Search NASA⌕ Search

Engineering topics

Sadeque, Fahmid

Publications and source records attributed to Sadeque, Fahmid.

Per-Phase Control for CHB Converters with Negative-Sequence Current and DC Voltage Balancing Control

This paper presents a per-phase controller for a grid-connected Cascaded H-Bridge (CHB) converter featuring negative sequence current regulation and DC bus voltage balancing capabilities. Unlike conventional three-phase controllers, each phase of the CHB can be separately and controlled to regulate the DC voltage and reactive power flow. per-phase negative sequence current control strategy is incorporated into the proposed controller to ensure compliance with IEEE Standard 2800-2022, which requires the absorption of negative-sequence reactive current during grid voltage disturbances. Furthermore, a feed-forward control-based DC bus voltage balancing method is employed, which eliminates the need for the integrator commonly used in traditional approaches. The performance of the proposed controller is validated under various unbalanced grid scenarios and DC bus voltage imbalances through electromagnetic transient (EMT) simulation using a three-phase, three-level grid-connected CHB–Dual Active Bridge (DAB) converter testbed developed on MATLAB/Simulink. Additionally, the performance of the negative-sequence current regulation is investigated through simulation under different unbalanced grid voltage scenarios.

negative sequence current↗

A Universal Controller for Grid-Forming Inverters in Microgrid during Islanding for Low Transient Current

This paper presents a universal controller to reduce the transient current during islanding of microgrid. In the proposed universal controller, two sets of semi-parallel paths are formed, where one set produces voltage and phase-angle references for the grid-following (GFL) mode, and the other set produces the voltage and phase-angle references for the grid-forming (GFM) mode of operation for the inverters. Herein, the controller enables an inverter to universally operate in GFL and GFM mode, whereas, only one set of voltage and phase-angle reference is engaged for PWM signal generation. When the microgrid is disconnected from the grid, the universal controller switches the voltage and phase-angle references from GFL to GFM mode. The proposed controller ensures lower transient current by keeping the two sets of semi-parallel paths synchronized throughout the operation of the inverter and enabling seamless transition between the modes. The proposed controller is verified through hardware experiments under different scenarios in a laboratory scale microgrid for inverters transitioning from GFL to GFM mode after islanding.

Sadeque, Fahmid↗

Frequency Restoration of Grid-Forming Inverters in Pulse Load and Plug-in Events

This article presents a restoration technique using grid-forming inverters in an islanded microgrid during pulse load and plug-in events. In a microgrid powered by droop-controlled inverters, frequency is the variable that is accessible to all inverters for adjusting their power contributions. The problem is that the microgrid frequency deviates from its nominal value after a load change. The presented method enables the inverters to restore the frequency to the nominal value and regulate their bus voltage amplitudes. The frequency and voltage restorations are performed without communication while achieving the desired power-sharing between grid-forming inverters. The restoration is activated after detecting any active or reactive power changes. In this article, the dynamic model of an inverter equipped with enabled restoration paths is developed to verify the stability of the inverter controller under various conditions. The frequency and voltage restorations are examined during pulse load and plug-in events. Furthermore, this study is performed using a laboratory-scale islanded microgrid powered by two 208 V, 60 Hz, 5 kVA inverters.

24 POWER TRANSMISSION AND DISTRIBUTION↗

On Control Schemes for Grid-Forming Inverters

Grid-forming inverters can collaboratively regulate the voltage and frequency of a microgrid. These inverters are expected to be seen more in the future microgrid, undertaking the roles of the conventional power generators. Like conventional power generators, they must balance supply and demand, contribute to power-sharing between inverters and other power generators, and restore the voltage and frequency after any power changes. These technical challenges are typically achieved through different primary and secondary controllers. This article reviews some state-of-the-art primary and secondary control schemes for the emerging technology of grid-forming inverters. First, the typical control schemes for grid-following inverters are briefly presented for the continuity of the discussion on the roles of the grid-forming inverters in future power-grid, followed by two basic control schemes for the grid-forming inverters. Then, two decentralized power-sharing techniques, i.e., droop, and virtual inertia, are analyzed. The technical challenges for inverter synchronization and some control methods are discussed afterward. Finally, several secondary control methods for the voltage and frequency restoration in grid-forming inverters are reviewed.

Sadeque, Fahmid↗

Multiple Grid-Forming Inverters in Black-Start: The Challenges

Black-start is a major challenge toward the successful operation of an islanded inverter-based system. In this article, the technical challenges for the black-start of multiple grid-forming inverters are reported. Specifically, this article discusses inverter synchronization, voltage and frequency regulation, and power-sharing between the grid-forming inverters. Experiment results from a multi-inverter test-bed have been provided to support the discussion. Furthermore, a grid-forming inverter controller for black-start operation is developed and presented in this article that addresses the discussed technical challenges. The performance of the developed controller in black-start operation is verified through experiment results.

Sadeque, Fahmid↗

Power-Sharing between Grid-Forming and Grid-Following Inverters

Power-sharing between the grid-forming and the grid-following inverter in a small microgrid is a challenging task. Specifically, the decentralized droop-based power-sharing is difficult to achieve when the grid-forming inverter regulates the voltage and the frequency. This article proposes controllers for the grid-forming and the grid-following inverters, which ensure proportional power-sharing as well as regulate the voltage and the frequency. Both controllers use active power-frequency and reactive power-voltage droops. Additional secondary loops and secondary forward paths are added to the controller of the grid-forming inverter and the grid-following inverter, respectively, to ensure simultaneous voltage and frequency regulation and power-sharing. The efficacy of the proposed controllers for power-sharing is verified through experiment results in a multi-inverter testbed.

Sadeque, Fahmid↗

Cooperative Inverters to Overcome PLL Malfunctions

This paper presents a cooperative strategy between smart inverters to overcome instability and undesired trips of inverters caused by Phase-Locked Loop (PLL) malfunctions. For the grid-interactive inverter, PLL is typically required to measure the phase angle of the AC voltage at the Point of Common Coupling (PCC) of the inverter. Accurate phase-angle measurement is critical for grid-interactive inverters to stay synchronized with the power grid. If the inverters are interconnected through a communication link, they can support each other by sharing their grid information, such as phase-angles at their PCCs. The cooperative strategy utilizes the phase-angles and voltages at PCCs in a neighborhood to identify any possible PLL malfunctions or measurement inaccuracies and then enable the inverters to make corrective decisions. The efficacy of the cooperative strategy has been verified through simulation results in MATLAB/Simulink environment in this paper.

Sadeque, Fahmid↗

Self-Secure Inverters Against Malicious Setpoints

The next generation of grid-interactive inverters brings a communication feature that allows data sharing from utility supervisory controllers and smart devices that are connected to the same network. This feature enhances the control capabilities of grid-interactive inverters to provide services beyond active power injection. However, communication networks entail more vulnerable surfaces to malicious attacks that may result in modifying active and reactive power setpoints and causing weak-grid conditions or abnormal inverter operation. In this paper, steady-state and the dynamic behavior of the inverter for the incoming setpoints are analyzed to detect false data injection attacks and provide device-level security. The steady-state behavior of the inverter in the operating region is determined from the grid parameters such as the grid voltage and the grid impedance. These estimations are accomplished by the proposed self-security technique through a low-frequency signal injection-based approach combined with the recursive least square method. Moreover, a reduced fourth-order inverter model is used as the dynamic reference model, and grid parameters as well as the incoming setpoints are implemented to the reference model to verify whether the dynamic behavior of the inverter is inside the permissible region of operation. The validity and performance of the proposed method are verified experimentally through Allen-Bradley Powerflex 755 three-phase inverter and a 12 kW NHR 9410 regenerative power grid emulator. The results show that the self-secure smart-inverter is able to accept or reject the incoming commands and thus is protected from malicious cyber-physical attacks.

Hossen, Tareq↗

Direct Phase-Angle Detection for Three-Phase Inverters in Asymmetrical Power Grids

This paper introduces a signal reformation based direct phase-angle detection (DPD-SR) technique for three-phase inverters supporting asymmetrical grids. Asymmetries in three-phase systems may happen because of unbalanced three-phase loads, which can lead to the voltage asymmetry at the terminals of grid-tied inverters. The proposed DPD-SR technique can detect the voltage phase-angle under asymmetrical conditions. The DPD-SR technique also offers precise and rapid phase-angle detection via signal reformation and trigonometric functions. In essence, the phase-angle detection is directly derived from the trigonometric properties of the line-line voltages, while signal reformation is implemented to handle asymmetrical voltages. The proposed method measures two line-line voltages and detects the phase-angle of a three-phase system under both symmetrical and asymmetrical conditions. Unlike classical phase-locked loop (PLL) techniques, DPD-SR does not need any closed-loop PI controller, which significantly reduces the complexity and the delay in detecting the phase-angle. In this paper, the efficacy of the proposed technique is examined in comparison with the state-of-the-art PLLs under asymmetrical conditions via a set of laboratory experiments. Here, the performance of the phase-angle detection is also tested as part of an inverter feeding an asymmetrical grid.

24 POWER TRANSMISSION AND DISTRIBUTION↗