Search NASA⌕ Search

Engineering topics

Munk, Jeffrey

Publications and source records attributed to Munk, Jeffrey.

At least 37 records · Page 2

Hybrid Heat Pump Controls: Conventional Dual Fuel versus Seamlessly Fuel Flexible Heat Pump

This paper compares the performance of a novel seamlessly fuel flexible heat pump (SFFHP) and conventional dual fuel heat pump (DFHP) for space heating. The conventional dual fuel systems either run on the gas furnace or electric heat pump at any given moment, as a comparison, the proposed seamlessly fuel flexible heat pump simultaneously consumes gas and electricity by continuously optimizing the proportion of each. The process air flows across the heat pump condenser first and then flows across the furnace coil, therefore, the heat pump temperature lift is reduced. SFFHP delivers energy savings by allowing each subsystem, i.e., gas furnace and electric heat pump, to operate where it performs best.For DFHP, two operation control strategies, i.e., non-restricted control and restricted control, are available on market. For the non-restricted mode, the thermostat has a switching temperature-programmed according to the balancing point of heating load and capacity curve. Heat pump operates above the switching temperature, while the furnace takes over under the switching temperature. For the restricted control, the compressor of a heat pump is disabled below a predefined lockout outdoor temperature to let the furnace take over. For SFFHP, a model predictive control strategy is developed to continuously adjust the capacities of the electric heat pump and gas furnace based on the foreseen weather data, utility price signals, and marginal grid emission signals with the goal of minimizing the utility cost and CO2 emission while guaranteeing comfort requirements.In this paper, DFHP and SFFHP are simulated using high-fidelity heat pump performance curves generated from DOE/ORNL heat pump design model. Performance comparison of DFHP and SFFHP during 2019-2020 heating season in Los Angeles shows that SFFHP with model predictive control achieves 23% utility cost reduction and 17 % CO2 emission reduction. Case studies demonstrate that SFFHP can deliver significant reductions in peak demand, utility cost, and CO2 emission. As a result, SFFHP can deliver superior benefits for utility cost reduction and CO2 emission reduction over conventional dual fuel heat pump.

Li, Zhenning↗

Demonstration of Intelligent HVAC Load Management With Deep Reinforcement Learning: Real-World Experience of Machine Learning in Demand Control

We report that buildings account for 40% of total primary energy consumption and 30% of all CO 2 emissions worldwide. A large portion of building energy consumption is due to heating, ventilation, and air-conditioning (HVAC) systems. In the summer, for example, more than 50% of a building’s electricity consumption is used for cooling. With proper energy management, buildings can provide load shifting, peak shaving, frequency regulation, and many other demand response services.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Hierarchical Model-Free Transactive Control of Residential Building Loads: An Actual Deployment

The transformation of electricity systems into more sustainable configurations brought some new challenges. The uncertain, intermittent, and variable nature of renewable energy sources require a significant amount of load demand flexibility, in which grid-interactive buildings (GEBs) are important flexible assets for electricity systems. In this regard, many demand response (DR) tools have been developed to harness this demand flexibility. However, such tools are mostly simulation-based or deal with a single load, which may not be sufficient to demonstrate their effectiveness. Towards this end, this paper presents a real-world field implementation and testing of a hierarchical model-free transactive DR control approach on actual GEBs. The control implementation incorporates elements of virtual battery, game theory, and model-free control mechanisms. The proposed approach was tested using a total of five GEBs, each having three zones. The results show that the proposed approach can mostly achieve all intended objectives, including flexibility estimation, peak load reduction, power tracking, and controlling GEBs while maintaining occupants’ comfort.

Amasyali, Kadir↗

COVID-19 pandemic ramifications on residential Smart homes energy use load profiles

The COVID-19 pandemic has significantly affected people’s behavioral patterns and schedules because of stay-at-home orders and a reduction of social interactions. Therefore, the shape of electrical loads associated with residential buildings has also changed. In this paper, we quantify the changes and perform a detailed analysis on how the load shapes have changed, and we make potential recommendations for utilities to handle peak load and demand response. Our analysis incorporates data from before and after the onset of the COVID-19 pandemic, from an Alabama Power Smart Neighborhood with energy-efficient/smart devices, using around 40 advanced metering infrastructure data points. This paper highlights the energy usage pattern changes between weekdays and weekends pre– and post–COVID-19 pandemic times. The weekend usage patterns look similar pre– and post–COVID-19 pandemic, but weekday patterns show significant changes. We also compare energy use of the Smart Neighborhood with a traditional neighborhood to better understand how energy-efficient/smart devices can provide energy savings, especially because of increased work-from-home situations. HVAC and water heating remain the largest consumers of electricity in residential homes, and our findings indicate an even further increase in energy use by these systems.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Ultra-clean condensing gas furnace enabled with acidic gas reduction

Natural gas furnaces are the most common space heating equipment in the U.S. residential and commercial building markets. However, current residential natural gas condensing furnaces generate substantial acidic condensate as well as significant emissions of sulfur oxides (SOx), nitrogen oxides (NOx), carbon monoxide (CO), hydrocarbons (HC), and methane (CH 4 ) contributing to environmental degradation of air, water, and soil. This paper describes a novel solution to reduce the environmental impact of natural gas condensing furnaces based on the technology of monolithic acidic gas reduction (AGR) catalyst for SOx trapping, NOx redox to nitrogen, and oxidation of formic acid, CO, HC, and CH 4 . This technology offers a new condensing natural gas furnace with both ultra-clean flue gas and neutral condensate. Here, a prototype of the condensing gas furnace with the AGR component is demonstrated to have condensate with pH = 7, NOx emissions of 1–2 ng/J, and an annual fuel utilization efficiency (AFUE) of 96%. The AGR component and the AGR-enabled furnace were tested for long-term reliability and durability, as well as for SOx storage and regeneration activity. In addition, this paper provides new data on measurements of the specific acidic gas content in natural gas condensing furnaces.

37 INORGANIC, ORGANIC, PHYSICAL, AND ANALYTICAL CH↗

A study on computational fluid dynamics modeling of a refrigerated container for COVID-19 vaccine distribution with experimental validation

A key issue with the distribution of vaccines to prevent COVID-19 is the temperature level required during transport, storage, and distribution. Typical refrigerated transport containers can provide a temperature-controlled environment down to -30 °C. However, the Pfizer vaccine must be carefully transported and stored under a lower temperature between -80 °C and -60 °C. One way to provide the required temperature is to pack the vaccine vials into small packages containing dry ice. Dry ice sublimates from a solid to a gas, which limits the allowable transport duration. This can be mitigated by transporting in a -30 °C refrigerated container. Moreover, because the dry ice will sublimate and thereby release CO 2 gas into the transport container, monitoring the CO 2 concentration within the refrigerated container is also essential. In the present work, a 3D computational fluid dynamics model was developed based on a commercially available refrigerated container and validated with experimental data. The airflow, temperature distribution, and CO 2 concentration within the container were obtained from the simulations. The modeling results can provide guidance on preparing experimental setups, thus saving time and lowering cost, and also provide insight into safety precautions needed to avoid hazardous conditions associated with the release of CO 2 during vaccine distribution.

59 BASIC BIOLOGICAL SCIENCES↗

COVID 19 vaccine distribution solution to the last mile challenge: Experimental and simulation studies of ultra-low temperature refrigeration system

Most COVID-19 vaccines require ambient temperature control for transportation and storage. Both Pfizer and Moderna vaccines are based on mRNA and lipid nanoparticles requiring low temperature storage. The Pfizer vaccine requires ultra-low temperature storage (between -80 °C and -60 °C), while the Moderna vaccine requires -30 °C storage. Pfizer has designed a reusable package for transportation and storage that can keep the vaccine at the target temperature for 10 days. However, the last stage of distribution is quite challenging, especially for rural or suburban areas, where local towns, pharmacy chains and hospitals may not have the infrastructure required to store the vaccine. Also, the need for a large amount of ultra-low temperature refrigeration equipment in a short time period creates tremendous pressure on the equipment suppliers. In addition, there is limited data available to address ancillary challenges of the distribution framework for both transportation and storage stages. As such, there is a need for a quick, effective, secure, and safe solution to mitigate the challenges faced by vaccine distribution logistics. The study proposes an effective, secure, and safe ultra-low temperature refrigeration solution to resolve the vaccine distribution last mile challenge. Furthermore, the approach is to utilize commercially available products, such as refrigeration container units, and retrofit them to meet the vaccine storage temperature requirement. Both experimental and simulation studies are conducted to evaluate the technical merits of this solution with the ability to control temperature at -30 °C or -70 °C as part of the last mile supply chain for vaccine candidates.

60 APPLIED LIFE SCIENCES↗

Comparative analysis of model-free and model-based HVAC control for residential demand response

In this paper, we present a comparative analysis of model-free reinforcement learning (RL) and model predictive control (MPC) approaches for intelligent control of heating, ventilation, and air-conditioning (HVAC). Deep-Q-network (DQN) is used as a candidate for model-free RL algorithm. The two control strategies were developed for residential demand-response (DR) HVAC system. We considered MPC as our golden standard to compare DQN's performance. The question we tried to answer through this work was, What % of MPC's performance can be achieved by model-free RL approach for intelligent HVAC control?. Based on our test result, RL achieved an average of ≈ 62% daily cost saving of MPC. Considering the pure optimization and model-based nature of MPC methods, the RL showed very promising performance. We believe that the interpretations derived from this comparative analysis provide useful insights to choose from various DR approaches and further enhance the performance of the RL-based methods for building energy managements.

Kurte, Kuldeep↗

Connected Loads – Grid Connected Appliances: Commercial Refrigeration System Fault Detection and Diagnostics

As one of the most energy-intensive end-uses in the commercial buildings sector, supermarkets consume around 50 kWh/ft 2 (or 537.6 kWh/m 2 ) of electricity annually, or more than 2 million kWh of electricity per year for a typical store. The biggest consumer of energy in a supermarket is its refrigeration system, which accounts for 40–60% of its total electricity usage and is equivalent to about 2–3% of the total energy consumed by commercial buildings in United States, or around 0.5 quadrillion Btu (or 0.53 quadrillion KJ). Also, the supermarket refrigeration system is one of the biggest consumers of refrigerants. Current supermarket refrigeration systems rely on high global warming potential hydrofluorocarbon refrigerants. Reducing refrigerant usage or using environment friendly alternatives can result in significant climate benefits. Transcritical CO2 refrigeration systems have attracted more attention in recent years because of their zero-carbon emission advantages compared with traditional refrigerants. These systems are widely used in commercial buildings such as supermarkets. The refrigeration system can also be adapted to handle flexible building loads and be integrated into grid response transactive control to balance the supply and demand of the electric grid. Even minor improvements in the efficiency and operational reliability of supermarket refrigeration systems can create significant value in terms of saving energy, improving food quality, protecting the environment, reducing carbon footprint, and enhancing electric grid resilience.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

A System of Agents for Supporting Optimization and Control of a Connected Community

The residential sector consumes a significant portion of the electricity sold in the United States. Above 60% of the energy used in the sector is used to operate heating, ventilation, and air conditioning (HVAC) systems and water heating (WH) systems. With the increase of intelligence in the grid and the new decision and control options enabled by the Internet of Things; control of these devices can be used to support the grid. Therefore, this article presents a scalable multiagent system for optimizing HVAC and WH systems while maintaining comfort. It allows a utility to orchestrate the shifting of energy from critical periods without direct control, but instead by using a price signal. The architecture, optimization formulation, implementation strategy and results from an implementation project are discussed.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Impact of Connected Communities

Buildings account for 35% of CO 2 emissions and almost 40% of the United States’ energy use. High-performance homes and neighborhoods play an important role in supporting efforts to decarbonize the US power system by 2035. Significant reductions in CO 2 emissions within the residential sector can be realized through electrification of loads paired with the flexibility created by leveraging smart Internet of Things (IoT) capabilities to shift energy use based on grid signals, thus improving generation/distribution efficiency and maximizing the use of renewable generation capacity. All of this can be achieved while allowing smart home appliances and equipment to meet homeowner needs – including reducing power bills - while optimizing operation in conjunction with the grid using novel control techniques. The Grid-Interactive Efficient Buildings Roadmap by the US Department of Energy’s (DOE’s) Building Technologies Office (BTO) notes that implementing grid-interactive efficient building (GEB) technology has the potential to reduce CO 2 emissions by 80 million tons/year—roughly equivalent to 17 million cars. To achieve this vision, the US Department of Energy’s Oak Ridge National Laboratory (ORNL)—in collaboration with Southern Company Research & Development, Alabama Power, Georgia Power, BTO and the US DOE’s Office of Electricity (OE) —is developing and demonstrating novel connected communities at two locations. Southern Company in turn engaged with industry partners, including design firms, residential developers, and residential HVAC and appliance manufacturers because their participation would be critical to the success of the initial research project, as well as the future scaling to the Southern Company service territory and beyond. Impacts of the Connected Communities projects in Alabama and Georgia are outlined including: energy, grid services and data management learnings; homeowner feedback; vendor engagement; adoption by utilities; technical, policy and business model challenges.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Cost-Optimized Cold Climate Heat Pump Development and Field Test

Cold climate heat pumps (CCHPs) expand the heat pump market to climates where heating demand is dominant. They can achieve more than 70% energy savings compared with electric resistance heating and operate at lower cost than using tank-stored propane to fuel a furnace. A high-efficiency heat pump with a heating seasonal performance factor (HSPF)—as defined by the Air-Conditioning, Heating, and Refrigeration Institute (AHRI 2008)—greater than 10.0 would be more efficient than gas heating in terms of source energy. However, developing a cost-effective CCHP involves some challenges. A typical single-speed, air-source heat pump (ASHP) with an HSPF of 7.7 Btu/Wh does not work well under cold outdoor temperature conditions typical of cold climate locations for four major reasons: 1. Discharge temperature is too high—The low suction pressure and high compression pressure ratio at low ambient temperatures causes high compressor discharge temperatures in excess of the maximum limit for many of the compressors on the market. Furthermore, system charge of a heat pump is usually optimized in the cooling mode, which leads to overcharge conditions in the heating mode, further increasing the discharge temperature. 2. Heating capacity is insufficient if sized to meet the building design cooling load— Heating capacity of a single-speed heat pump decreases with ambient temperature. The heating capacity at -13°F (-25°C) typically decreases to 20%–40% of the rated heating capacity at 47°F (8.3°C) (~equivalent to the rated cooling capacity at 95°F [35°C]). Therefore, a single-speed heat pump, typically sized to match the building design cooling load, cannot provide adequate heating capacity to match the building heating load at low ambient temperatures. The capacity deficit is filled by inefficient resistance heat, thus lowering the system efficiency and significantly increasing power demand. 3. Cyclic loss is significant if sized to meet the building design heating load—If a single-speed heat pump is sized to meet the heating load, it will be significantly oversized relative to the cooling load in many cold climates. This will cause excessive on/off cyclic loss during the cooling and heating operations at moderately low ambient temperatures. Thus, capacity modulation capability (e.g., using a variable-speed or multi-stage compressor) is necessary for a CCHP, which uses its full capacity to meet the peak heating load and partial capacity to meet the cooling and part-load heating loads. 4. Coefficient of performance (COP) is low—Heating COP degrades significantly at low ambient temperatures owing to the large temperature difference between the heat source and sink. A target CCHP should be sized to meet the building design heating load while minimizing the cyclic loss for the cooling and heating operations at moderate ambient temperatures.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Methodology for interpretable reinforcement learning model for HVAC energy control

Deep reinforcement learning (DRL) approaches have been used in various application areas to improve efficiency, optimization, or automation. However, very little is known about how the DRL algorithms make decisions and what features affect their performance. Using a case study of a DRL based Heating, Ventilation and Air Conditioning (HVAC) optimization methodology, we demonstrate how we can address these challenges by applying interpretability tools and systematically exploring the model inputs for better understanding the DRL behaviour and decision making process. We developed a methodology for interpretable reinforcement learning and evaluated our approach in real-world house located in Knoxville, TN. Our findings explain the reasoning behind DRL-based optimization decisions under different circumstances which has been discussed and confirmed by the experts in the field.

Kotevska, Olivera↗

A Real-time Agent Based Optimization and Control Approach for Residential Building Heating Ventilation and Air Conditioning Systems

The prevalence of the loT (Internet of Things) is fostering the development of new control options and decision making that was not previously available. This is creating a wealth of opportunities for real-time control approaches and systems that can optimize for a common goal. This paper presents a smart residential neighborhood with optimization at the residential level utilizing a system of agents. The optimization utilizes information and modeling to optimize variable speed HVAC real-time operation in actual residential buildings. Data is presented showing the performance of the optimization and conclusions are drawn on next steps for development.

Hall, Joni↗

Double Deep Q-Networks for Optimizing Electricity Cost of a Water Heater

Electric water heaters represent 14% of the electricity consumption in the residential buildings and the cost associated with domestic water heating account for a good portion of the household expenses in the United States. In this context, intelligent control of water heaters gained a lot of research attention. In recent years, a significant number of intelligent water heater controllers, with various methods and intended uses, have been proposed. However, existing studies are mostly model-based approaches that require an accurate modelling of the water heater. Towards addressing this research gap, this paper presents a model-free reinforcement learning-based controller for a day-ahead price market. The controller aims to minimize the cost of domestic water heating while maintaining the user comfort. The results showed that the developed controller can help save energy cost while maintaining the temperatures within the desired comfort band.

Amasyali, Kadir↗

Data Analysis Approach for Large Data Volumes in a Connected Community

Recent advancements within smart neighborhoods where utilities are enabling automatic control of appliances such as heating, ventilation, and air conditioning (HVAC) and water heater (WH) systems are providing new opportunities to minimize energy costs through reduced peak load. This requires systematic collection, storage, management, and in-memory processing of large volumes of streaming data for fast performance. In this paper, we propose a multi-tier layered IoT software framework that enables effective descriptive and predictive data analysis for understanding live operation of the neighborhood, fault identification, and future opportunities for further optimization of load curves. We then demonstrate how we achieve live situational awareness of the connected neighborhood through a suite of visualization components. Finally, we discuss a few analytic dashboards that address questions such as peak load reductions obtained due to optimization, customer preference for automatic control of appliances (do they override the automatic control of HVAC?, etc.). 1 1 This manuscript has been authored by UT-Battelle, LLC under Contract No. DE-AC05-00OR22725 with the U.S. Department of Energy. The United States Government retains and the publisher, by accepting the article for publication, acknowledges that the United States Government retains a nonexclusive, paid-up, irrevocable, world-wide license to publish or reproduce the published form of this manuscript, or allow others to do so, for United States Government purposes. The Department of Energy will provide public access to these results of federally sponsored research in accordance with the DOE Public Access Plan (http://energy.gov/downloads/doe-public-access-plan).

Chinthavali, Supriya↗

Analysis of power conversion technology options for a self-powered furnace

A self-powered furnace is defined as one that imports no electricity: a power cycle integrated into the furnace generates all the electrical power needed, and the heat rejected by the power cycle contributes to space heating. This paper presents criteria for selection of suitable power generation technology for such a furnace. A weighting system was presented to assign weight to each criterion based on its importance to the success of a self-powered furnace implementation. Power generation candidates were reviewed and scored based on the selection criteria. The top five candidates were analyzed to quantitatively compare the additional heat exchange requirements they impose on a baseline furnace. Air-cooled internal combustion engines and microturbine generators had negligible impact on the heat exchange requirement compared to a baseline furnace. Liquid-cooled internal combustion engines increased the heat exchange requirement by a factor of 1.5. Thermoelectric generators and thermophotovoltaic increased the heat exchange requirement by a factor of roughly 2.5. Organic Rankine cycle increased the heat exchange requirement by a factor of 5.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Low global warming potential (GWP) refrigerant supermarket refrigeration system modeling and its application

As an environmentally friendly low global warming potential (GWP) refrigerant, Carbon dioxide (CO 2 ) has continuously gained popularity and research attention as alternative refrigerant for supermarket refrigeration system. In this paper, to fulfill the increasing need of accurate Low-GWP supermarket refrigeration models for development of supervisory level control and optimization strategies, a high fidelity model is developed for CO 2 transcritical supermarket refrigeration system which includes compressor rack of low temperature (LT) compressors and medium temperature (MT) compressors, air-cooled gas cooler, evaporator, expansion valves and other auxiliary equipment. A resistance-capacity model structure is proposed to simulate the display cases. Semi-thermodynamic models are proposed to estimate reciprocating compressors volumetric efficiency and power consumption. Furthermore the zone modeling approach is used for evaporator simulation, and air-cooled gas cooler is modeled with distributed modeling method. The expansion valve simulation is based on orifice flow model. To calibrate these models, both manufacture performance data and experimental data are used. The experiments are conducted with a full instrumental CO 2 supermarket refrigeration system installed in Oak Ridge National Lab Flexible Research Platform (FRP). The simulation model can predict the system performance, including power consumption, cooling capacity, mass flow rate, temperature, and pressure, with high accuracy (within ±4%) compared to experimental data. In addition, this developed model has been used to create the system optimum high side pressure for high side expansion valve control, and to generate wide operating range simulation data for developing the batter-equivalent commercial refrigeration system model which can be used in grid interactive control development.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗