Engineering topics
Winkler, J
Publications and source records attributed to Winkler, J.
Laboratory Test Report for Fujitsu 12RLS and Mitsubishi FE12NA Mini-Split Heat Pumps
Mini-split heat pumps are being proposed as a new retrofit option to replace resistance heating in the Pacific Northwest. NREL has previously developed a field test protocol for mini-split systems to ensure consistent results from field tests. This report focuses on the development of detailed system performance maps for mini-split heat pumps so that the potential benefits of mini-split systemscan be accurately analyzed for different climate regions and housing types. This report presents laboratory test results for two mini-split heat pumps. Steady-state heating and cooling performance for the Fujitsu 12RLS and Mitsubishi FE12NA was tested under a wide range of outdoor and indoor temperatures at various compressor and fan speeds. Cycling performance for each unit was also testedunder both modes of operation. Both systems performed quite well under low loads and the experimental test data aligned with manufacturer reported values. Adequate datasets were attained to promote performance modeling of these two systems in the future.
Field Monitoring Protocol: Mini-Split Heat Pumps
The report provides a detailed method for accurately measuring and monitoring performance of a residential Mini-Split Heat Pump. It will be used in high-performance retrofit applications, and as part of DOE's Building America residential research program.
Using EnergyPlus to Perform Dehumidification Analysis on Building America Homes: Preprint
A parametric study was conducted using EnergyPlus version 6.0 to investigate humidity issues on a typical mid-1990s reference home, a 2006 International Energy Conservation Code home, and a high-performance home in a hot-humid climate. The impacts of various dehumidification equipment and controls are analyzed on the high performance home. The study examined the combined effects of infiltrationand mechanical ventilation with balanced and unbalanced mechanical ventilation systems. Indoor relative humidity excursions were examined; specifically, the number of excursions, average excursion length, and maximum excursion length. Space relative humidity, thermal comfort, and whole-house source energy consumption were analyzed for indoor relative humidity set points of 50%, 55%, and 60%. Thestudy showed and explained why similar trends of high humidity were observed in all three homes regardless of energy efficiency, and why humidity problems are not necessarily unique in high-performance homes. Thermal comfort analysis indicated that occupants are unlikely to notice indoor humidity problems. The study confirmed that supplemental dehumidification should be provided to maintainspace relative humidity below 60% in a hot-humid climate.
Ducts in the Attic? What Were They Thinking? Preprint
As energy-efficiency efforts focus increasingly on existing homes, we scratch our heads about construction decisions made 30, 40, 50-years ago and ask: 'What were they thinking?' A logical follow-on question is: 'What will folks think in 2050 about the homes we're building today?' This question can lead to a lively discussion, but the current practice that we find most alarming is placing ductsin the attic. In this paper, we explore through literature and analysis the impact duct location has on cooling load, peak demand, and energy cost in hot climates. For a typical new home in these climates, we estimate that locating ducts in attics rather than inside conditioned space increases the cooling load 0.5 to 1 ton, increases cooling costs 15% and increases demand by 0.75 kW. Theaggregate demand to service duct loss in homes built in Houston, Las Vegas, and Phoenix during the period 2000 through 2009 is estimated to be 700 MW. We present options for building homes with ducts in conditioned space and demonstrate that these options compare favorably with other common approaches to achieving electricity peak demand and consumption savings in homes.
HVAC Loads in High-Performance Homes (Presentation)
This presentation was delivered at the ASHRAE 2010 Annual Summer Conference on June 27, 2010, and addresses humidity and AC loads in energy efficient houses.
Laboratory Test Report for ThermaStor Ultra-Aire XT150H Dehumidifier
This report documents the performance of the ThermaStor Ultra-Aire XT150H Dehumidifier. Its performance was measured across a wide range of inlet air conditions and fit to a numerical model.