Search NASA⌕ Search

Engineering topics

Wang, Zufen

Publications and source records attributed to Wang, Zufen.

Loose Belt Fault Detection and Virtual Flow Meter Development Using Identified Data-driven Energy Model for Fan Systems

An energy model that correlates fan airflow, head, speed, and system power input is essential to detect device faults and optimize control strategies in fan systems. Since the application of variable-frequency drives (VFDs) makes the motor-efficiency data published by manufacturers inapplicable for VFD–motor–fan systems, the fan efficiency and drive (belt–motor–VFD) efficiency must be identified for each individual system to obtain accurate energy models. The objectives of this paper are to identify an energy model of existing VFD–motor–fan systems using available experimental data and demonstrate its applications in loose belt fault detection and virtual airflow meter development for optimal control. First, an approach is developed to identify the fan head, fan efficiency, and drive-efficiency curves using available fan head, speed, and system power input as well as temporarily measured airflow rate without measuring shaft power. Then, the energy model is identified for an existing VFD–motor–fan system. Finally, the identified model is applied to detect the slipped belt faults and develop the virtual airflow meter. The experiment results reveal that the developed approach can effectively obtain the energy model of VFD–motor–fan systems and the model can be applied to effectively detect slipped belt faults and accurately calculate the fan airflow rate.

42 ENGINEERING↗

Evaluation of supply air temperature control performance with different control strategies at air handling units

Due to its nonlinear feature, supply air temperature control systems at air handling units using single-loop fixed gain control frequently suffer unstable response under dynamic conditions. This paper is aimed at identifying a more effective control strategy to stabilize the valve control and achieve desirable supply air temperature response under various operation conditions by evaluating three control strategies, cascade, gain scheduling and cascade plus gain scheduling controls. Firstly, a control-oriented model is developed and calibrated through open-loop tests. Then, the control issues with single-loop fixed gain control are evaluated through simulations and field tests, which indicates that the system has more aggressive response or becomes unstable under lower load conditions when the chilled-water flow rate is less than 0.1 L/s. Finally, three control strategies are proposed and evaluated. Further, the results reveal that all three proposed controls can achieve better robustness with the integral square error of supply air temperature decreased to 16%, 47% and 5%, respectively, under lower load condition. However, since high-frequency oscillation of the control valve occurs with cascade and cascade plus gain scheduling control, the gain scheduling control is recommended considering a trade-off among the supply air temperature response, valve lifetime and implementation complexity.

42 ENGINEERING↗