modular, hierarchical approach. Automatically-generated models for computing window heat gains, daylight illuminance, and discomfort glare are described. The open source Modelica and JModelica software tools were used to determine the optimum state of control given inputs of window heat gains and lighting loads for a 24-hour optimization horizon. Penalty functions for glare and view/ daylight quality were implemented as constraints. The control system was tested on a low-power controller (1.4 GHz single core with 2 GB of RAM) to evaluate feasibility. The target platform is a low-cost ($35/unit) embedded controller with 1.2 GHz dual-core cpu and 1 GB of RAM. Configuration and commissioning of the curtainwall unit was designed to be largely plug and play with minimal inputs required by the manufacturer through a web-based user interface. An example application was used to demonstrate optimal control of a three-zone electrochromic window for a south-facing zone. The overall approach was deemed to be promising. Further engineering is required to enable scalable, turnkey solutions.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

High-Performance Integrated Window and Façade Solutions for California

The researchers developed a new generation of high-performance façade systems and supporting design and management tools to support industry in meeting California’s greenhouse gas reduction targets, reduce energy consumption, and enable an adaptable response to minimize real-time demands on the electricity grid. The project resulted in five outcomes: (1) The research team developed an R-5, 1-inch thick, triplepane, insulating glass unit with a novel low-conductance aluminum frame. This technology can help significantly reduce residential cooling and heating loads, particularly during the evening. (2) The team developed a prototype of a windowintegrated local ventilation and energy recovery device that provides clean, dry fresh air through the façade with minimal energy requirements. (3) A daylight-redirecting louver system was prototyped to redirect sunlight 15–40 feet from the window. Simulations estimated that lighting energy use could be reduced by 35–54 percent without glare. (4) A control system incorporating physics-based equations and a mathematical solver was prototyped and field tested to demonstrate feasibility. Simulations estimated that total electricity costs could be reduced by 9-28 percent on sunny summer days through adaptive control of operable shading and daylighting components and the thermostat compared to state-of-the-art automatic façade controls in commercial building perimeter zones. (5) Supporting models and tools needed by industry for technology R&D and market transformation activities were validated. Attaining California’s clean energy goals require making a fundamental shift from today’s ad-hoc assemblages of static components to turnkey, intelligent, responsive, integrated building façade systems. These systems offered significant reductions in energy use, peak demand, and operating cost in California.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Split-pane electrochromic window control based on an embedded photometric device with real-time daylighting computing

Well-designed electrochromic (EC) glazing control can improve the energy performance of buildings and visual comfort of occupants in highly glazed buildings. Here in this paper, we designed and demonstrated a compact integrated EC glazing automation system to control tint states of a split-pane EC window according to variations of sky conditions. The control is based on monitoring the luminance distribution of the sky and real-time lighting computation for a building interior, using an embedded photometric device (EPD). It optimizes tint states of EC glazing to offer sufficient daylight provision and temper discomfort glare for occupants, which potentially mitigates excessive solar heat gain. ’In-situ’ experiments were conducted in a full-scale testbed to demonstrate the daylighting performance under various sky conditions. Finally, experimental results showed 83% of the working time for work-plane illuminance (WPI) and 95% of the time for daylight glare probability (DGP) were constrained in comfort range (WPIϵ[500, 2000] lux, DGP ≤ 0.35) by the automated EC glazing (controlled by EPD) under clear skies; 68% of the time for WPI and 94% of the time for DGP in confined range under clear skies with thin clouds; 62% of the time for WPI and 85% of the time for DGP in confined range under partly cloudy skies.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Electrochromic Window Demonstration at the John E. Moss Federal Building, 650 Capitol Mall, Sacramento, California

Dynamic windows have the potential to provide real-time optimization of perimeter zone energy use, peak demand, comfort, amenity, and cost criteria on a seasonal or even minute-to- minute basis in response to weather, occupant or regional grid demands. Electrochromic (EC) windows, a type of dynamic window, have the ability to adjust their tint dynamically in response to a small applied voltage. In previous studies, they have shown potential to reduce heating, ventilation and air conditioning (HVAC) energy consumption and increase occupant satisfaction. This technology is available in the U.S. as a commercial product from multiple vendors with high-capacity manufacturing facilities, and could be broadly deployed if successful in a pilot test. This Green Proving Ground (GPG) program study examines the energy and comfort performance of EC windows in south-facing perimeter zones of a typical U.S. General Services Administration GSA office building.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Innovative Glazing Materials

Windows have the unique capability of being able to achieve a net zero energy impact by admitting solar gains in the winter to offset thermal losses and admitting daylight to offset electric lighting. If rejection or admission of solar heat gains and daylight are appropriately timed, then heating, cooling and lighting energy use at the perimeter zone can be reduced to net zero energy levels. Nano-scale switchable coatings on glass have been developed to actively modulate solar intensity and spectral transmission. We provide a brief overview of these switchable glazing materials, discuss the desired performance objectives for such materials, and present results from recently completed monitored studies of state-of-the-art switchable windows, particularly with respect to occupant response and market factors. Careful application of state-of-the-art switchable windows and new material science developments on the horizon can deliver the desired net zero energy performance while meeting critical human factors and market related requirements.

Building energy efficiency↗

Efficient modeling of optically-complex, non-coplanar exterior shading: Validation of matrix algebraic methods

It has long been established that shading windows with overhangs, fins, and other types of non-coplanar systems (NCS) is one of the most effective ways of controlling solar heat gains in buildings because they intercept solar radiation prior to entry into the building. Designers however often specify non-opaque materials (e.g., louvers, fritted glass, expanded metal mesh) for these systems in order to admit daylight, reduce lighting energy use, and improve indoor environmental quality. Most simulation tools rely on geometric calculations and radiosity methods to model the solar heat gain impacts of NCS and cannot model optically-complex materials or geometries. For daylighting analysis, optically-complex NCS can be modeled using matrix algebraic methods, although time-efficient parametric analysis has not yet been implemented. Determining the best design and/or material for static or operable NCS that minimize cooling, heating, and lighting energy use and peak demand requires an iterative process. This study describes and validates a matrix algebraic method that enables parametric energy analysis of NCS. Such capabilities would be useful not only for design but also for development of prescriptive energy-efficiency standards, rating and labeling systems for commercial products, development of design guidelines, and development of more optimal NCS technologies. A facade or “F” matrix, which maps the transfer of flux from the NCS to the surface of the window, is introduced and its use is explained. A field study was conducted in a full-scale outdoor testbed to measure the daylight performance of an operable drop-arm awning. Simulated data were compared to measured data in order to validate the models. Results demonstrated model accuracy: simulated workplane illuminance was within 11–13%, surface luminance was within 16–18%, and the daylight glare probability was within 6–9% of measured results. Methods used to achieve accurate results are discussed. Results of the validation of daylighting performance are applicable to solar heat gain performance. Since exterior shading can also significantly reduce peak demand, these models enable stakeholders to more accurately assess HVAC and lighting impacts in support of grid management and resiliency goals.