Search NASA⌕ Search

Engineering topics

Suryanarayanan, Siddharth

Publications and source records attributed to Suryanarayanan, Siddharth.

At least 19 records

Value-based Insights from the Implementation of Hierarchical Control for Energy Savings and Demand Response in Residential Premises

As the adoption of distributed energy resources and electric vehicles at residential customer premises increases exponentially, behind-the-meter assets can be utilized to achieve energy cost reduction and demand response through coordination and control strategies. A hierarchical control architecture from the utility headend to residential premises is implemented to attain these objectives. This paper extracts the values from the development, implementation, and deployment of that control hierarchy. The development of the control philosophy is built upon the existing advanced metering infrastructure, communication protocols, and industry-compatible application programming interfaces. Results are presented visually with analytical insights by utilizing the data from hardware-in-the-loop testing and simulation analysis out of the collected data from the field.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A Hierarchical Control Architecture: Utilization of Behind-the-Meter Appliances with Increased Visibility and Controllability

Optimal operations of distribution systems to enhance reliability and resiliency can be achieved if information with higher fidelity can be accessed from grid premise devices. This paper discusses a hierarchical control architecture that can introduce higher visibility and controllability by utilizing the estimated injection and absorption of different behind-the-meter controllable loads, and DERs, including EVs, within a premise. The acquired information is used to make control decisions for scheduling the premise appliances to reduce energy consumptions. The premise controller can also optimize the consumptions on a day-to-day basis in addition to taking input signals from the utility operators to support grid-service events (e.g., peak shaving). The entire control architecture is designed in a modular and scalable fashion that provides benefits to the utility from the reuse of existing infrastructure while creating opportunities for various grid services to be enabled by the operation of premise controllers.

24 POWER TRANSMISSION AND DISTRIBUTION↗

The LSBmax algorithm for boosting resilience of electric grids post (N‐2) contingencies

Abstract A computationally improved algorithm is presented to find the best transmission switching (TS) candidate for boosting resilience of electricity grids subject to ( N ‐2) contingencies. Here, resilience is computed as the reduction in load shed after the above‐mentioned ( N‐ ) contingencies. TS is a planned line outage, and past research shows that changing the transmission system's topology changes the power flow and removes post contingency violations. Finding the best TS candidate in a computationally suitable time for effectively boosting resilience is a challenge. The best TS candidate is found using a novel heuristic method by decreasing the search space based on proximity to the bus with the maximum load shedding (LSB). The LSB algorithm is faster than existing algorithms in the literature; and, it is compatible with both the AC and DC optimal power flow formulations. To validate the authors' claims of speedup and accuracy, two metrics are used to analyze the results from the IEEE 39‐bus and 118‐bus systems. Finally, the inherent parallelism of the LSB algorithm is leveraged on a high‐performance computing platform and applied to the large‐scale Polish 2383‐bus test system to validate scalability in both size and speedup in computation time.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A Computationally Improved Heuristic Algorithm for Transmission Switching Using Line Flow Thresholds for Load Shed Reduction

We present a computationally improved heuristic algorithm for transmission switching (TS) to recover load shed. Research from the past showed that changing power system topology may control power flows and remove line congestion. Hence, TS may reduce the required load shed. One of the main challenges is to find a potential TS candidate in a suitable time. Here, we propose a novel heuristic method that is capable of finding the potential TS candidate faster than existing algorithms in literature. The proposed method is compatible with both the AC and DC optimal power flows (OPF). Three metrics are used to compare the proposed algorithm with the state-of-the-art from literature to show the speedup and accuracy achieved. The proposed method is implemented on the IEEE 30-bus system, PEGASE 89-bus system, IEEE 118-bus system, and Polish 2383- bus system. The results on the large-scale Polish 2383-bus system shows that the proposed algorithm is scalable to large real-world systems. Parallel computing is implemented to further improve the computational performance of the proposed algorithm.

24 POWER TRANSMISSION AND DISTRIBUTION↗

An Integrated High-performance Computing and Digital Real-time Simulation Testbed to Benchmark Closed-loop Load Shedding Algorithms in Power Systems

An integrated testbed using digital real-time simulator (DRTS) and a high-performance computing (HPC) cluster is presented here to compare speed and performance of computational schemes to mitigate time-critical issues in electric power systems. The first approach in this testbed validation is taken by running a set of closed-loop load shedding algorithms to compare and contrast two paradigms of arresting cascading failure propagation. Two algorithms involve solving DC and AC power flow model-based optimization problems to compute load shedding at different buses, while a model-based stochastic search using parallel computing provides a viable alternative. The algorithms are implemented in the DRTS-HPC testbed for the IEEE 14-bus benchmark transmission system. As a proof of the concept, simulation results are presented for implementation of closed-loop load-shedding algorithms for cascading failures in the DRTS-HPC testbed

24 POWER TRANSMISSION AND DISTRIBUTION↗

Dirty dishes or dirty laundry? Comparing two methods for quantifying American consumers' preferences for load management in a smart home

One challenge of transitioning to renewable energy is that household electricity use and renewable generation are often misaligned. Smart home energy management systems hold promise for shifting usage to match generation, but these systems need to be designed with the occupants’ preferences in mind. The purpose of the present research is to compare two approaches for collecting and modeling consumers’ load management preferences, both of which are amenable to use in a home energy management system. Specifically, we examine the performance of Simple Multi-Attribute Rating Technique Exploiting Ranks (SMARTER) and Analytic Hierarchy Process (AHP) in quantifying consumers’ preferences regarding air temperature (air conditioning and heating), water heating, dishwashing, clothes washing and drying, monetary costs, environmental impacts, and comfort/convenience. Two studies are presented: Study 1 examines the SMARTER approach, and Study 2 focuses on the AHP approach. In both studies, online surveys (N SMARTER = 956 and N AHP = 1023) were conducted to elicit preferences from participants across the United States. The preferences modeled by both approaches were validated based on (a) their ability to predict participants’ choices in a Discrete Choice Experiment and (b) their convergence with previous research on load-shifting behavior. The validation procedure suggests that the SMARTER approach is superior in modeling consumers’ preferences for load management. Overall, this research lays the groundwork for designing a smart home interface capable of collecting occupants’ preferences and using those preferences to deliver improved occupant comfort, lower operating costs, reduced environmental impact, and more significant demand response than exists today.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

An Improved Transmission Switching Algorithm for Managing Post-(N-1) Contingencies in Electricity Networks

In this presentation, we detail the shortcomings of existing transmission switching (TS) methodologies for preventing post-contingency loss of load in wide area electric power networks. Following that, we present a bi-level algorithm as an improvement to the state of the art. We show proof-of-concept level results that indicate computational viability, fast solutions, and the ability to pick the same best candidate as non computationally viable methods. Further, our method also minimizes load shedding after the contingency, thus enhancing the reliability and security of electricity supply. We also include a futuristic scenario of increased renewables and decreased natural gas sourced generators to show promising results. We grant permission for our presentation to be recorded and uploaded by the conference organizers.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Impacts of Voltage-Based Grid Support Functions on Energy Production of PV Customers

This paper presents the impact of inverter grid- support functions (GSFs) on photovoltaic (PV) customer energy production on a real distribution feeder in Oahu, HI. These autonomous GSFs based on local voltage measurements are good alternatives to increase PV hosting capacity. However, these functions can result in PV energy curtailment to the customer, and this study addresses the concerns about the impact of inverter GSFs through detailed quasi-static time series (QSTS) simulations. It proposes four metrics: maximum and average GSF curtailment, average increased generation and average net generation change, to assess the impact of a given control on PV systems located on customer sites. It was found that curtailment of PV production is negligible for customers where peak voltage is within ANSI C84.1 range. A reliable relationship between curtailment and peak customer voltage is demonstrated, suggesting that peak voltage could be used as an indicator of customer curtailment.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Impacts of Voltage-Based Grid-Support Functions on Energy Production of PV Customers: Preprint

This paper presents the impact of grid-support utility-interactive inverter functions, such as volt/volt-ampere reactive and volt/watt controls, on quasi-steady-state feeder voltages and on photovoltaic (PV) customer energy production on a real distribution feeder in Oahu, Hawai'i. These autonomous inverter controls provide an effective means to modulate active and reactive power based on local voltage measurements and therefore serve as good candidates for non-wire alternatives to increase PV hosting capacity. However, because the activation of these functions can result in PV energy curtailment, this study addresses the concerns about the impact of these advanced inverter controls on curtailment through detailed quasi-static time series (QSTS) simulations. This study proposes four metrics-maximum and average grid-support function curtailments, average increased generation, and average net generation change-to assess the impact of a given control on PV systems located on customer sites. For representative scenarios modeled in detail, it was found that curtailment of PV production is negligible for customers where peak voltage is within ANSI C84.1 ranges. A reliable relationship between curtailment and peak customer voltage is demonstrated, allowing peak voltage to be used as an indicator of curtailment without the need to measure curtailment directly.

14 SOLAR ENERGY↗

Final Report: TIP-337 Home Battery System for Cybersecure Energy Efficiency and Demand Response

Many challenges related to energy use and grid participation face the residential building sector and utilities that serve our homes today. To reduce energy consumption, increase grid service participation, and improve homeowner benefits, a solution is needed that can adapt itself to each home and homeowner/occupant, that can deliver both building and grid services with reliability and high availability, that can automate these operations to minimize cost and complexity of deployment, and that can provide both home data privacy and grid cybersecurity. We hypothesize that customer-oriented home automation can mutually satisfy home occupant/owner needs, reduce energy consumption, and deliver reliable grid services. This project seeks to develop innovative technology solutions that prove this hypothesis. The Home Battery System (HBS) is a technology package comprised of connected 'smart' appliances, rooftop solar photovoltaics, a home battery, and a coordinating smart controller. This system is envisioned, developed and demonstrated by the National Renewable Energy Laboratory (NREL), Bosch, ESCRYPT and Colorado State University (CSU). It is the result of three years of research by our diverse team. NREL developed the home automation controller, and performed simulation and laboratory evaluations of the HBS. Bosch developed and delivered most of the connected appliances used in the project, and provided technical and commercialization guidance. ESCRYPT led cybersecurity analysis and developed the cybersecurity layer. CSU provided leadership on preference elicitation methodologies.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

A Global Real-Time Superlab: Enabling High Penetration of Power Electronics in the Electric Grid

The Global Real-Time Superlaboratory (Global RT Superlab) represents a vendor-neutral distributed platform based on the virtual interconnection of digital real-time simulators (DRTSs) and hardware-in-the-loop (HIL) setups hosted at eight geographically distributed laboratories in the United States and Europe (Figure 1). This article describes the efforts toward the realization of this largescale virtual infrastructure and explains a demonstration of the multilab setup for simulation and testing of next-generation global power grids.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Distribution Feeder Modeling for Time-Series Simulation of Voltage Management Strategies

This paper presents techniques to create baseline distribution models using a utility feeder from Hawai'ian Electric Company. It describes the software-to-software conversion, steady-state and time-series validations of a utility feeder model. It also presents a methodology to add secondary low-voltage circuit models to accurately capture the voltage at the customer meter level. This enables preparing models to perform studies that simulate how customer-sited resources integrate into legacy utility distribution system operations.

24 POWER TRANSMISSION AND DISTRIBUTION↗

An application of the Analytic Hierarchy Process for prioritizing user preferences in the design of a Home Energy Management System

Most demand response programs focus primarily on commercial and industrial loads. The sheer number of decision-influencing variables combined with a lack of a comprehensive understanding of human behavior make it difficult to develop response programs that encourage greater residential consumer participation. This paper presents a multi-criteria decision making approach using actual survey data for identifying user preferences. The novelty of the work is in considering functionality, cost, and carbon emissions for a given set of home appliances toward energy management. The paper explains the design methodologies used to prioritize the preferences from 1023 survey participants. Furthermore, the results are expected to inform the design of Home Energy Management Systems (HEMS) for participating in demand response programs.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Distribution Feeder Modeling for Time-Series Simulation of Voltage Management Strategies: Preprint

This paper presents techniques to create baseline distribution models using a utility feeder from Hawai'ian Electric Company. It describes the software-to-software conversion, steady-state, and time-series validations of a utility feeder model. It also presents a methodology to add secondary low-voltage circuit models to accurately capture the voltage at the customer meter level. This enables preparing models to perform studies that simulate how customer-sited resources integrate into legacy utility distribution system operations.

24 POWER TRANSMISSION AND DISTRIBUTION↗

A multi-criteria decision analysis-based approach for dispatch of electric microgrids

This paper presents a decision support system (DSS) for multi-objective dispatch of an electric microgrid con-sidering cost of operation, peak load reduction, and emissions. Discrete compromise programming (DCP) is used as the multi-criteria decision analysis (MCDA) technique for providing the decision support to the distribution system operator (DSO) by ranking various alternatives based on preference of the objec-tives. Simulations are performed on a notional electric microgrid based on the IEEE 13-node test feeder and the results are pre-sented with appropriate visualization.

24 POWER TRANSMISSION AND DISTRIBUTION↗