Evaluation and optimization of flow boiling frictional pressure drop correlations using the data from traditional and next-generation refrigerants in a micro-fin tube

This study presents an experimental evaluation and optimization of flow boiling frictional pressure drop correlations for conventional and next-generation refrigerants in a horizontal micro-fin tube, with particular emphasis on the newly emerging refrigerant blends R-454C and R-455A, for which pressure-drop data in enhanced tubes remain limited. Experiments were conducted with R-410A, R-454C, R-455A, R-134a, R-1234yf, and R-1234ze(E) in a copper micro-fin tube with an inner diameter of 8.468 mm, over mass fluxes ranging from 100 to 300 kg/(m²·s) depending on the refrigerant, and evaporation temperatures of 7, 12, and 14 °C. Frictional pressure gradients were determined from measured total pressure drops after subtracting acceleration pressure drop, and the resulting database was used to assess four existing models: Kuo and Wang (1996), Cavallini et al. (1997), Goto et al. (2001), and Diani et al. (2014). The measured frictional pressure gradient increased with vapor quality and mass flux for all refrigerants and increased further at lower evaporation temperatures, with the overall trend strongly related to liquid viscosity. Among the four correlations, the Goto et al. (2001) model provided the best overall agreement with the measured data before optimization. To further improve prediction accuracy, the Kuo and Wang (1996) and Goto et al. (2001) models were optimized using the complete experimental database. After optimization, both models reduced the overall mean absolute deviation to below 15%, while the optimized Goto et al. (2001) model maintained the best and most consistent overall performance. The results provide new pressure-drop data for next-generation refrigerants and demonstrate that parameter optimization can significantly enhance the applicability of existing micro-fin-tube correlations.

Hu, Yifeng [ORNL] (ORCID:0000000242875185)↗

Experimental Evaluation of a Microchannel Condenser for R600a Domestic Refrigerators

Domestic refrigerators are among the most common household appliances, accounting for approximately 4% of total household energy consumption, which is higher than that of clothes dryers, lighting, or cooking appliances. With nearly 13 million new domestic refrigerators sold annually, even marginal improvements in their energy performance can yield significant reductions in overall energy demand and cost. This study focuses on enhancing the performance of domestic refrigerators using R600a as the refrigerant. Most domestic refrigerators currently employ wire-and-tube condensers, which are bulky and require a larger refrigerant charge. Given that R600a is classified as an A3 flammable refrigerant under ASHRAE standards, minimizing the system charge while maintaining or improving performance is critical. To address this, a compact and light weight single-pass serpentine microchannel heat exchanger (made of aluminum) was adopted as a condenser, replacing the conventional wire-and-tube configuration. The modified system was experimentally tested according to AHAM test standards, and charge optimization was performed. The results demonstrated that the refrigerator equipped with the microchannel condenser achieved a 5.3% reduction in energy consumption compared to the baseline configuration with wire-and-tube condenser.

Murugan, Muneeshwaran [ORNL] (ORCID:00000003340352↗

Visualization of Two-phase Flow Maldistribution in Brazed Plate Heat Exchangers

Brazed plate heat exchangers (BPHEs) are widely used in refrigeration and HVAC applications, but are susceptible to two-phase flow maldistribution especially when operated as evaporators. Existing visualization approaches are either limited to idealized conditions or suffer from poor optical transparency. This paper presents a novel visualization method in which one edge of a BPHE, parallel to the refrigerant inlet or outlet port, is removed by wire electrical discharge machining and replaced with a flat, transparent plate. The planar geometry allows the use of optically and infrared (IR)-transparent materials, enabling both high-speed videography and IR thermography of the two-phase flow at the channel entrances and exits. Preliminary tests with R134a and R1234ze(Z) at saturation temperatures between 5 °C and 15 °C demonstrate that distinct two-phase flow patterns in the inlet header can be clearly identified and differentiated under realistic operating conditions. Potentials of optical flow analysis of high-speed videos are shown to provide objective, quantitative indicators for flow regime characterization and comparison. IR imaging of the outlet port reveals non-uniform temperature distributions at the channel exits, providing independent evidence of maldistribution across the channel stack. Limitations of IR temperature accuracy due to the spectral properties of the sapphire window are discussed, and directions for improvement are identified.

Hausherr, Carsten [Technical University of Berlin ↗

Flow Boiling Pressure Drop Characteristics of Next-generation Refrigerants in a Micro‑fin Copper Tube

This paper presents experimental frictional pressure-drop data for flow boiling of R-410A, R-134a, and next-generation alternatives R-454C, R-455A, R-1234yf, and R-1234ze(E) in a horizontal micro-fin copper tube. Tests were conducted over a range of mass fluxes and evaporation temperatures to characterize refrigerant-dependent two-phase pressure-drop behavior. The results show that frictional pressure gradient increased with mass flux and vapor quality and generally increased as evaporation temperature decreased, with liquid viscosity strongly affecting the observed trends. Among the evaluated correlations, the Goto et al. (2001) model gave the best overall agreement with the measurements before optimization. Further optimization of the Kuo and Wang (1996) and Goto et al. (2001) models reduced the overall mean absolute deviation to below 15%, with the optimized Goto (2001) model providing the most consistent predictions across all six refrigerants. The results support improved pressure-drop prediction and evaporator design for next-generation refrigerants in micro-fin tubes.

Hu, Yifeng [ORNL] (ORCID:0000000242875185)↗

Thermal-Hydraulic Performance of a Zeotropic Refrigerant in a Brazed Plate Evaporator

In this work we report the results of a preliminary investigation focused on evaluating the thermal-hydraulic performance of R455A (CO2, R32, R1234yf – 3/21.5/75.5) in a commercial brazed plate heat exchanger. Three key parameters were measured which were refrigerant flow maldistribution, overall refrigerant side heat transfer coefficient, and total refrigerant side pressure drop. These same parameters were also measured for R134a which served as a base-line refrigerant for comparison. The experimental test matrix was set up to investigate the influence of refrigerant mass flux (3 ≤ Gref ≤ 5 kg m-2 s-1), refrigerant inlet vapor quality (0.1 ≤ xin ≤ 0.4), and refrigerant exit superheat (5 ≤ Tsh ≤ 10 K) on the above mentioned thermal-hydraulic parameters. For these experimental conditions, on average, the overall refrigerant side heat transfer coefficients for R455A were 45.2% lower than those of R134a. Refrigerant flow maldistribution for R455A, on average, was observed to be 62.6 % higher than that measured for R134a, and the total pressure drop across the heat exchanger (minor and frictional losses) for R455A was on average 26.5% higher than that measured for R134a. These initial results set the stage for a comprehensive investigation focused on further investigating the thermal-hydraulic performance of zeotropic refrigerants in brazed plate heat exchangers.

Jajja, Saad [ORNL]↗

Heat transfer and visual observation of pool boiling of next-generation low-pressure refrigerant: R1336mzz(Z)

R1336mzz(Z) is a non-flammable and non-toxic hydrofluoroolefin (HFO), which is a potential alternative working fluid for multiple applications such as centrifugal chillers, industrial high temperature heat pumps, and Organic Rankine Cycles. Pool boiling is one of the primary heat transfer modes in shell-and-tube evaporators, and there is limited data for R1336mzz(Z) due to its recent introduction. This study investigated the pool boiling characteristics of R1336mzz(Z) using a closed-loop apparatus. Heat transfer coefficients on a smooth aluminum surface were measured at various heat fluxes with a heating block, and the results were compared to predictions from various correlations. Additionally, a high-speed camera was employed to visualize and analyze the pool boiling behavior of this next-generation low-pressure refrigerant.

Yang, Cheng-Min [ORNL]↗

Optimizing flow condensation models for next-generation refrigerants in axial micro-fin aluminum tubes

To support the transition to next-generation refrigerants, accurate modelling of heat transfer and pressure drop is essential for designing efficient heat exchangers. Current models, largely based on traditional refrigerants and unexpanded micro-fin tubes, may not reliably predict performance for new refrigerants and expanded micro-fin geometries. This study evaluates four condensation models using experimental data for six A2L refrigerants: R-32, R-454B, R-454C, R-455A, R-1234yf, and R-1234ze(E). For heat transfer models, the Han and Lee (2005) model initially yields the best accuracy (mean absolute Deviation, MAD = 22.1%). To further improve predictions, a correction factor reduces the Cavallini et al. (2009) model’s MAD from 68.2% to 15.4%, while optimization of the Kedzierski and Goncalves (1997) model achieves a MAD of 13.1%. For pressure drop, the Cavallini et al. (1997) model proves most accurate (MAD = 6.4%), with the simpler Haraguchi et al. (1993) model also effective (MAD = 9.4%). Keywords: Flow condensation models, heat transfer coefficient, frictional pressure drop, next-generation refrigerants, aluminum micro-fin tubes

Hu, Yifeng [ORNL] (ORCID:0000000242875185)↗