Search NASA⌕ Search

Engineering topics

Qu, Ming

Publications and source records attributed to Qu, Ming.

50 records · Page 3

Development and case study of the liquid desiccant system module in sorption system simulation program (SorpSim)

Liquid desiccant systems (LDS) have recently seen an increase in research interest as they can utilize low-grade heat resources and separate the sensible and latent cooling loads by efficiently removing moisture in the air without cooling it to the dew point. Yet, simulation and analysis of LDS had remained complex and demanding due to the limited resources of LDS simulation tools. This work presents the new LDS module developed in the Sorption system Simulation program (SorpSim), which is an open-source and flexible platform for steady-state simulation and analysis of various sorption systems. First, the new LDS module containing a finite-difference model and an effectiveness-NTU model for the heat and mass transfer in LDS dehumidifier/regenerator component was introduced. Then the simulation results of the new module were verified using data from the literature. Lastly, a case study was carried out in SorpSim where an LDS cycle was built and simulated using the new module. The impacts of design and operating parameters on the simulated LDS performance were investigated. The parametric study revealed that a high source temperature improved moisture removal rate (MRR) but reduced the system coefficient of performance (COP); the COP increased monotonically with the desiccant solution recirculation ratio, while the MRR peaked at a ratio of 85%; and an internal solution heat exchanger with UA of 800 W/K was found to be sufficient for optimal performance under high recirculation ratios. The case study demonstrated the LDS module’s capability to facilitate the analysis of LDS design and operation. The LDS module can be further coupled with other component models in SorpSim to simulate and analyze various liquid-desiccant-based systems.

42 ENGINEERING↗

Membrane-based liquid desiccant air dehumidification: A comprehensive review on materials, components, systems and performances

Membrane-based liquid desiccant air dehumidification (MLDAD) is a separation process driven by the vapor pressure difference. In contrast to the conventional liquid desiccant air dehumidification, MLDAD uses semi-permeable membranes to separate the processing air and desiccant liquid so that only water vapor molecules in the air side can transfer through the membrane and be absorbed by the solution. Here, the vapor is removed from the air stream, and the carryover of solution droplets in the air is also able to be eliminated. This review addresses the characteristics of liquid desiccants and membranes, the design of MLDAD modules and systems, the performance assessment and comparison of the dehumidification and regeneration module, as well as the system-level energy analysis. State-of-the-art research results are presented, and the future needs for this promising technology are discussed.

42 ENGINEERING↗

A Novel Heat and Mass Transfer Model for Membrane-based Ionic Liquid Desiccant Air Dehumidifier

A numerical model is developed to predict and analyze the heat and mass transfer process of the membrane-based dehumidifier using liquid desiccant. Several mass transfer mechanisms of water vapor across the membrane are accounted for in this model to calculate the amount of permeated water vapor under various operating conditions based on the physical properties of the membrane and the liquid desiccant. This model is validated against experimental data available from the literature. The maximum discrepancy between the model-predicted results and the experimental data for air outlet temperature, solution outlet temperature, air outlet humidity ratio, and latent effectiveness are 3.38%, 2.7%, 4.3%, and 6.5%, respectively. It indicates that this model can be used to guide the design of the membrane-based dehumidifier to improve its performance.

Liu, Xiaobing↗

Energy-saving technologies for building heating, ventilation, and air conditioning systems

Buildings are responsible for about 38-quadrillion BTU of the total energy in the U.S. at present. The energy demands from buildings keep increasing remarkably to meet the improving life level and the needs of occupants' thermal comfort in the future. Therefore, the developments of high-performance building and efficient building energy systems are highly needed to address the challenges of the climate changes and energy depletion. In this paper, we provide a critical review of the studies on energy-saving technologies for building heating, ventilation, and air conditioning (HVAC) systems. We start with the heat recovery technologies applied to HVAC systems. We continue with the reviews on energy-efficient technologies in heating, cooling, and air dehumidification. After a brief background, we focus on the aspects of those systems: advanced materials, component and system design, and system performance. We highlight the recently emergent design, modeling, and experimental research on those technologies and provide the suggestions and outlook for future research and development of energy-efficient building HVAC systems.

Qu, Ming↗

Isothermal membrane-based air dehumidification: A comprehensive review

Isothermal membrane-based air dehumidification (IMAD), a recent emerged air dehumidification technology, separates the moisture from the humid air by using a selective membrane, through which only vapor molecules can transfer from the one side of the membrane at a high concentration to the other side at a low concentration. The IMAD process has superior performance potentially in energy and economic than other traditional dehumidification technologies. This paper comprehensively reviews the literature on IMAD including membrane characteristics, membrane configuration, membrane-related mass transport mechanism, and system design and operation, as well as the mass transfer modeling. State of the art in the IMAD is presented and finally the recommendations of future research are provided.

47 OTHER INSTRUMENTATION↗

Aqueous solution of [EMIM][OAc]: Property formulations for use in air conditioning equipment design

Liquid desiccant air conditioning (LDAC) is a promising alternative to vapor compression refrigeration based space cooling and dehumidification for the reduction of energy consumption and the improvement of indoor air quality. However, its use in the air conditioning market is still very limited due to its high installation cost, intensive carryover, and high cost of operation and maintenance associated to the corrosion of the current desiccant liquids. Substitutes for the traditional desiccant liquids with better properties and no corrosion are highly needed. Ionic liquids, which are salts comprised of organic cations and inorganic anions or organic anions, have high thermal stability, negligible or no vapor pressure, varied solubility in water, low or no corrosion to metals, and low driving temperatures to achieve dew point temperatures. All of those characteristics make them as perfect substitutes for traditional desiccant liquids. Up to date, a very few research groups investigated ILs as potential alternatives to traditional desiccant liquids for LDAC. The study aimed to identify the ionic liquids as ideal desiccant liquids to achieve better cost-effectiveness and higher system performance of LDAC. There were 13 different ionic liquids (IL) identified and screened for the most promising candidate. 1-Ethyl-3-methylimidazolium acetate, [EMIM][OAc], was selected as an ideal candidate for the capable of the most adsorption and desorption. The study was mainly focused on the development of calculation models for the thermo-physical properties of the aqueous solution of [EMIM][OAc] to represent the property data needed for use as the desiccant liquid in sorption-based air conditioning equipment. It aims to provide convenient methods for use in the design and model of the sorption-based air conditioning. Finally, the calculation models for the following thermo-physical properties of the aqueous solution of [EMIM][OAc] were proposed and presented in the study: the vapor pressures, specific heat capacity, density, and dynamic viscosity at various temperatures and concentrations.

1-Ethyl-3-methylimidazolium acetate↗

Modeling and Simulation of Membrane-Based Dehumidification and Energy Recovery Process

This paper introduces a first-order physics-based model that accounts for the fundamental heat and mass transfer between a humid-air vapor stream on feed side to another flow stream on permeate side. The model comprises a few optional submodels for membrane mass transport; and it adopts a segment-by-segment method for discretizing heat and mass transfer governing equations for flow streams on feed and permeate sides. The model is able to simulate both dehumidifiers and energy recovery ventilators in parallel-flow, cross-flow, and counter-flow configurations. The predicted tresults are compared reasonably well with the measurements. The open-source codes are written in C++. The model and open-source codes are expected to become a fundament tool for the analysis of membrane-based dehumidification in the future.

Gao, Zhiming↗

Development of Separate Sensible and Latent Cooling System Using Electrochemical Compressor

Separate sensible and latent cooling systems offer superior energy efficiency performance compared to conventional vapor compression air conditioning systems. In this paper we describe an innovative non-vapor compression system that uses electrochemical compressor (ECC) to pump hydrogen between 2-metal hydride reservoirs to provide the sensible cooling effect. The heat rejected during this process is used to regenerate the ionic liquid (IL) used for desiccant dehumidification. The overall system design is illustrated. The Xergy version 4C electrochemical compressor, while not designed as a high pressure system, develops in excess of 2 MPa (300 psia) and pressure ratios > 30. The projected base efficiency improvement of the electrochemical compressor is expected to be ~ 20% with higher efficiency when in low capacity mode due to being throttleable to lower capacity with improved efficiency. The IL was tailored to maximize the absorption/desorption rate of water vapor at moderate regeneration temperature. This IL, namely, [EMIm].OAc, is a hydrophilic IL with a working concentration range of 28.98% when operating between 25 75 C. The ECC metal hydride system is expected to show superior performance to typical vapor compression systems. As such, the combined efficiency gains from the use of ECC and separate and sensible cooling would offer significant potential savings to existing vapor compression cooling technology. A high efficiency Window Air Conditioner system is described based on this novel configuration. The system s schematic is provided. Models compared well with actual operating data obtained by running the prototype system. Finally, a model of an LiCl desiccant system in conjunction with the ECC-based metal hydride heat exchangers is provided.

Electrochemical Compression↗

Development of Updated ABsorption SIMulation Software (ABSIM)

ABsorption SIMulation, ABSIM, was developed for the simulation of absorption systems by The Oak Ridge National Laboratory during 1980s and 1990s. ABSIM provides a platform for users to investigate various cycle configurations and working fluids, to calculate their operating parameters, to predict their performance, and to compare them with each other on a uniform basis. ABSIM is indeed a very useful and accurate tool for researchers to investigate various absorption systems. However, it has not been well maintained: it is incompatible with recent operating systems; the interface needs improved user-friendliness, and the system needs better parameter setting and debugging tools to help achieve convergence. Therefore, it is highly needed to update and improve ABSIM. The paper presents recent efforts to improve ABSIM s compatibility with current operating systems, user interface, and analysis capabilities. The paper details the features and functions of the newly updated ABSIM software. The new ABSIM still uses the previously validated calculation engine of the old ABSIM. The new graphic user interfaces (GUI) were developed in Qt, which is an open source license GUI software based on C++. XML was used as the database for data storage in the new ABSIM. The new ABSIM has been designed to be easily learned and used. It has enhanced editing and construction functions, plus enhanced analysis features including parametric tables, plotting, property plots, and master panels for debugging. A single effect water/LiBr absorption system is used as a case study in this paper to illustrate the features, capabilities, and functions of the new ABSIM. This case study was actually an example system available in the old ABSIM. The new version of ABSIM will be continuously developed to include additional subroutines for the components in liquid desiccant systems. The new ABSIM will be available to public for free. The ultimate goal of the new ABSIM is to allow it to become a simulation platform for both absorption heat pump and liquid desiccant systems.

ABSIM↗

A solar thermal cooling and heating system for a building: Experimental and model based performance analysis and design

A solar thermal cooling and heating system at Carnegie Mellon University was studied through its design, installation, modeling, and evaluation to deal with the question of how solar energy might most effectively be used in supplying energy for the operation of a building. This solar cooling and heating system incorporates 52 m{sup 2} of linear parabolic trough solar collectors; a 16 kW double effect, water-lithium bromide (LiBr) absorption chiller, and a heat recovery heat exchanger with their circulation pumps and control valves. It generates chilled and heated water, dependent on the season, for space cooling and heating. This system is the smallest high temperature solar cooling system in the world. Till now, only this system of the kind has been successfully operated for more than one year. Performance of the system has been tested and the measured data were used to verify system performance models developed in the TRaNsient SYstem Simulation program (TRNSYS). On the basis of the installed solar system, base case performance models were programmed; and then they were modified and extended to investigate measures for improving system performance. The measures included changes in the area and orientation of the solar collectors, the inclusion of thermal storage in the system, changes in the pipe diameter and length, and various system operational control strategies. It was found that this solar thermal system could potentially supply 39% of cooling and 20% of heating energy for this building space in Pittsburgh, PA, if it included a properly sized storage tank and short, low diameter connecting pipes. Guidelines for the design and operation of an efficient and effective solar cooling and heating system for a given building space have been provided. (author)

14 SOLAR ENERGY↗