Search NASA⌕ Search

Engineering topics

Liu, Yunting

Publications and source records attributed to Liu, Yunting.

Fast Quasi-Static Time-Series Simulation for Accurate PV Inverter Semiconductor Fatigue Analysis with a Long-Term Solar Profile

Power system simulations with long-term data typically have large time steps varying from one second to a few minutes. However, for PV inverter semiconductors, the minimum thermal stress cycle occurs over the fundamental grid frequency (50 or 60 Hz). This requires the time step of the fatigue simulation to be around 100 µs. This small time step requires long computation times to process yearly power production profiles. This paper proposes a fast fatigue simulation for inverter semiconductors using the quasi-static time series (QSTS) simulation concept. The proposed simulation calculates the steady state of the semiconductor junction temperature by using a Fast Fourier Transform (FFT). The small thermal cycling during a switching period and even over the fundamental waveform is disregarded to further accelerate the simulation speed. The resulting time step of the fatigue simulation is 15 minutes, which is consistent with the solar dataset. The error of the proposed simulation is 0.16% compared to the fatigue simulation results using the complete thermal stress profile. A PV inverter that responds to a Transactive Energy System (TES) is simulated to demonstrate the use of the proposed fatigue simulation. The proposed simulation has the potential to co-simulate with system level simulation tools that also adopt the QSTS concept.

Liu, Yunting↗

GMLC 1.5.03: Increasing Distribution System Resiliency using Flexible DER and Microgrid Assets Enabled by OpenFMB (Duke-RDS Final Report)

This is the final project report for the Grid Modernization Laboratory Consortium (GMLC) Resilient Distribution System (RDS) project titled “Increasing Distribution System Resiliency using Flexible DER and Microgrid Assets Enabled by OpenFMB”. The primary goal of this project was to increase the resiliency of distribution systems at utilities around the nation by deploying flexible operating strategies that engage end-use assets as a resource.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Integrating Transactive Energy into Reliability Evaluation for a Self-healing Distribution System with Microgrid

Non-utility owned distributed energy resources (DERs) are mostly untapped currently, but they can provide many grid services such as voltage regulation and service restoration, if properly controlled, and can improve the distribution systems reliability when coordinated with utility-owned assets such as self-healing control and microgrids. This paper integrates transactive energy control into the distribution system reliability evaluation to quantitatively assess the impact of non-utility owned DERs on reliability improvement. Here, a transactive reactive power control strategy is designed to incentivize the DERs to provide reactive power support for improving voltage profiles thus enabling additional customer load restoration during an outage. Also, an operational sequence to coordinate the non-utility owned DERs with the utility owned self-healing control and utility owned microgrids is designed and integrated into the service restoration process with the operational constraints guaranteed by checking the three-phase unbalanced power flow for post-fault network reconfiguration. The reliability indices are then calculated through a Monte Carlo simulation. The transactive reactive power control strategy is tested on a four-feeder distribution system operated by Duke Energy in the U.S. Results demonstrate that the non-utility owned DERs with the transactive control improve the reliability of both the system and critical loads by more than 30%.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Primary Frequency Control Using Motor Drives for Short Term Grid Disturbances

Industrial motor systems make up a quarter of all electric sales in the United States. Variable speed drives (VSDs) can provide energy efficiency savings to the customer by regulating motor speed based on specific and varying needs. In addition to the benefits provided to the customer, VSDs can provide support to the grid through ancillary services. The Center for Ultra-Wide-Area Resilient Electric Energy Transmission Networks (CURENT) developed a power electronics converter-based grid emulator to allow testing of various power system architectures and demonstration of key technologies in monitoring, control, actuation, and visualization. This paper proposes using an active front-end VSD's connected motor load to provide frequency regulation to a large scale power grid. Each part of the emulator is described including motor and power electronics model and control. The proposed frequency regulation is implemented in VSDs and modeled in both a transmission system in EMTDC/PSCAD and verified on CURENT's hardware testbed.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Modeling of Marginal Cost for PV Inverter Ancillary Services Considering Inverter Aging under Transactive Energy Framework

PV inverters can provide ancillary services while providing active power. Transactive energy system (TES) incentivizes PV inverter to provide ancillary services and compensates for the cost of additional power losses due to additional reactive power production. However, providing ancillary services can shorten the lifetime of the PV inverter since additional reactive power increases the thermal stress of the PV inverter. This paper theoretically derives the lifetime shortening effect of a PV inverter when providing ancillary services. Based on the lifetime estimation, an improved marginal cost curve for the PV inverter ancillary services is derived. The improved marginal cost quantitively describe the willingness of the PV inverter to provide ancillary services by the given active power production and the ambient temperature. The proposed model is validated by a simulation case study.

Liu, Yunting↗

Reconfigurable Real-Time Power Grid Emulator for Systems With High Penetration of Renewables

Novel power system control and new utility devices need to be tested before their actual deployment to the power grid. To assist with such a testing need, real-time digital emulators such as RTDS and Opal-RT can be used to connect to the physical world and form a hardware in the loop (HIL) emulation. However, due to the limitations of today's computational resources, the accuracy and fidelity suffer from different levels of model reductions in purely digital simulations. CURENT has developed a reconfigurable electric grid hardware testbed (HTB) to overcome the limitations of digital emulators. The HTB has been used to develop measurement, control, modeling, and actuation techniques for a national grid with a high penetration of renewables. The power electronic-based system includes emulators for synchronous generators; photovoltaics with grid-interfacing inverter; wind turbines; induction motor loads, ZIP loads, power electronic loads; batteries; ac and dc transmission lines; short circuit faults and grid relay protection; and a multiterminal HVDC overlay including power electronics interfaces. The system contains real elements of power flow, measurement, communication, protection, and control that mimic what would be seen in an actual electric grid. This paper presents an overview of the HTB and several scenarios that have been run to determine control and actions needed for the future power grid.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Aging Effect Analysis of PV Inverter Semiconductors for Ancillary Services Support

PV inverters can provide reactive power while generating active power. An ongoing microgrid implementation at Duke Energy actively engages non-utility PVs to generate/absorb reactive power in support of ancillary services to increase microgrid resiliency during extreme events. PV systems are requested to provide reactive power support: 1) in response to grid voltage variation to better regulate the local voltage; or 2) in response to utility incentives, such as following Transactive Energy System (TES) incentives. However, providing ancillary services might shorten the lifetime expectation of PV inverter semiconductors. This paper summarizes the potential impacts on a PV inverter semiconductor's lifetime when providing ancillary services. The analysis presented in this research work shows that providing reactive power support will increase the mean junction temperature and the junction temperature variation of the inverter diodes. This increased junction temperature will eventually lead to shorter diode lifetime. The lifetime estimation of semiconductors is briefly reviewed. The power losses of PV inverter semiconductors are derived as a support analysis to the junction temperature calculation. In addition, the impact of the filtering inductor on the semiconductor current distribution is discussed. The theoretical analysis presented in this research work is supported by simulation results.

14 SOLAR ENERGY↗