Peak Demand Management and Voltage Regulation Using Coordinated Virtual Power Plant Controls
Not Available
Engineering topics
Publications and source records attributed to Pratt, Annabelle.
Not Available
This paper performs a transient stability study of a real-world microgrid that can operate with 100% renewables to better understand the stability and reliability of the microgrid under various dynamic scenarios. In particular, the operation of multiple grid-forming (GFM) and grid-following (GFL) inverters in such a power system is not well understood under dynamic operation conditions, such as islanding and black start; therefore, in this paper, an electromagnetic transient model of the microgrid is developed to investigate the stability of the system under various dynamic operating conditions and to identify potential reliability risks. The PSCAD/EMTDC simulation with the high-fidelity model provides helpful insights into the optimal operation modes of GFM and GFL inverters as well as the stability and reliability of the microgrid. It can also inform field deployment in terms of inverter control parameters and coordination as well as the expected performance of black start and unplanned islanding.
This paper performs a transient stability study of a real-world microgrid with 100% renewables to fully understand the stability and reliability of the microgrid under various dynamic scenarios. In particular, the operation of multiple grid-forming (GFM) and grid-following (GFL) inverters in such a power system is not well understood under dynamic operation conditions, such as islanding and black start; therefore, in this paper, the full-scale electromagnetic transient modeling of the microgrid is developed to investigate the stability of the system under various dynamic operating conditions and to identify potential reliability risks. The PSCAD/EMTDC simulation with the high-fidelity model provides helpful insights into the optimal operation modes of GFM and GFL inverters as well as the stability and reliability of the microgrid, which gives good references for the field deployment in terms of inverter configuration and coordination as well as the capabilities of black start and unplanned islanding.
Every microgrid is unique in its diversity of assets, operation, and network structure. This uniqueness presents challenges for each microgrid implementation that need to be understood and addressed to prevent power quality concerns, stability issues, and blackouts. In this research work, we present one challenge faced during microgrid operation that could potentially cause a blackout in some microgrid configurations. Through the incorrect operation of the load tap changer controller during an islanding event for a microgrid with generation present on both primary and secondary busses, the primary voltage will increase or decrease beyond allowable bounds, causing a cascading failure. This work presents the issue first with simulation results to demonstrate the phenomenon and then presents results of load tap changer controller operation using a controller-hardware-in-the-loop experiment. Finally, details of the complete sequence of operation and the blackout scenarios are presented and summarized.
This paper performs a transient stability study of a real-world microgrid that can operate with 100% renewables to better understand the stability and reliability of the microgrid under various dynamic scenarios. In particular, the operation of multiple grid-forming (GFM) and grid-following (GFL) inverters in such a power system is not well understood under dynamic operation conditions, such as islanding and black start; therefore, in this paper, an electromagnetic transient model of the microgrid is developed to investigate the stability of the system under various dynamic operating conditions and to identify potential reliability risks. The PSCAD/EMTDC simulation with the high-fidelity model provides helpful insights into the optimal operation modes of GFM and GFL inverters as well as the stability and reliability of the microgrid. It can also inform field deployment in terms of inverter control parameters and coordination as well as the expected performance of black start and unplanned islanding.
Transform utility electric distribution management systems to enable the integration and management of all assets and functions across the utility enterprise regardless of vendor or technology. Four program areas: Platform: Develop an open-source platform; evaluate advanced applications. Test bed: Build a vendor-neutral test bed to evaluate existing and future advanced distribution management system (ADMS) functionalities in a realistic setting. Applications: Develop an initial suite of ADMS applications. Advanced control: Develop new integrated optimization and control solutions.
Today’s power engineer needs to be able to work in a multi-disciplinary environment and this presentation provides an overview of the challenges faced by today’s power engineers and sets forth skills most needed in this environment.
NREL's advanced distribution management system (ADMS) research helps utilities meet customer expectations of reliability, power quality, renewable energy use, data security, and resilience to natural disasters and other threats.
Residential customers use more than one-quarter of the electricity in the world. Optimally managing home energy consumption is an effective way of easing the operational challenges facing the electric grid with increasing solar photovoltaics (PV). This paper studies the impact of the future proliferation of home energy management systems (HEMS) in the presence of PV on large-scale distribution systems. First, we present a stochastic HEMS model that minimizes residential customers' thermal discomfort and energy costs under uncertainty. The HEMS model schedules the optimal operations of residential appliances in the presence of PV within a mixed-integer linear programming-based model predictive control framework that links the proposed HEMS to a quasi-steady-state time-series simulation tool. Additionally, extensive simulations are conducted for a stand-alone residential home using two tariff structures and for 1977 homes on an 8,500-node distribution feeder. Simulation results quantify the impact of the future proliferation of HEMS on the large-scale distribution system with PV.
Develop a controls architecture to manage a broad range of DERs across the grid for bulk system services through transactive, aggregation, and direct control methods.
This document provides system-level specifications for a federated architecture for secure and transactive distributed energy resource management solutions (FAST-DERMS), presents a solution, and describes operational concepts for the proposed solution. FAST-DERMS enables the provision of reliable, resilient, and secure transmission and distribution (T&D) grid services through the scalable aggregation and near-real-time management of utility-scale and small-scale distributed energy resources (DERs). We first present the principles and objectives of FAST-DERMS. Then, after discussing important system concepts, we present the specifications for FAST-DERMS and a solution that employs a distributed and federated control methodology in which the DERs connected to a single point of common coupling with the rest of the system, such as individual substations, are optimized coordinately to provide system-level grid services. FAST-DERMS aims to aggregate and coordinate the operations of DERs to support T&D grid operations. The key optimization and control component of this FAST-DERMS reference implementation is a flexible resource scheduler (FRS) that aggregates the DERs within a substation service area. These FRSs operate at the substation level and perform constrained economic dispatch of DERs, either directly or through a transactive market or aggregator, as shown in Figure ES-1. An FRS Coordinator at the distribution system operator (DSO) level aggregates distribution substations operated by FRSs and interfaces with the transmission system operator (TSO) to provide transmission services. FAST-DERMS also allows for the integration of the FRS Coordinator with an existing distribution utility management system that could be employed by the DSO to enhance distribution grid operations.
Not Available
This webinar will present results from a joint project with utility partner Xcel Energy in which we evaluated their ADMS application for volt-var optimization using different levels of model quality. We were able to help Xcel Energy understand the trade-offs of telemetry measurements and model quality when managing a feeder's voltage profile to maximize energy conservation. We simulated scenarios with varying levels of model quality and measurement density to evaluate Xcel's options for best using its ADMS. The results help Xcel and other utilities understand how network data affects voltage management as grid operations see continued growth in solar photovoltaic (PV) systems and electric vehicles (EVs).
This presentation provides an overview of peak load management for distributed energy resources.
This presentation provides an overview of the National Renewable Energy Laboratory's advanced distribution management system test bed overview.
The ability to perform peak load management in distribution systems has several benefits for utilities, including reduced demand charges and improved reliability, efficiency, and utilization of the network infrastructure. This paper demonstrates the coordinated operation of an advanced distribution management system (ADMS) and a distributed energy resource management system (DERMS) to achieve peak load management using a realistic laboratory test bed. A commercial ADMS reduces the peak demand by reducing system voltages using a dynamic voltage regulation (DVR) application. A prototype DERMS-based on real-time optimal power flow-controls distributed battery energy storage systems to further reduce the feeder power. Results from the experiments conducted using a model of a real distribution feeder show that the coordinated operation of the ADMS and DERMS is effective in accomplishing peak load management.
The SCC software calculates the step response characteristics based on the data collected from the plant. The tools available to characterize the step response needs a plant model. Our tool calculates the characteristics based on the data captured from the plant. This prevents the user from building a plant model and directly calculates the response.