Utility Perspective on Protection Challenges with High IBR Penetration [Slides]

Utilities have seen rapid increase in Solar, Wind, and Battery Energy Storage Resources that interconnect to their electric system through Inverters. Inverter-Based Resources (IBRs) have fault current characteristics that are unlike the fault current response of traditional rotating-machine-based generators, which is well known and repeatable. IBR’s non-traditional fault current behavior is due to the IBR control scheme, which is configured to provide a clean AC output but also protect the inverter’s sensitive power electronics devices from damage, one source of which is overcurrent. This results in low fault current magnitude, low or no negative sequence current injection, the variability of sequence component currents, the variability of voltage with respect to current angles, and the lack of inertia. The control scheme also results in a fault current response that can vary between manufactures and between models of the same manufacturer. High penetration of IBRs can adversely affect the protection schemes applied in areas with high penetration of IBRs. With the proliferation of IBRs, utilities are finding out that conventional protection schemes are not adequately equipped to protect the electric systems. This is mainly because the existing protection elements and practices have been designed based on the fault current response of conventional rotating machines. In several cases, the available literature does not provide any clear solution for the issues when the protection scheme does not operate properly near IBRs. This report identifies various protection challenges due to IBRs that industry is facing, from the utility perspective. Instead of facing on one issue, this report looks broadly on all the challenges that system protection has experienced with high penetration of IBRs. Based on the IBR response from various utilities during real fault events and gathering perspective from different utility SMEs via questionnaire, the report summarizes on gathered data and internal experiences.

14 SOLAR ENERGY

Utility Perspective on Protection Challenges with High Penetration of IBRs

Utilities have seen rapid increase in Solar, Wind, and Battery Energy Storage Resources that interconnect to their electric system through Inverters. Inverter-Based Resources (IBRs) have fault current characteristics that are unlike the fault current response of traditional rotating-machine-based generators, which is well known and repeatable. IBR’s non-traditional fault current behavior is due to the IBR control scheme, which is configured to provide a clean AC output but also protect the inverter’s sensitive power electronics devices from damage, one source of which is overcurrent. This results in low fault current magnitude, low or no negative sequence current injection, the variability of sequence component currents, the variability of voltage with respect to current angles, and the lack of inertia. The control scheme also results in a fault current response that can vary between manufactures and between models of the same manufacturer. High penetration of IBRs can adversely affect the protection schemes applied in areas with high penetration of IBRs. With the proliferation of IBRs, utilities are finding out that conventional protection schemes are not adequately equipped to protect the electric systems. This is mainly because the existing protection elements and practices have been designed based on the fault current response of conventional rotating machines. In several cases, the available literature does not provide any clear solution for the issues when the protection scheme does not operate properly near IBRs. This report / presentation identifies various protection challenges due to IBRs that industry is facing, from the utility perspective. Instead of facing on one issue, this report looks broadly on all the challenges that system protection has experienced with high penetration of IBRs. Based on the IBR response from various utilities during real fault events and gathering perspective from different utility SMEs via questionnaire, the report summarizes on gathered data and internal experiences.

14 SOLAR ENERGY

Model of Inverter-Based Resources

Blackbox modelling for SC analysis is a possible solution. Accuracy can be acceptable even without having vendor control diagrams. Is an NDA required to share a vendor Blackbox model for SC analysis? Differences in VRT detection and injection logics. Angle rotation is not addressed in control logics of most vendors. Current limitation logic during unbalanced faults is not clear. Model IBR as a current source with shunt to improve convergence

IBRs, Model of IBRs, Short Circuit Analysis, Class

IBR Black Model Lessons Learned (C45)

Blackbox modelling for SC analysis is a possible solution. Accuracy can be acceptable even without having vendor control diagrams. Blackbox modelling is not as user friendly as a generic model. Is an NDA required to share a vendor Blackbox model for SC analysis? Difference in VRT detection and injection logics. Angle rotation is not addressed. Current limitation logic during unbalanced faults is not clear.

24 POWER TRANSMISSION AND DISTRIBUTION

A review on protection challenges of Transmission Lines connected to Inverter Based Resources

The increased penetration of inverter-based resources (IBRs) connected to transmission grids is challenging how traditional electric power systems operate. Such systems were originally designed based on the dominant presence of synchronous generators. Some main challenges include the increased concerns about system stability due to the reduced system inertia caused by IBRs and the reduced protection reliability caused by the non-deterministic fault current response of IBRs. The protection relays’ algorithms have been designed and validated based on well-known fault current characteristics of synchronous generations, while the short-circuit responses of IBRs heavily depend on their vendor-specific control schemes, which are mainly set to protect inverter semiconductor switches and DC components. The magnitude of short current that IBRs contribute is typically between 1.1–1.5 times the rated current that may behave unstably and incoherently with the voltages. The control scheme of the IBRs also controls the active (P) and reactive (Q) support during system voltage sag and swell conditions. These characteristics challenge not only protective relay schemes but also existing short-circuit software tools to correctly model IBRs for fault studies and protection coordination analyses.

14 SOLAR ENERGY

IBR Bulk System Protection Issues and Modeling Challenges

Issue to be Address: Difficulty in predicting Inverter (IBR) generation dynamic response characteristics. Main challenges are unavailability of proprietary control details for modeling and the aggregate mixed IBRs with different dynamic response characteristics all contributing during system faults. Framework for Discussion: Identifying issues by sharing experience Reviewing options to improve IBR modeling accuracy, computation speed, use of test results. Presenting related research by EPRI and PG&E (DOE project) Desired Outcomes: Provide technical update for participants Get feedback and suggestions for ongoing research Improve research collaboration

IBR, Protection Challenges, dynamic response, IBR

A Review on Protection Challenges of Transmission Lines Connected to Inverter-Based Resources

The increased penetration of inverter-based resources (IBRs) connected to transmission grids is challenging how traditional electric power systems operate. Such systems were originally designed based on the dominant presence of synchronous generators. Some main challenges include the increased concerns about system stability due to the reduced system inertia caused by IBRs and the reduced protection reliability caused by the non-deterministic fault current response of IBRs. The protection relays’ algorithms have been designed and validated based on well-known fault current characteristics of synchronous generations, while the short-circuit responses of IBRs heavily depend on their vendor-specific control schemes, which are mainly set to protect inverter semiconductor switches and DC components. The magnitude of short current that IBRs contribute is typically between 1.1–1.5 times the rated current that may behave unstably and incoherently with the voltages. The control scheme of the IBRs also controls the active (P) and reactive (Q) support during system voltage sag and swell conditions. These characteristics challenge not only protective relay schemes but also existing short-circuit software tools to correctly model IBRs for fault studies and protection coordination analyses

14 SOLAR ENERGY