Search NASA⌕ Search

Engineering topics

Nayak, Neeraj

Publications and source records attributed to Nayak, Neeraj.

Cloud-Based Demonstration of the Eastern Interconnection Situational Awareness Monitoring System (ESAMS)

This report describes a cloud-based implementation and field demonstration of the Eastern Interconnection Situational Awareness and Monitoring System (ESAMS). ESAMS was developed to support the detection and source localization of forced oscillations using synchrophasor measurements from tie-lines connecting areas served by different reliability coordinators (RCs), so that RCs could better coordinate their response to wide-area events. A previous effort had identified deployment barriers associated with hosting shared situational awareness tools at a single RC. To address these barriers, ESAMS was migrated to Amazon Web Services and evaluated in a six-month field demonstration. ISO New England (ISO-NE) and PJM streamed data to the platform using AWS Direct Connect and a site-to-site VPN, respectively. The resulting multi-utility measurement footprint enabled regional source localization across major portions of the U.S. Eastern Interconnection and supported routine identification of oscillation events. During the final three months of the trial, 24 events above 2 MW/MVAR were detected. The largest detected oscillation approached a 25 MW peak-to-peak amplitude, and the longest persisted intermittently for more than 11 hours. The demonstration also assessed operational considerations—including data transfer volumes, end-to-end latency, and cloud computing costs—and found that network and compute requirements were modest relative to typical cloud capabilities while providing performance comparable to prior on-premises deployments. Overall, the results indicate that cloud hosting can provide a practical path to shared interconnection-wide oscillation monitoring. The cloud ESAMS demonstration establishes a foundation for broader utility participation and for building future wide-area analytics that leverage measurements across organizational boundaries.

Follum, James D.↗

Online Tracking of Two Dominant Inter-Area Modes of Oscillation in the Eastern Interconnection

Reliable power system operation requires that small-signal stability be maintained at all times. Mode meters are measurement-based tools that provide operators with situational awareness of the system's stability margin. They operate by continually tracking the inter-area modes of oscillation that govern small-signal stability. This paper reports on the deployment of mode meters for online monitoring of two dominant modes of oscillation in the United States' Eastern Interconnection (EI). The use of measurements from system operators across the interconnection to provide continuous tracking is novel in the EI. Results from over four months of analysis reveal diurnal patterns in the modes and demonstrate that they can be tracked through a variety of system conditions. The results from this study continue to build an understanding of the EI's modes that will inform future modeling and monitoring efforts.

Follum, James D.↗

Discovery of Signatures, Anomalies, and Precursors in Synchrophasor Data with Matrix Profile and Deep Recurrent Neural Networks (Final Project Report)

The widespread deployment of phasor measurement unit (PMU) across the U.S. together with the burgeoning machine learning technology made it possible to develop data-driven PMU data analytics to improve grid security and reliability in a more insightful and effective manner. Although PMU applications have been explored for over a decade, the representative PMU usage is limited to the bulk power system monitoring mainly due to the data integrity issues associated with PMUs (typically missing, fragmented, and wrongly amplified data). To forge a breakthrough on this stalemate and embrace PMUs for power system control and protection as well, we applied various advanced machine learning and big data analysis technology to the power system event detection and classification as the first step toward the power system control and protection pertaining to grid security enhancement.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Robust Learning of Dynamic Interactions for Enhancing Power System Resilience (Final Scientific Report)

The overall goal of the project is to leverage robust graphical learning and phase measurement unit (PMU) data to learn the dynamic interactions of electrical grid components in order to improve the power system resilience. Specifically, the learned dynamic interaction graphs are utilized to detect known and unknown anomalous patterns in power systems, identify high-risk operational conditions, and enable risk-based cascading mitigation.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Online Detection of Low-Quality Synchrophasor Data Considering Frequency Similarity

Here, this letter proposes a new approach for online detection of low-quality synchrophasor data under both normal and event conditions. The proposed approach utilizes the features of synchrophasor data in time and frequency domains to distinguish multiple regional PMU signals and detect low-quality synchrophasor data. It is more effective to detect low-quality data with apparently indistinguishable profiles. Case studies from recorded synchrophasor measurements verify the effectiveness of the proposed approach for detecting low-quality synchrophasor data in frequency, voltage magnitude and voltage angle.

42 ENGINEERING↗

Real Time Applications Using Linear State Estimation Technology (RTA/LSE)

Electric Power Group, LLC (EPG) was awarded DOE OE0000849 to design, develop, and demonstrate three real-time applications for monitoring power system stability. The applications use phasor measurements and processing by a linear state estimator (LSE) to improve system visibility and accuracy. These applications leverage the large and expanding phasor measurement systems being deployed by utilities throughout the world, and specifically in the United States. Phasor measurements provide a much more detailed view of the power systems than traditional SCADA systems, so can provide better visibility of events and an early warning of developing problems. These three applications are real-time contingency analysis (RTCA), area angle monitoring (AAM), and a voltage stability index (VSI). The project was fully completed as proposed. All three applications were successfully implemented and demonstrated. There were challenges the caused project delays, however. While the RTCA is based on well-known concepts and readily available tools, its deployment using phasor measurements meant it needed to be adapted to sometimes sparse measurements and limited coverage areas. EPG met these challenges with extensive modeling and testing. The AAM is based on unproven research, so EPG had to deal with a lot of unknowns and develop additional methods for practical implementation. These activities took more time than anticipated, so required extra time for development. In addition, there was difficulty getting adequate measurement locations for successful deployment and utility installation delays. Consequently, the project required a time extension to complete. These three real-time applications, RTCA, AAM, and VSI, use only phasor measurement input. Since they do not require the EMS or other measurement systems, they can serve as a backup and security check for the EMS. Phasor measurements are validated and extended by an LSE. The LSE will always produce an output even when some inputs are impaired, so the RT applications will operate even when the EMS state estimator does not converge and the applications it supports cannot function. Consequently, these RT applications can provide valuable additional reliability for control center operation.

24 POWER TRANSMISSION AND DISTRIBUTION↗