Search NASA⌕ Search

Engineering topics

VanGilder, James W.

Publications and source records attributed to VanGilder, James W..

Optimization of Workload Distribution of Data Centers Based on a Self-Learning In Situ Adaptive Tabulation Model

Data center cooling typically involves non-uniform airflow and temperature distributions, which are affected by the IT workload distribution. It is helpful to simulate the airflow and temperature to optimize the workload distribution. Traditional computational fluid dynamics (CFD) simulation is usually time-consuming while conventional reduced order models (ROMs), though computationally fast, may generate inaccurate results even after being fully trained. In Situ Adaptive Tabulation (ISAT), contracting to conventional ROM, can make prediction with error lower than a user-specified tolerance. To demonstrate using of ISAT for optimal workload distribution in data center, this paper presents a preliminary study of an ISAT-based genetic algorithm optimization platform. The ISAT is trained offline by using the results from CFD simulations using a hypothetical simple data center. The optimal workload distribution determined by the platform leads to approximately 6.8% of energy savings when compared to the benchmark with a uniform workload distribution. We note that the time cost for the entire optimization process, including the training of ISAT is about 4 hours, which is acceptable in the design phase.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

An Accurate Fast Fluid Dynamics Model for Data Center Applications

Traditional CFD is broadly useful in the design and operation of reliable and efficient data centers. It is nevertheless computationally expensive, particularly when employed for design optimization, which usually requires multiple simulations. To speed-up calculations while retaining essential airflow physics, several researchers have turned to an alternative CFD methodology, namely, fast fluid dynamics (FFD). FFD has been reported to be much faster than traditional CFD, but at an assumed (acceptable) trade-off of reduced accuracy. However, a recent comparison of FFD and traditional CFD for data center plenum applications produced nearly indistinguishable results and suggested that previously-reported FFD/traditional-CFD differences were due primarily to inconsistent: 1) advection schemes, 2) computational grids, and 3) turbulence models. The present paper extends this FFD/traditional-CFD comparison to the data center whitespace and confirms the finding that a true like-for-like comparison produces nearly identical predictions. Our FFD implementation utilizes a first-order upwind finite-volume scheme for advection like traditional CFD, so alternative advection schemes (e.g., semi-Lagrangian) are not considered further here. Likewise, the effect of grid choice on traditional-CFD predictions is well known. However, the effect of turbulence model for data center applications has not been reported extensively so we do consider this topic further here. We compare the standard k-e and a simpler algebraic model to benchmark experimental data from a real data center. We find that the algebraic turbulence model predicts rack-inlet temperatures at a similar level-of-accuracy as the k-e model for our fairly-simple-airflow reference data center.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Equation-based object-oriented modeling and simulation of data center cooling systems

In this paper, we introduce a newly developed open source data center package in the Modelica Buildings library to support modeling and simulation of cooling and control systems of data centers. The data center package contains major thermal and control component models, such as Computer Room Air Handler, Computer Room Air Conditioner, models of different subsystem configurations such as chillers with differently configured waterside economizers, as well as templates for different systems. Two case studies based on this package are performed to investigate the performances of the cooling and electrical system under normal conditions and emergency situations such as a blackout: one is for a data center powered by conventional energy, and the other is for a data center powered by renewable energy. Simulation results show that the dynamic modeling and multi-domain simulation in the Modelica-based tool make it convenient for users to investigate both normal and emergent operations for conventional and renewable data centers.

29 ENERGY PLANNING, POLICY, AND ECONOMY↗

A New Fast Fluid Dynamics Model for Data-Center Floor Plenums

A raised-floor plenum is often used to distribute cooling airflow in data centers. Traditional Computational Fluid Dynamics (CFD) can accurately model airflow distribution in plenums, but it is expensive (computationally and financially) and is, therefore, often not accessible to the data center designer or operator. This paper presents an alternative CFD methodology based on Fast Fluid Dynamics (FFD), which is faster, more parallelizable, and simpler to program. The improvement in computational speed afforded by FFD is particularly important for multiple-iteration optimization, transient simulations, or applications for which near-real-time performance is required. Here, the potential speed improvements of FFD have been widely documented; however, it has been generally accepted that this benefit is accompanied by a modest loss of accuracy relative to traditional CFD. We show here that this is not necessarily true. Plenum airflow predictions by our FFD implementation, which utilizes a first-order upwind rather than Semi-Lagrangian advection scheme of previous research, are extremely close to those predicted by traditional CFD - provided the same turbulence model and computational grid are used consistently.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗