Search NASA⌕ Search

Engineering topics

Thimmapuram, Prakash R.

Publications and source records attributed to Thimmapuram, Prakash R..

Transmission Constraint Filtering in Large-Scale Security-Constrained Unit Commitment

When solving the security-constrained unit commitment problem, one of the most complicating factors is handling the large number of transmission constraints, corresponding to both base case and N - 1 line contingency scenarios. Although it is well known that only a few of these constraints need to be enforced, identifying this critical subset of constraints efficiently remains a challenge. In this letter, we propose a novel and simple iterative contingency-screening procedure that is able to eliminate 99.4% of the constraints selected by existing iterative methods, allowing for the solution of much larger-scale problems. We report computational results in realistic instances with up to 6468 buses and 9000 transmission lines. Furthermore, the method was also independently implemented and evaluated at MISO, where it performed faster than alternative methods.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Impact of battery degradation on energy arbitrage revenue of grid-level energy storage

This study investigates the representation of battery degradation in grid level energy storage applications. In particular, we focus on energy arbitrage, as this is a potential future large-scale application of energy storage and there is limited existing research combining the modelling of battery degradation and energy storage arbitrage. We implement two different representations of battery degradation within an energy arbitrage model, and show that degradation has a strong impact on battery energy storage system (BESS) profitability. In a case study using historical electricity market prices from the MISO electricity market in the United States, we find that the achievable net present value (at an interest rate of 10%) for a battery system with a C-rate of 1C dropped from 358 /kWh in the case considering no degradation to 194-314 /kWh depending on the battery degradation model and assumptions for end of life (EOL) criteria. This corresponds to a reduction in revenue due to degradation in the 12-46% range.Furthermore, we find that reducing the cycling of the bat-tery via introducing a penalty cost in the objective function of the energy arbitrage optimization model can improve the profitability over the life of the BESS.

25 ENERGY STORAGE↗