Search NASA⌕ Search

Engineering topics

Mendiola, Emanuel

Publications and source records attributed to Mendiola, Emanuel.

At least 19 records

A CHIL Validation of Machine Learning-Assisted Methods for Real-Time Controls of Solar PV for Grid Services

Recent research has highlighted the potential for solar to act as a zero-marginal-cost and zero-emission flexibility resource on the bulk power system when operated with advanced control systems. To increase the performance of these systems, leading technologies, including machine learning (ML) and hierarchical inverter set point allocation, have been proposed; however, these technologies lack comprehensive validation under real-world application scenarios. This paper addresses this gap by designing and developing a controller-hardware-in-the-loop framework to evaluate the performance of different flexible solar technologies in responding to automatic generation control signals in a closed-loop fashion. Simulation results indicate the superior performance of an ML-based approach compared to the conventional reference-control grouping-based approach, showcasing its potential to support grid stability and operational efficiency.

closed-loop validation↗

Probing Signal-Based Inertia and Frequency Response Estimation for Power Systems With High Levels of Inverter-Based Resources

Power system inertia is the inherent capability of a power system to resist changes in its frequency during disturbances. Real-time inertia estimation technology has become more important due to the low-inertia issues caused by the increasing integration levels of inverter-based resources (IBRs) from renewable energy; however, existing inertia estimation methods hardly consider multiple frequency response controls that act within the same time frame as conventional inertial response, thus making measured inertia values vary under different testing conditions. To resolve this issue, this paper proposes a novel real-time estimation method to simultaneously estimate a power system's inertia constant and frequency response droop constant using a well-designed probing signal. First, we formulate the inertia and frequency response model of a power system with IBRs. Second, through the integration and manipulation of the developed model, we propose a multivariate linear regression-based estimation method that is resilient to measurement noise. Third, we design a probing signal that can be injected by IBRs to incite the required transients for estimation. Finally, we validate the proposed estimation method through comprehensive power-hardware-in-the-loop experiments using inverter hardware and a realistic island power system model. The results demonstrate that the proposed method can accurately estimate the inertia and droop value of the power system with grid-following IBRs and grid-forming IBRs with virtual synchronous machine control.

frequency response↗

GFM Inverter Hardware Testing

This presentence provides overview of NREL's testing capabilities and experience with advanced testing of multimegawatt grid-forming inverters.

GFM↗

Probing Signal-Based Inertia and Frequency Response Estimation for Power Systems with High Penetration of Inverter-Based Resources: Preprint

Power system inertia is the inherent capability of a power system to resist changes in its frequency during disturbances. Real-time inertia estimation technology has become more important due to the low-inertia issues caused by the increasing integration levels of inverter-based resources (IBRs) from renewable energy; however, existing inertia estimation methods hardly consider multiple frequency response controls that act within the same time frame as conventional inertial response, thus making measured inertia values vary under different testing conditions. To resolve this issue, this paper proposes a novel real-time estimation method to simultaneously estimate a power system's inertia constant and frequency response droop constant using a well-designed probing signal. First, we formulate the inertia and frequency response model of a power system with IBRs. Second, through the integration and manipulation of the developed model, we propose a multivariate linear regression- based estimation method that is resilient to measurement noise. Third, we design a probing signal that can be injected by IBRs to incite the required transients for estimation. Finally, we validate the proposed estimation method through comprehensive power- hardware-in-the-loop experiments using inverter hardware and a realistic island power system model. The results demonstrate that the proposed method can accurately estimate the inertia and droop value of the power system with grid-following IBRs and grid-forming IBRs with virtual synchronous machine control.

frequency response↗

A CHIL Validation of Machine Learning-Assisted Methods for Real-Time Controls of Solar PV for Grid Services: Preprint

Recent research has highlighted the potential for solar to act as a zero-marginal-cost and zero-emission flexibility resource on the bulk power system when operated with advanced control systems. To increase the performance of these systems, leading technologies, including machine learning (ML) and hierarchical inverter set point allocation, have been proposed; however, these technologies lack comprehensive validation under real-world application scenarios. This paper addresses this gap by designing and developing a controller-hardware-in-the-loop framework to evaluate the performance of different flexible solar technologies in responding to automatic generation control signals in a closed-loop fashion. Simulation results indicate the superior performance of an ML-based approach compared to the conventional reference-control grouping-based approach, showcasing its potential to support grid stability and operational efficiency.

closed-loop validation↗

Regional Power System Black Start with Run-of-river Hydropower Plant and Battery Energy Storage

Battery energy storage systems (BESSs) are an important asset for power systems with high integration levels of renewable energy, and they can be controlled to provide various critical services to the power grid. This paper presents the real-world experience of using a megawatt-scale BESS with grid-following (GFL) and grid-forming (GFM) controls and a run-of-river (ROR) hydropower plant to restore a regional power system. To demonstrate this, we carry out power-hardware-in-the-loop experiments integrating an actual GFL- or GFM-controlled BESS and a load bank. Both the simulation and experimental results presented in this paper show the different roles of GFL- or GFM-controlled BESS in power system black starts. The results provide further insight for system operators on how GFL- or GFM-controlled BESS can enhance grid stability and how an ROR hydropower plant can be converted into a black-start-capable unit with the support of a small-capacity BESS. The results show that an ROR hydropower plant combined with a BESS has the potential of becoming one of enabling elements to perform bottom-up black-start schemes as opposed to conventional bottom-down method, thus enhancing the system resiliency and robustness.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Real-Time Inertia Estimation Tool Implementation Based on Probing Signals

As renewable energy penetration increases and the traditional generators retire in power grids, system inertia decreases and exhibits significant daily fluctuations. Furthermore, fast frequency responses (FFRs) provided by the inverter-based resources (IBRs) begin to playa very critical role and bring new challenges to real-time system inertia monitoring due to the difficulties of quantifying its artificial inertia contribution. Thus, necessitating an accurate real-time inertia estimation tool will not only benefit the secure power grid operations, but also provide insights on assessing the artificial inertia contribution from the IBRs. This paper presents a probing-based real-time inertia estimation tool that has been validated through a power-hardware-in-the-Ioop (PHIL) test system using identical hardware battery energy storage system (BESS) and control in an actual power grid. Preliminary results indicate high estimation accuracy of the developed tool and pave the way for the field test and deployment.

inverter-based resources↗

Testing GFM and GFL Inverters Operating With Synchronous Condensers

Inverter-based resources (IBRs) are quickly evolving into a source of reliability services to the electric grid. Penetration levels of variable generation are rapidly increasing, ranging from 60% -70% in some systems. To go further, a fundamental shift is required to address challenges associated with grid stability. Synchronous condensers (SCs) are considered an important complementary technology in such transitions. This paper provides one-of-a-kind insights into real experimental results from operating a real MW-scale system consisting of a 2.2-MVA grid-forming (GFM) and grid-following (GFL) battery energy storage system, 2.5-MVA SCs, and a 3-MVA load bank operating as a small, islanded grid. Challenges that are expected in larger systems were mimicked in this small but real system to demonstrate seamless transitions from one mode to another as well as stable operation with different combinations of GFM and GFM resources, including a "loss of last synchronous generator" case. The experimental results presented in this paper are a valuable resource to everyone involved in developing and validating models or developing controls of power systems consisting of inverters and synchronous condensers.

grid-following converter↗

Validation of the Fault Ride-Through Response of a Generic EMT Inverter Model by Laboratory Testing

This paper presents the validation of the fault ride-through response of a large-scale inverter model using laboratory testing of a commercial inverter. First, we present the generic inverter model specifications. The generic inverter control is developed based on the fault ride-through response performance requirements of IEEE Std 2800-2022 for inverter-based resources. Next, we present laboratory tests that emulate voltages at the inverter terminal resulting from balanced and unbalanced faults on the transmission system. The tests are performed on a commercia12.2 MVA battery storage inverter at the U.S. National Renewable Energy Laboratory. Comparisons of the model's response to the laboratory measurements show the generic model presented can predict the controlled response of the commercial equipment. The differences between the model's response and the laboratory measurements during the initial transient at fault inception are discussed.

fault ride-through↗

A Reversed Impedance-Based Stability Criterion for IBR Grids

The existing impedance-based stability criterion is effective for analyzing local control interactions; however, it is difficult to scale the existing criterion to analyze wide-area control interactions among numerous IBRs through a complex power system network. The scaled version of the existing criterion requires the impedance response of each IBR in the system as well as of the network looking from all the IBRs. It is quite challenging to obtain all these impedance responses because of the computational effort and the requirement of separately scanning the impedance of the network and the IBRs. We propose a reversed criterion for the impedance-based stability analysis to address these problems. In contrast to the existing criterion, the reversed criterion analyzes the stability of a power system when an IBR is disconnected from the system. The reversed criterion estimates the impact of an IBR on the frequency and damping of power system oscillation modes using the impedance scans of only the IBR and the grid at its terminal. It can be sequentially applied at different IBRs to evaluate their impact on the power system stability. In addition to scalability, the reversed criterion gives flexibility to focus only on a few selected IBRs, depending on their rating, the magnitude of oscillations observed at their terminals, and the vendor support available for implementing stabilizing control system updates. The reversed criterion is demonstrated on a 14-bus power system with 100% IBRs.

control interactions↗

Multi-Timescale Integrated Dynamics and Scheduling for Solar (MIDAS-Solar) (Final Technical Report)

Solar photovoltaic (PV) installations have experienced unprecedented growth in the United States. PV will become not only an energy producer but also a necessary provider of ancillary services at multiple timescales. Conventional methods to simulate power systems operations - such as long-term production simulation (which typically considers schedules from hours to minutes by using an optimization framework) and short-term transient studies (which simulate dynamics from seconds to sub-seconds using state variables and differential equations) - are not sufficient for studying the multiple-timescale variation of solar generation and its impact on system reliability. Long-term system economics and short-term system dynamics are highly coupled, particularly when the penetration level of renewable generation is extremely high, because the uncertainty and variability of solar generation will impact both power system steady-state and dynamic performance. This project helps meet and exceed the U.S. Department of Energy Office of Energy Efficiency and Renewable Energy Solar Energy Technologies Office goal of systems integration by directly addressing this stability and reliability challenge for power grid planning and operation. We have developed a temporally comprehensive, closed-loop simulation model, named Multi-timescale Integrated Dynamics and Scheduling (MIDAS), that seamlessly simulates power system operations from economic scheduling (day-ahead to hours) to dynamic response analysis (seconds to sub-seconds). For schedules with very high levels of inverter-based resources (IBRs), up to and including 100%, the stability of grid controls has been evaluated through electromagnetic transient (EMT) simulations and power-hardware-in-the-loop (PHIL) simulations of key transient events at key schedule points. Specifically, MIDAS provides: 1) a closed-loop simulation framework for simulating timescales from economic scheduling to dynamic stability analysis; 2) machine learning-based stability assessment; 3) EMT modeling and analysis for large-scale power systems; 4) MIDAS PHIL test bed. We worked with Hawaii Electric Companies to apply the MIDAS study framework to a Maui grid study. The entire island's transmission system was modeled in detail - from a yearly scheduling model, to a second-level frequency dynamic model, down to a sub-second-scale EMT model to address critical stability issues. The project demonstrated how MIDAS can help system planners and operators assess system reliability and stability while the power grid is marching toward a high-renewable, high-IBR future. In this Maui grid study, we found that 100% instantaneous IBR operation is achievable in EMT simulation and PHIL testing, and grid planners and operators might need new analysis/simulation tools to assess grid reliability and stability in the scheduling stage. MIDAS will bring Maui and other systems closer to 100% clean and stable energy futures. (In this study, we examined transient stability. Other topics necessary for 100% IBR operation, such as protection and resource adequacy, were not examined.)

100% Renewables↗

NREL CGI and PHIL Platform for Validation of Multi-Technology Energy Systems at Scale

The presentation is an update on National Renewable Energy Laboratory Flatirons Campus' capabilities around multi-megawatt grid simulation and power hardware-in-the-loop. Recent improvements in operational and dynamic range of existing 7MVA Controllable Grid Interface (CGI) are described together with improvements in site-wide automation and data acquisition systems. In later part of presentation, a second 19.9MVA CGI that is currently under development is introduced. Its features are described further explaining future site's capabilities.

acquisition↗

A Reversed Impedance-Based Stability Criterion for IBR Grids: Preprint

The existing impedance-based stability criterion is effective for analyzing local control interactions; however, it is difficult to scale the existing criterion to analyze wide-area control interactions among numerous IBRs through a complex power system network. The scaled version of the existing criterion requires the impedance response of each IBR in the system as well as of the network looking from all the IBRs. It is quite challenging to obtain all these impedance responses because of the computational effort and the requirement of separately scanning the impedance of the network and the IBRs. We propose a reversed criterion for the impedance-based stability analysis to address these problems. In contrast to the existing criterion, the reversed criterion analyzes the stability of a power system when an IBR is disconnected from the system. The reversed criterion estimates the impact of an IBR on the frequency and damping of power system oscillation modes using the impedance scans of only the IBR and the grid at its terminal. It can be sequentially applied at different IBRs to evaluate their impact on the power system stability. In addition to scalability, the reversed criterion gives flexibility to focus only on a few selected IBRs, depending on their rating, the magnitude of oscillations observed at their terminals, and the vendor support available for implementing stabilizing control system updates. The reversed criterion is demonstrated on a 14-bus power system with 100% IBRs.

control interactions↗

GIST (Grid Impedance Scan Tool) [SWR-22-73]

NREL has developed GIST (Grid Impedance Scan Tool) to scan the impedance response of inverter-based resources such as land-based and offshore wind power plants, solar power plants, etc., from their electromagnetic transient simulation models to evaluate their impact on grid stability. GIST can scan impedance response of inverter-based resources from vendor-supplied black-box simulation models without requiring internal proprietary details, enabling detailed stability analysis of power systems with high levels of inverter-based generation.

Shah, Shahil↗

Unleashing the Frequency: Multi-Megawatt Demonstration of 100% Renewable Power Systems with Decentralized Communication-Less Control Scheme

Power systems, which range in size from small microgrids to island systems to large regional grids, are typically managed by a central controller that requires complex communication methods and can be unreliable and pose cyber security risks in certain applications, especially when controlling a larger number of nodes. We propose an inherently robust, scalable method of integration using multiple energy storage systems and distributed energy resources, which does not require any means of dedicated communication. This method moves beyond the paradigm of controlling grid frequency at a fixed value (e.g., 60 Hz), instead allowing the frequency to fluctuate within certain limits (e.g., 59.6-60.4 Hz). With a greater operating range, the frequency can carry necessary information from energy storage systems to highly variable distributed energy resources like photovoltaics, wind, hydro, etc.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Grid-Forming Wind Power

This presentation is a summary of research conducted by NREL team in the area of developing and testing grid forming controls by wind power.

grid forming↗