Electrical power requirements analysis. Single failure tolerant entry
Abstract
The results of an analysis of the orbiter electrical power system for the case of a single failure tolerant (SFT) entry are presented. The analysis was performed using the shuttle electrical power system analysis computer program. It was performed to permit assessment of the capability of the orbiter systems to support the proposed entry configuration and to provide the data necessary to identify potential constraints and limitations. Three contingency modes have been identified which would require an SFT entry. This analysis addresses an SFT entry resulting from the loss of two fuel cell powerplants, while on orbit. The results of the analysis indicate that, even under near optimum conditions, the fuel cell power demand will exceed the tested operating capacity of 16 kw, and that various electrical components may experience voltages below 24 VDC.