Quantified Fast Frequency Response of Inverter-Based Resources for Bulk-Power System Study

Quantifying fast frequency response (FFR) of inverter-based resources (IBRs) is crucial for robust frequency regulation, managing resources, and improving system reliability in the power grids with high penetration levels of IBRs. This paper proposes a concept of frequency response scheme that its response is quantifiable and applicable to the generic IBR models. To achieve this, a stepwise-energy function is derived as a control module by considering operational constraints of IBRs. Then the module is implemented along with generic IBR models in electromagnetic transient (EMT) and electromechanical-based software. To quantify the FFR, the implemented module calculates available incremental active power for a specific time duration. This energy profile is being updated depending on IBR’s operating conditions and is provided into a power grid upon detecting a frequency event. Thus, due to this characteristic, this scheme can quantify the FFR and enable applicable IBRs to provide their available headroom within frequency arrest period. Thereby, this scheme can help estimate IBRs’ frequency response and is more effective in improving the initial frequency response than frequency-dependent control schemes: rate-of-change-of-frequency based and droop-based control schemes. The performance of the proposed scheme was tested under different IBR penetration levels using PSLF and PSCAD simulators.

Kim, Jinho↗

Optimal Droop Setting for Congestion Reduction in a 100% Grid-Forming Inverter-based Power System

he high penetration of inverter-based resources (IBRs) introduces new challenges to power systems due to the complex inverter control. However, IBRs can be configured to maximize their benefits to improve system resilience and reliability. This paper proposes a steady-state optimization model that aims to mitigate transmission congestion in a 100% grid- forming (GFM) IBR-based power system. This goal is achieved by determining the optimal droop settings for the GFM IBRs under different congestion conditions due to renewable energy and load variations. The numerical solution is rigorously verified by a high-fidelity model of the IEEE 39-bus test system with detailed GFM IBR control in the time-domain electromagnetic transient (EMT) simulation tool PSCAD. The numerical solution and simulation results show a significant congestion reduction while meeting all other operating requirements. It is also observed that the numerical solving time is substantially less compared to the EMT simulation time.

Nguyen, Quan H.↗

An Assessment of Deploying Advanced Pumped Storage Hydropower Technology in U.S. Electricity Markets

Pumped storage hydropower (PSH) is a type of hydropower technology where energy can be stored and generated by moving water between two reservoirs of differing elevations. In addition to providing 97% of the total utility-scale hydropower storage in the United States, PSH plants have operational characteristics - such as high ramp rates and the ability to provide reserves - that contribute to greater flexibility and reliability of the power grid. New PSH technologies can provide additional flexibility beyond existing, fixed-speed units. With the emergence of high levels of variable renewable energy resources (e.g., wind and solar), energy storage is expected to be crucial to the reliability and reliance of the power grid in a low-carbon future. At diurnal and longer durations, PSH plants have some of the lowest costs per unit of energy, have been proven to be reliable and efficient, are not cycle-limited, and typically have long lives, often exceeding 50 years. The work presented here focuses on a new generation of PSH: ternary PSH and quaternary PSH (together referred to as T/Q-PSH). Given recent experience in Europe, grid operators in the United States and elsewhere are increasingly focusing their attention on T/Q-PSH as a proven, financeable technology that can offer utility-scale, long-duration, fast-acting energy storage capabilities and grid services. T/Q-PSH differs from conventional PSH in that it can provide fast-response ancillary services during both generating and pumping operations. This capability together with fast mode switching times are key attributes that make T/Q-PSH technologies attractive for managing and stabilizing electricity systems with high amounts of variable renewable energy.

ENERGY PLANNING, POLICY, AND ECONOMY,HYDRO ENERGY↗

Inter-Area Oscillation Damping with Type-5 Wind Power Plant

This paper investigates the potential of using brushless excitation (BLE) for not only riding through the fault but also to damp inter-area power oscillation with the help of a synchronous generator (SG) used in Type 5 Wind Power Plant (WPP). In BLE, an auxiliary synchronous generator (ASG) behaving like an exciter is coupled and driven by the rotor of the main SG. The BLE's field current's ASG is fed by two separate loops of the automatic voltage regulator (AVR) and power system stabilizer (PSS). The AVR system implements a control loop to regulate the generator terminal voltage, VT. For the PSS, the kinetic energy of the wind turbine is utilized according to the estimated rotational speed of the synchronous generator shaft of the SG. It may mitigate the necessity of any curtailment of active power for damping. The effectiveness of the proposed control scheme is verified with a three-phase short circuit fault in a two-area power system.

brushless↗

Enhanced Frequency Support Scheme of Generic Inverter-Based Resource Models for Renewable-Dominated Power Grids

The frequency response of SG-dominated power grids is predictable ahead of an occurrence of a frequency event because the frequency response of SGs is consistent, and it can be inferred from the swing equation [1]. However, increasing the portion of IBRs in an SG-dominated power grid might make the characteristics of the conventional power grids no longer valid because this changing resource mix affects grid dynamics and controls [2]. Thus, maintaining these characteristics greatly benefits the control and operation of the power grids with high penetration of IBRs. To maintain these characteristics in IBR-dominated power grids, IBRs should have frequency response capability similar to that of an SG. The WECC modeling validation subcommittee has developed generic IBR models for large system planning [3]-[5]. These models can represent various vendors' dynamic behavior for WTG, PV, and ESS [5]. The current generic IBR models approved by WECC can provide frequency response only from droop control loops in REPC models [6], [7]. The contribution of the loops is proportional to the frequency deviation from the nominal frequency. Thus, it presents an insufficient contribution to arrest frequency variation compared to the frequency response of SGs because it allows a high ROCOF in the early stage of frequency events. This shortfall will become greater as the PL of IBRs increases in power grids. Controller enhancement for the generic IBR models is required to secure the frequency stability under high PL of IBRs as in the SG-dominated power grids. This paper proposes a control extension for the generic IBR models to enhance the frequency support capabilities and discusses the classification of frequency support for the different types of IBR considering their operating constraints. An inertial control scheme is implemented in the REPC and REEC models of the generic IBR models to achieve these objectives. The inertial control scheme includes the following stages: Control area data acquisition, inertia time constant estimation, IBR-related constraint check, IBR contribution determination, and inertial response provision. In the scheme, a REPC acquires control area data from a system operator and estimates a total inertia time constant for the control area the applicable IBR power plant belongs. Then, the estimated inertial time constant is transferred to each IBR controller—REEC—within the power plant. Each REEC checks the availability of applicable IBR for inertial response participation. If the IBR is available, the REEC amplifies the estimated inertial time constant to utilize it for inertial response provision. In this way, the proposed inertial response scheme extends the functionality of the generic IBR models to provide SG-like frequency response within their constraints. Various scenarios considering different IBR types, IBR penetration levels, and frequency control schemes were simulated and compared in an IEEE 39-bus system using PSCAD simulator to verify the effectiveness of the proposed scheme.

Kim, Jinho↗

Impact of Quaternary Pumped Storage Hydropower on Frequency Response of U.S. Western Interconnection with High Renewable Penetrations

As renewable penetration increases in the United States, maintaining stability and reliability of low-inertia power grid by providing sufficient frequency control capability becomes a challenge. Advanced pumped storage hydro technologies (APSH) will be expected to play an important role for future grid as not only an energy supplier, but also as an ancillary services provider. This paper studies the impact of using quaternary pumped storage hydropower (Q-PSH), as one of the newly proposed APSH technology, to provide primary frequency response. To quantify the impact of Q-PSH on frequency response of the U.S. Western Interconnection, a user-defined dynamic model of Q-PSH is developed on the GE Positive Sequence Load Flow (PSLF) platform and is implemented in a set of detailed U.S. Western Electricity Coordination Council (WECC) planning cases in which renewable penetration levels are 20%, 40%, 60% and 80%. Simulation results show that Q-PSH can help improve frequency nadir and settling frequency comparing to the conventional PSH.

frequency response↗

Co-Development of Oscillating Water Column (OWC) and Offshore Power Station

The project proposed an Oscillating Water Column (OWC) at a low power rating (1-5kW); to build a prototype and perform field testing within 1–3 years and achieving a commercial version of the OWC 3–5 years. We selected the OWC off-the-shelf components to secure the supply-chain sources and to warrant stable and minimum pricing. We want to curtail the capital cost by reducing the weight and volume of the overall system structure at the design level by designing a high-speed turbine generator and optimizing the airspeed amplification. We want to minimize the operational and maintenance (O&M) costs through simplified architecture, minimal parts, modular/plug-and-play, and easy access designs.

16 TIDAL AND WAVE POWER↗

Impact of Quaternary-Pumped Storage Hydropower on Frequency Response of U.S. Western Interconnection with High Renewable Penetrations: Preprint

As renewable penetration increases in the United States, maintaining stability and reliability of low-inertia power grid by providing sufficient frequency control capability becomes a challenge. Advanced pumped storage hydro technologies (APSH) will be expected to play an important role for future grid as not only an energy supplier, but also as an ancillary services provider. This paper studies the impact of using quaternary pumped storage hydropower (Q-PSH), as one of the newly proposed APSH technology, to provide primary frequency response. To quantify the impact of Q-PSH on frequency response of the U.S. Western Interconnection, a user-defined dynamic model of Q-PSH is developed on the GE Positive Sequence Load Flow (PSLF) platform and is implemented in a set of detailed U.S. Western Electricity Coordination Council (WECC) planning cases in which renewable penetration levels are 20%, 40%, 60% and 80%. Simulation results show that Q-PSH can help improve frequency nadir and settling frequency comparing to the conventional PSH.

frequency response↗

Investigations into Balancing Peak-to-Average Power Ratio and Mean Power Extraction for a Two-Body Point-Absorber Wave Energy Converter

The power harnessed by wave energy converters (WECs) in oceans is highly variable and, therefore, has a high peak-to-average power (PTAP) ratio. To minimize the cost of a WEC power take off (PTO) system, it is desirable to reduce the PTAP ratio while maximizing the mean power extracted by WECs. The important issue of how PTAP ratio reduction measures (such as adding an inertia element) can affect the mean power extracted in a reference model has not been thoroughly addressed in the literature. To investigate this correlation, this study focuses on the integration of the U.S. Department of Energy’s Reference Model 3, a two-body point absorber, with a slider-crank WEC for linear-to-rotational conversion. In the first phase of this study, a full-scale numerical model was developed that predicts how PTO system parameters, along with an advanced control algorithm, can potentially affect the proposed WEC’s PTAP ratio as well as the mean power extracted. In the second phase, an appropriate scaled-down model was developed, and extracted power results were successfully validated against the full-scale model. Finally, numerical and hardware-in-the-loop (HIL) simulations based on the scaled-down model were designed and conducted to optimize or make trade-offs between the operational performance and PTAP ratio. The initial results with numerical and HIL simulations reveal that gear ratio, crank radius, and generator parameters substantially impact the PTAP ratio and mean power extracted.

16 TIDAL AND WAVE POWER↗

Electrical Systems of Pumped Storage Hydropower Plants: Electrical Generation, Machines, Power Electronics, and Power Systems

Adjustable-speed (AS) pumped storage hydropower (PSH) technology has the potential to become a large, consistent contributor to grid stability enabling higher penetrations of wind and solar energy on the future U.S. power system. AS-PSH has high-value characteristics, such as fast response to provide ancillary services to the grid, because it is a power converter interface with the grid (like battery storage), but at the same time it has the energy content large enough to supply both short-term (seconds-to-minutes) and long-term (minutes-to-hours) of energy needs, like more conventional power plants. However, designs must be optimized to lower the capital expenditure (CapEx) and to provide a high-quality grid interface capability (e.g. power quality, ancillary service provider, fault-tolerant or fault ride-through capability), which is a primary factor in the acceptance of AS-PSH into a utility’s generation mix. This CapEx will be greatly affected by the cost savings associated with the civil structure, turbine design, power electronics, control systems, or unique generator designs. A holistic design must be considered to get a full picture of the benefits of the technology proposed. The AS-PSH can be controlled to reduce the impact of transient disturbance on a power system and at the same time can be controlled to minimized subsequent component fatigue and potential oscillation modes within the plant, with the overall impact in reducing the operational expenditures (OpEx).Generating clean power to meet standards such as Institute of Electrical and Electronics Engineers (IEEE) 519 and International Electrotechnical Commission (IEC) 1000-3-2 will be a continuing challenge. For many technology developers, however, improved AS-PSH technologies will become a key component of generator-storage systems of the future given the prospects of increased performance and decreasing costs, and the ever-increasing penetration of renewables (e.g wind power and solar power).

13 HYDRO ENERGY↗

A Novel Framework for Optimizing Ramping Capability of Hybrid Energy Storage Systems

Hybrid Energy Storage System has been widely applied in aerospace, electric vehicle, and microgrid applications. The advantages are that they include complimentary technologies with both high power and energy capabilities. HESS have the potential to be useful to the bulk power systems, for example to increase the value of energy produced by variable generation resource through enabling participation in ancillary service markets. Actualizing the benefits of HESSs requires optimizing the combined ramping capability of aggregated HESS resources. To provide quality ancillary service, source of HESSs locating at multiple sites of variable generation resource must be optimally sized and cohesively controlled. Optimizing aggregated resources can be formulated as an optimization problem. Successfully solving this problem not only requires using effective solution methods but also depends on accurately and rapidly setting the necessary parameters in the problem formula. This article proposes a novel framework with double-layer structure to solve the optimization problem of aggregating ramping capability. Program developed on the upper layer focuses on solving the optimization of aggregating ramping capability among multiple HESSs and is compatible with most existing optimization algorithms. Program on lower layer of the framework targets at optimizing the local control of a single HESS based on a thorough analytics of HESS operation strategy presented in this article. Result of local optimization is also provided to upper layer program for updating the parameters in formula of optimization problem. Real time hardware-in-the-loop test is conducted to verify the performance of the optimization framework developed. The work presented is expected to provide guidance for implementing this framework in practical operation.

Luo, Yushen↗

Modelling and control coordination scheme of a wind‐to‐hydrogen set for future renewable‐based power systems

New challenges regarding system stability and efficiency arise when power systems operate with a high penetration level of inverter‐based renewable sources (IBRSs) and few synchronous generators. Since IBRSs have been on the rise, to secure the stable operation of future power systems, IBRSs will be required to support systems without having to rely on remaining synchronous generators. Also, to efficiently manage the uncertainty of renewable production, power‐to‐gas technology can provide the required flexibility. This study proposes modelling and a control coordination scheme (CCS) of a wind‐to‐hydrogen (W2H) set to optimise electricity production from a variable‐speed wind turbine generator (WTG) while helping balance between supply and demand in a system. To achieve this, a grid‐forming (GFM) inverter‐based WTG is modelled and a set of electrolyser and fuel cell is integrated at the DC circuit of a GFM‐WTG to be coordinated. Furthermore, the CCS offers an opportunity to reduce the investment cost for deploying a W2H set by utilising the control capabilities of a WTG and reducing the need for an additional device. The performance of the proposed W2H set with the CCS was verified considering the variations in system load and wind speed by using Power System Computer Aided Design (PSCAD)/ElectroMagnetic Transients including Direct Current (EMTDC).

Kim, Jinho↗

Investigating the Impact of Power-Take-Off System Parameters and Control Law on a Rotational Wave Energy Converter’s Peak-to-Average Power Ratio Reduction

Due to the irregular nature of real waves, the power captured in a wave energy converter (WEC) system is highly variable. This is an important barrier to the effective use of WECs. To address this challenge, this study focuses on a rotational WEC power-take-off system in which high-speed and high-efficiency generators along with a torque/power smoothing inertia element can be effectively utilized. In the first phase of this study, the U.S. Department of Energy’s reference model 3 (WEC-Sim RM3; two-body point absorber), along with a slider-crank WEC, were integrated for linear to rotational conversion. Relative motion between the float and spar in RM3 was the driving force for this slider-crank WEC, which is connected to a motor/generator set through a gearbox. RM3 geometry was scaled down by 25 times to work within the limits of the physical motor/generator set used in the experimentation. Once the integration in a hardware-in-the-loop simulation environment was successfully completed, data on the peak-to-average power ratio was collected for various wave conditions including regular and irregular waves. The control algorithm designed to keep the system in resonance with waves was able to maintain relatively high speed depending on the specific gear ratio and wave period. Initial results with hardware-in-the-loop simulations reveal that gear ratio and crank radius have a strong impact on the peak-to-average power ratio. In addition, it was found that output power from the generator was maximized at a larger gear ratio, as the crank radius was increased.

50 EE - Wind and Water Power Program - Water (EE-4↗

Dynamic Modeling of Full Converter Adjustable-speed Pumped Storage Hydropower (FC AS-PSH)

Full converter adjustable-speed pumped storage hydropower (FC AS-PSH) technology, as one of advanced-PSH technology, is developed from wind turbine technology. By making the synchronous machine connect to the grid through a full-size converter, FC AS-PSH has a wider adjustment range of speed and a better reactive power control capability compared with a doubly-fed asynchronous generator AS-PSH technology. When it plays as an energy backup in the power system, FC AS-PSH can provide a much faster response than conventional-PSH (C-PSH) which makes this technology provide better ancillary service for a high renewable penetrated system. In this paper, the dynamic modeling of FC AS-PSH is fully studied. We develop a detailed model of this technology in the IEEE 14-bus system based on GE Positive Sequence Load Flow (PSLF) platform. Especially, the first governor model is developed based on the Engineer’s Program Control Language (EPCL) user-defined model in this platform. All operation modes are validated and studied under a system contingency. Besides, comparison cases between FC AS-PSH and C-PSH are studied to show advantages providing from FC AS-PSH when it works with renewable energy.

50 EE - Wind and Water Power Program - Water (EE-4↗

Developing of Quaternary Pumped Storage Hydropower for Dynamic Studies

Quaternary pumped storage hydropower (Q-PSH) technology, as one of the new advanced-PSH technology, has been developed by taking advantage of Conventional-PSH (C-PSH) and Adjustable Speed-PSH (AS-PSH). By combining adjustable-speed pump unit and conventional hydropower turbine unit in the quaternary configuration, Q-PSH has the more competitive capability of providing fast power support in the future high renewable penetrated power system. Acting as energy storage (ES), Q-PSH provides promising power supply to deal with the uncertainty and variability from renewable energy generation. This paper focuses on the dynamic modeling of Q-PSH technology employing full-converter machine and the impact of Q-PSH on the frequency response in a system. The detailed model of Q-PSH is developed and implemented in the IEEE 14-bus system based on GE Positive Sequence Load Flow (PSLF) platform, which captures the dynamic of multiple operation modes, especially hydraulic short-circuit (HSC) operation mode. Several cases are set up to reveal the advantages of Q-PSH technology when power electronic based renewable energy generation is deployed in the system. Sensitivity studies of the controller in pump governor show the impact of parameters in pump response performance. The comparison case illustrates the impact of frequency response provided by the Q-PSH in the system.

dynamic modeling↗

Impacts of Ternary-Pumped Storage Hydropower on U.S. Western Interconenction with Extremely High Renewable Penetrations

In recent years, ternary pumped storage hydropower (T-PSH), as one of the advanced PSH technologies, has attracted more attention from the industry. The interest is because of the capability of providing fast power support for the future electric grid with high penetration of renewable energy (RE). This paper focuses on studying the impact of T-PSH on frequency response of the U.S. Western Interconnection under different penetration levels of RE, which are from 20% to 80%. The detailed model of T-PSH is developed and implemented in the Western Interconnection grid model based on the GE Positive Sequence Load Flow (PSLF) platform, which can capture the unique dynamics of hydraulic short-circuit (HSC) mode and fast mode switching of T-PSH. To reveal the dynamic benefit from T-PSH, the frequency response of the Western Interconnection has been compared with and without T-PSH. In addition, a new solution is discussed that uses T-PSH to improve system stability issues caused by high RE penetration.

13 HYDRO ENERGY↗

Cost Estimation of a Permanent Magnet Synchronous Machine for Use in Adjustable Speed-Pumped Storage Hydropower

Electric machine design has become an easier process with the availability of computers in recent decades. However, the interest in electric machine design among students has declined. University-level design courses must compete with courses perceived as more desirable by the potential job market. Hence, the power system engineers with this expertise are very few and are nearing retirement. Contrarily, renewable energy has been picking up in the past few decades. The indeterminacy and variation of renewable energy sources require a balancing mechanism to maintain the constant voltage and frequency of the grid. Adjustable-Speed Pumped-Storage Hydropower plants are considered the contender for future energy storage, providing large capacity and fast-acting response. Large-scale hydropower applications depend on the natural characteristics of each project site, making less expensive, off-the-shelf generators unfeasible. This work gives a shortcut to estimate the cost of constructing a permanent magnet generator for low-volume manufacturing.

13 HYDRO ENERGY↗