Estimating ASHRAE Guideline 36 energy savings for multi-zone variable air volume systems using Spawn of EnergyPlus
Not Available
Engineering topics
Publications and source records attributed to Paliaga, Gwelen.
Not Available
Most existing buildings have sub-optimal heating, ventilation, and air conditioning (HVAC) controls, resulting in wasted energy and occupant discomfort. Retro-commissioning (RCx) addresses many of these issues, but it is a lengthy and highly customized process. Limited capabilities of existing building automation system hardware restricts the scope of most RCx projects. Incentive programs consider building automation system (BAS) hardware retrofits to be high-capital investments and do not allow them in typical RCx programs. This paper describes work that the authors are leading to facilitate technical and market innovation in the BAS industry to unlock large savings in existing commercial buildings through deep retrofits of BAS hardware and software. California and New York research projects are demonstrating BAS retrofits leveraging the American Society of Heating, Refrigeration, and Air Conditioning Engineers’ (ASHRAE) new Guideline 36 high performance sequences of operation to achieve greater than 20 percent whole building energy savings, while saving costs and reducing risk through streamlined processes and standardization across BAS manufacturer product lines and across implementation practices. This paper describes market barriers that impede achieving deep savings from BAS retrofits in custom incentive and traditional RCx programs and presents a new maximum potential BAS retrofit model that addresses these barriers. The new model leverages the authors’ efforts in market enablement through open standards, BAS industry partnerships, and tools for cost-effective scaling that includes tools for project screening, savings calculations, and measurement and verification (M&V). This approach is widely applicable and will be ready for at-scale implementation within two years.
Innovations in commercial building control sequences (ASHRAE guideline 36) and fault detection and diagnostics (FDD) technology have the potential to transform existing building operational efficiency by realizing whole-building level savings on the order of 15% and higher. However, several technical and market barriers related to up-front estimation of achievable savings, verifying implementation, and ensuring persistence are slowing down their adoption as a core offering through diverse owner-funded initiatives and rate-payer funded programs. This paper describes a suite of solutions to overcome these barriers to program delivery of advanced HVAC controls integrated with FDD energy management and information system (EMIS) technology. First, the Guideline 36 conformance test offers an automated method to confirm correct sequence implementation by the manufacturer, before field deployment. A successful test of a controller was conducted using a new manufacturer-independent hardware-in-the-loop testbed demonstrating the viability and scalability of this approach. Second, the Guideline 36 energy savings calculator uses modeling paired with high-level user inputs to estimate building-specific savings potential, target cost effective implementation and minimize uncertainty. Initial results indicate the baseline control sequences significantly impact energy savings, however, as much as 50% savings may be possible for the worst-case baseline scenario. Third, a functional specification provides minimum recommended EMIS-FDD capabilities, and best practices to integrate the technology into organizational practice and ensure that advanced control sequences provide persistent savings.