A Co-Simulation Framework for Steady-State Analyses of Multiple Droop-based MTdc Grids in Continental-Scale Systems

The growing scale and complexity of planning continental hybrid ac and multi-terminal dc (MTdc) systems require scalable steady-state modeling and analysis approaches not currently available in commercial tools. This paper presents a comprehensive multi-fidelity model-conversion framework that enables the efficient transition of MTdc grid models from production cost modeling (PCM) and approximated ac power flow to detailed ac–MTdc power flow for large-scale planning studies. The core of this framework is a scalable co-simulation approach that, for the first time, enables power flow analysis in continental-scale ac–MTdc systems. It seamlessly couples commercial ac solvers with a detailed MTdc grid model that incorporates droop-based control and current-limiting strategies of multiple meshed MTdc grids. Leveraging this capability, an evaluation framework to systematically assess and compare different MTdc power redispatch strategies under ac and dc contingencies is introduced. The proposed framework and algorithm are evaluated using a combined Western and Eastern Interconnection system with 11 MTdc grids of various sizes, showing a coherent transition from PCM to detailed ac–MTdc power flow and improved system performance in voltage regulation and line overload mitigation following typical contingencies.

Nguyen, Quan H.↗

Western Interconnection Baseline Study

The purpose of the baseline study is to evaluate the degree to which current industry planning processes meet the national 2035 decarbonization goals for the Western Interconnection. This analysis serves as a comparative baseline for the scenario analysis conducted in the NTP Study using a Western Interconnection dataset that is readily available to industry. This baseline analysis differs from the production cost modeling analysis and power flow analysis in the main NTP Study report (forthcoming). In particular, the analysis presented in this report reflects a business-as-usual future with an optimistic build out of specific planned transmission projects and foreseeable generation. In contrast, the NTP Study models a future generation and transmission expansion based on optimization from a capacity expansion model. The analysis presented herein also reflects a 2030 timeframe, whereas the main NTP Study production cost modeling analysis and power flow analysis reflect a 2035 time frame. This baseline analysis utilizes industry’s most reliable data to account for future transmission projects across various stages of development, with a particular focus on those in the permitting stage. Additionally, it incorporates projections for changes in generation capacity (both additions and retirements). This baseline analysis outlines a probable trajectory, given current process and practice, for the future of the bulk power system with a horizon extending to 2030.

29 ENERGY PLANNING, POLICY, AND ECONOMY↗

Bulk Electric System Protection Model Demonstration with 2011 Southwest Blackout in DCAT

Protection equipment modeling is critical to power systems planning and operational studies, it enables more accurate system response when control actions including protection relays and remedial action schemes (RAS) are adequately modeled and assessed. This paper incorporates a generic protection philosophy to the Dynamic Contingency Analysis Tools (DCAT), and demonstrates its effectiveness by modeling 2011 Pacific Southwest Blackout event autonomously.

Bulk Electric System, Protection, Blackout, DCAT↗

Database Management Module Framework for Dynamic Contingency Analysis and Visualization

The Dynamic Contingency Analysis Tool (DCAT) is being developed to mimic the response of generation dynamics, protection, and load components to extreme contingencies in power systems. Currently, DCAT generates a huge data set, with the analysis results stored in multiple subfolders using a great many files in different formats (power flow cases, time series, figures, spreadsheets). To help power system engineers thoroughly understand and analyze system behavior under many scenarios and contingencies, we developed a database management module (DBM) that enables future integration of DCAT with industry-grade Big Data analytical and interactive visualization platforms. In this paper, we demonstrate the DBM framework with interactive analytics and visualization for DCAT on the synthetic South Carolina 500-bus power system model using hurricane contingencies that capture possibilities for an extreme contingency. DCAT’s advanced data management and interactive visualization can help planning engineers to visually explore and analyze system behavior, all in one view.

Cascading, dynamic simulations, database managemen↗

Dynamic Contingency Analysis Tool 2.0 User Manual with Test System Examples

This document introduces Version 2 of the Dynamic Contingency Analysis Tool (DCAT) software package developed by Pacific Northwest National Laboratory and serves as a guide for using this package to conduct cascading failure simulations for the electric power system. The DCAT is an open-platform and publicly available software; it is intended to help develop applications that aim to improve the capabilities of power system planning engineers to assess the impact and likelihood of extreme contingencies and potential cascading events across their systems and interconnections. Outputs from the DCAT will support finding mitigating actions to reduce the risk of cascading outages in technically sound and effective ways. This manual provides detailed instructions on how to use this tool on multicore Windows workstations or servers. In the public version of DCAT, several improvements have been made over the previous version: (1) it was modularized; (2) a graphical user interface (GUI) was developed; (3) a new version of the MPjobs parallel processing module was incorporated; and (4) a batch-processing function was added. The features of the DCAT GUI are described, including some examples of how to use the GUI to perform simulations. A full explanation of the DCAT methodology is available in the Phase 1 report.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Trial Implementation of a Multihazard Risk Assessment Framework for High-Impact Low-Frequency Power Grid Events

The Pacific Northwest National Laboratory developed a risk framework for modeling high-impact, low-frequency power grid events to support risk-informed decisions. In this research article, we briefly recap the framework and demonstrate its implementation for seismic and geomagnetic hazards using a benchmark reliability test system. We describe integration of a collection of models implemented to perform hazard analysis, fragility evaluation, consequence estimation and post-event restoration. We demonstrate the value of the framework as a multi-hazard power grid risk assessment and management tool. The research will benefit transmission planners and emergency planners by improving their ability to maintain a resilient grid infrastructure against impacts from major events.