Search NASA⌕ Search

Engineering topics

Trudnowski, Daniel J.

Publications and source records attributed to Trudnowski, Daniel J..

At least 19 records

The Power and Energy Storage Systems Toolbox–PSTess (V1.0)

This document describes the Power and Energy Storage Systems Toolbox for MATLAB, abbreviated as PSTess. This computing package is a fork of the Power Systems Toolbox (PST). PST was originally developed at Rensselaer Polytechnic Institute (RPI) and later upgraded by Dr. Graham Rogers at Cherry Tree Scientific Software. While PSTess shares a common lineage with PST Version 3.0, it is a substantially different application. This document supplements the main PST manual by describing the features and models that are unique to PSTess. As the name implies, the main distinguishing characteristic of PSTess is its ability to model inverter-based energy storage systems (ESS). The model that enables this is called ess.m , and it serves the dual role of representing ESS operational constraints and the generator/converter interface. As in the WECC REGC_A model, the generator/converter interface is modeled as a controllable current source with the ability to modulate both real and reactive current. The model ess.m permits four-quadrant modulation, which allows it to represent a wide variety of inverter-based resources beyond energy storage when paired with an appropriate supplemental control model. Examples include utility-scale photovoltaic (PV) power plants, Type 4 wind plants, and static synchronous compensators (STATCOM). This capability is especially useful for modeling hybrid plants that combine energy storage with renewable resources or FACTS devices.

97 MATHEMATICS AND COMPUTING↗

Systems and methods for controlling electrical grid resources

The present invention relates to PMU-based control systems for dampening inter-area oscillations in large-scale interconnected power systems or grids to protect against a catastrophic blackout. The control systems receive phasor measurements from two or more locations on an AC transmission line and generates a power control command to a power resource on the grid.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Impacts of swinging door lossy compression of synchrophasor data

As the number of operational Phasor Measurement Units (PMUs) is increasing, compression is becoming crucial for efficiently transferring and storing enormous amount of synchrophasor data continuously measured from a power system. Some utilities in the U.S. have already adopted a nonlinear compression technique, called Swinging Door Algorithm (SDA), assuming compressed data meets technical and regulatory requirements without resulting in any degradation of the measurements. This paper studies impacts of this compression algorithm on field measured and simulated PMU data, and presents results from spectral analyses of raw and decompressed measurements. The results show blind application of the SDA compression alters frequency content in the measurements and introduces false harmonics and aliasing. These can lead to false conclusions being drawn from the measurements about the power system condition.

42 ENGINEERING↗

A Strategy for Forced Oscillation Suppression

Wide-area time-synchronized measurements have recently revealed troublesome forced oscillations (FOs) within modern synchronized power grids. In some cases, these FOs represent a dangerous hazard to the system. Recent research has focused on locating the source of FOs to provide operators with knowledge for mitigating their impact locally. This paper presents a complementary mitigation strategy, which is to purposely induce a second oscillation into the grid which cancels the impact of the FO. Such a strategy is complementary in that it may provide valuable time to operators attempting to locate the FOs source and to determine how to rectify it. This paper presents a suppression control strategy which modulates controllable devices to automatically cancel the impact of the FO without the need for locating the source of the original FO. The strategy is based upon tuned feedback control. In this study, the approach is demonstrated on a simulation system via modulation of inverter-based generation.

42 ENGINEERING↗

PDCI Damping Controller Summary of Project Achievements

This report presents a complete listing, as of May 2019, of the damping controller (DCON) project accomplishments including a project overview, project innovations, awards, patent application, journal papers, conference papers, project reports, and project presentations. The purpose of the DCON is to mitigate inter-area oscillations in the WI by active improvement of oscillatory mode damping using phasor measurement unit (PMU) feedback to modulate power flow in the PDCI. The DCON project is the result of a collaboration between Sandia National Laboratories (SNL), Montana Technological University (MTU), Bonneville Power Administration (BPA), and the Department of Energy Office of Electricity (DOE-OE).

42 ENGINEERING↗

PDCI Damping Controller Test Results and Project Summary

This report presents the results from testing of the Pacific DC Intertie (PDCI) wide-area damping controller (DCON) on the actual electric power grid in the western region of North America known as the Western Interconnection (WI). In addition, this report summarizes the key contributions and development strategy of the DCON. Therefore, this report also serves as the final report for the DCON project, which is known as TIP (Technology Innovation Project) no. 289. The purpose of the DCON is to mitigate inter-area oscillations in the WI by active improvement of oscillatory mode damping using phasor measurement unit (PMU) feedback to modulate power flow in the PDCI. This report describes the tests conducted, analysis of the results, and conclusions drawn as to the performance and safety of the DCON in the improvement of damping for inter-area oscillations in the WI. The DCON is the result of a collaboration between Sandia National Laboratories (SNL), Bonneville Power Administration (BPA), Montana Technological University (MTU), and the Department of Energy Office of Electricity (DOE-OE).

24 POWER TRANSMISSION AND DISTRIBUTION↗

Design of the Pacific DC Intertie Wide Area Damping Controller

This study describes the design and implementation of a proof-of-concept Pacific DC Intertie (PDCI) wide area damping controller and includes system test results on the North American Western Interconnection (WI). To damp inter-area oscillations, the controller modulates the power transfer of the PDCI, a ±500 kV DCtransmission line in the WI. The control system utilizes real-time phasor measurement unit feedback to construct a commanded power signal which is added to the scheduled power flow for the PDCI. After years of design, simulations, and development, this controller has been implemented in hardware and successfully tested in both open and closed-loop operation. The most important design specifications were safe, reliable performance, no degradation of any system modes in any circumstances, and improve damping to the controllable modes in the WI. The main finding is that the controller adds significant damping to the modes of the WI and does not adversely affect the system response in any of the test cases. The primary contribution of this paper, to the state of the art research, is the design methods and test results of the first North American real-time control system that uses wide area PMU feedback.

24 POWER TRANSMISSION AND DISTRIBUTION↗

PDCI Wide-Area Damping Control: PSLF Simulations of the 2017 Test Plan - Light Summer Case

To demonstrate and validate the performance of the wide-area damping control system, the project plans to conduct closed-loop tests on the PDCI in spring/summer 2017. A test plan details the open and closed loop tests to be conducted on the PDCI using the wide-area damping control system. To ensure the appropriate level of preparedness, simulations were performed in order to predict and evaluate any possible unsafe operations before hardware experiments are attempted. This report contains the results from these simulations using the power system dynamics software PSLF (Power System Load Flow, trademark of GE). The simulations use the WECC (Western Electricity Coordinating Council) 2016 light summer and heavy summer base cases and the 2014 dual export base case. Because of the large volume of plots, the results were divided into three reports corresponding to the three base cases. This report contains results from the 2016 light summer base case.

25 ENERGY STORAGE↗

PDCI Wide-Area Damping Control: PSLF Simulations of the 2017 Test Plan - Heavy Summer Case

To demonstrate and validate the performance of the wide-area damping control system, the project plans to conduct closed-loop tests on the PDCI in spring/summer 2017. A test plan details the open and closed loop tests to be conducted on the PDCI using the wide-area damping control system. To ensure the appropriate level of preparedness, simulations were performed in order to predict and evaluate any possible unsafe operations before hardware experiments are attempted. This report contains the results from these simulations using the power system dynamics software PSLF (Power System Load Flow, trademark of GE). The simulations use the WECC (Western Electricity Coordinating Council) 2016 light summer and heavy summer base cases and the 2014 dual export base case. Because of the large volume of plots, the results were divided into three reports corresponding to the three base cases. This report contains results from the 2016 heavy summer base case.

25 ENERGY STORAGE↗

PDCI Wide-Area Damping Control: PSLF Simulations of the 2017 Test Plan - Dual Export Case

To demonstrate and validate the performance of the wide-area damping control system, the project plans to conduct closed-loop tests on the PDCI in spring/summer 2017. A test plan details the open and closed loop tests to be conducted on the PDCI using the wide-area damping control system. To ensure the appropriate level of preparedness, simulations were performed in order to predict and evaluate any possible unsafe operations before hardware experiments are attempted. This report contains the results from these simulations using the power system dynamics software PSLF (Power System Load Flow, trademark of GE). The simulations use the WECC (Western Electricity Coordinating Council) 2016 light summer and heavy summer base cases and the 2014 dual export base case. Because of the large volume of plots, the results were divided into three reports corresponding to the three base cases. This report contains results from the 2014 dual export base case.

25 ENERGY STORAGE↗

PDCI Wide-Area Damping Control: PSLF Simulations of the 2016 Open and Closed Loop Test Plan

To demonstrate and validate the performance of the wide-are a damping control system, the project plans to conduct closed-loop tests on the PDCI in summer/fall 2016. A test plan details the open and closed loop tests to be conducted on the P DCI using the wide-area damping control system. To ensure the appropriate level of preparedness, simulations were performed in order to predict and evaluate any possible unsafe operations before hardware experiments are attempted. This report contains the result s from these simulations using the power system dynamics software PSLF (Power System Load Flow, trademark of GE). The simulations use the WECC (Western Electricity Coordinating Council) 2016 light summer and heavy summer base cases.

24 POWER TRANSMISSION AND DISTRIBUTION↗