Ductless Heat Pump Energy Monitoring in a Cold Climate

In 2018, the City and Borough of Juneau, Alaska, set the goal of reaching 80% renewable energy for heating and transportation by 2045. An important factor to help reach this goal is energy-efficient home heating technologies such as ductless air- source heat pumps (DHPs), which rely on the local hydropower electric grid to provide space heating for an entire home or a main living area. To help residents reduce energy costs and move toward the community renewable energy goal, a team of local, state, and national partners joined together to run Thermalize Juneau 2021, an energy campaign that provided education, a simplified installation process, and a bulk purchase discount. Overall, the campaign enrolled 165 participants, resulting in 75 DHP installations and over 30 other energy efficiency improvements. To evaluate the reliability and energy use of the DHPs installed during the Thermalize Juneau campaign, researchers installed energy monitors on heat pumps of 14 participants and conducted interviews with homeowners. Data from two heating seasons (2021-2022 and 2022-2023) allowed researchers to examine the accuracy of pre-campaign energy savings predictions, establish energy savings for a small group of households, and provide insights on the energy use and occupant satisfaction of DHPs, which will help inform future heat pump deployment efforts in the area.

air source heat pump↗

Chapter 7: Principles of Northern Housing Design with Examples from Alaska

The Arctic has unique challenges and needs with respect to housing due to extreme climate, remoteness of communities, cultural aspects, and other factors. Attempts to adopt designs from other regions often resulted in failures, such as rotten building envelopes or features incompatible with local values. The main goal of this chapter is to inform a broad audience involved in northern housing about basic principles important for the Arctic. Particular attention is given to energy efficiency, health and durability, foundations appropriate for the underlying terrain such as permafrost, inclusive design process to assure meeting cultural and other needs and building design factoring in seasonality and logistical challenges of remote communities. Examples of existing prototype homes are given throughout the chapter to demonstrate how the individual principles can be successfully applied in real-life scenarios. This chapter also covers current trends, what the future might look like, how it is informed by indigenous perspectives, and how northern housing design can influence approaches in other regions of the world. The ultimate goal is to contribute to a vibrant future of communities in the Arctic and beyond.

Arctic↗

Heat Pumps and the Electrification of Heating

70 to 80% of building energy load in Alaska is heating. About 81% of residential heating is supplied via on-site combustion of fossil fuels. How can heat pumps provide heat energy from renewable sources?

Alaska↗

Energy Data from Heat Pumps Installed in Juneau, AK

Heat pumps offer a great low carbon emission method to heat homes. Thermalize Juneau 2021 was a clean energy campaign that helped homeowners in Juneau, Alaska install heat pumps into their homes. Juneau is located near the climactic limit of many heat pumps, and we were interested in how well the heat pumps can function in cold climates. This was done by using Sense meters to remotely monitor the energy usage of 10 homes with heat pumps. The Sense meters are small devices that connect to the electrical panel and monitor the energy use of multiple appliances through machine learning. First, we recorded the energy usage of a heat pump in the lab using both the Sense meter and the existing lab datalogger. Both recorded very similar energy usage data which confirmed that the Sense meter can accurately measure the fluctuations in the heat pump energy use. Next, we looked at the energy data from the Sense meters in the homes with heat pumps and paired it with local weather data to see how well the heat pumps functioned in the cold weather.

Alaska↗

Air Source Heat Pumps in Very Cold Climates

Air source heat pumps (ASHPs) in heating mode use a refrigeration cycle to remove heat from the outside air and transfer it into a building. Therefore, ASHPs have the potential to save energy compared to conventional heat sources that create the heat as opposed to transferring it from outside. Many cold climate ASHPs available on the market today can operate at outside temperatures of -25 degrees C (-13 degrees F) or even lower. As a result of technological advances and other factors, there is growing interest in ASHPs in cold climates, including very cold regions such as Alaska. However, guidance on the selection, installation, and operation of ASHPs in these very cold climates is limited, as significant data gaps exist regarding the performance of ASHPs in very cold environments. To address these data gaps and guide future innovations, our research team has studied the field performance of several ASHP installations in Alaska and done lab evaluations of several ASHP models using a cold chamber. While a cold chamber cannot fully reflect field conditions, it allowed for changing one variable at a time and gaining additional understanding of the behavior of ASHPs that would be difficult to gain from field studies only. This study focused on two main variables: the temperature in the chamber (representing the outdoor temperature) and the level of thermal loading of the ASHP. The results from the field as well as the lab show that ASHPs can operate with relatively high efficiency even in very cold climates if used in appropriate situations and in an appropriate way. It was found that not only the outside temperature, but also the level of thermal loading is a significant factor affecting the ASHP efficiency and needs to be carefully considered when sizing and operating ASHPs in very cold climates.

air source heat pump↗

Empirical Study of the Effect of Thermal Loading on the Heating Efficiency of Variable-Speed Air Source Heat Pumps

Heating buildings with air source heat pumps (ASHPs) has the potential to save energy compared to utilizing conventional heat sources. Accurate understanding of the efficiency of ASHPs is important to maximize the energy savings. While it is well understood that, in general, ASHP efficiency decreases with decreasing outdoor temperature, it is not well understood how the ASHP efficiency changes with different levels of thermal loading, even though it is an important consideration for sizing and controlling ASHPs. The goal of this study was to create an empirical model of the ASHP efficiency as a function of two independent variables–outside temperature and level of thermal loading. Four ductless mini-split ASHPs were evaluated in a cold chamber where the temperature (representing the outdoor temperature) was varied over a wide range. For each temperature, the ASHP performance data were collected at several levels of thermal loading. The data for all four ASHPs were combined and approximated with an analytical function that can be used as a general model for the ASHP steady-state efficiency as a function of the outside temperature and level of thermal loading. To the knowledge of the authors, no such empirical model that is solely based on third-party test data has been published before. While limitations exist, the model can be used to help guide future selection and operation of ASHPs.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Clean Indoor Air and Lower Environmental Impacts: Heat Recovery Ventilation in Cold Climates

Over half of Alaska homes are at risk of poor indoor air quality, which increases the risk of respiratory and other illnesses for people and animals. Heat recovery ventilators (HRVs) provide warm, fresh air to a building interior while minimizing energy use. They can be programmed to provide varying amounts of fresh air to ensure adequate ventilation for occupants and can be configured to filter air during wildfires or other events. In addition to improving the safety of indoor air and extending the life of a building, HRVs can improve surrounding outdoor air because they reduce the amount of fossil fuels needed to heat a building. Recent research by CCHRC has focused on lowering barriers to using HRVs in cold climates through laboratory evaluations and homeowner education. This poster will cover data on indoor air quality in Alaska, results of CCHRC research, and future research questions.

buildings↗

Impact of Intake and Exhaust Ducts on the Recovery Efficiency of Heat Recovery Ventilation Systems

The heat recovery efficiency of ventilation systems utilizing heat recovery ventilators (HRVs) depends not only on the heat recovery efficiency of the HRV units themselves but also on the intake and exhaust ducts that connect the HRV units to the outside environment. However, these ducts are often neglected in heat loss calculations, as their impact on the overall heat recovery efficiency of HRV systems is often not understood and, to the knowledge of the authors, a mathematical model for the overall heat recovery efficiency of HRV systems that accounts for these ducts has not been published. In this research, a mathematical model for the overall heat recovery efficiency of HRV systems that accounts for the intake and exhaust ducts was derived and validated using real-life data. The model-predicted decrease in heat recovery efficiency due to the ducts was in reasonable agreement (relative error within 20%) with the real-life measurements. The results suggest that utilizing this model allows for more correct ventilation heat loss calculations compared to using the heat recovery efficiency of the HRV unit alone, but more field studies are needed to verify the accuracy of this model in a wide range of applications.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗