NASA NTRS · 19850000018
High-Voltage Isolation Transformer
Abstract
Arcing and field-included surface erosion reduced by electrostatic shields around windings and ferromagnetic core of 80-kilovolt isolation transformer. Fabricated from high-resistivity polyurethane-based material brushed on critical surfaces, shields maintained at approximately half potential difference of windings.
Keep this discovery
Explore connections, maps & timelines
Clatterbuck, C. H., Ruitberg, A. P.. 1985-06-01. High-Voltage Isolation Transformer. https://ntrs.nasa.gov/citations/19850000018
Cite the original work for its findings. Save a collection to share your selection of sources.