NASA NTRS ยท 20110011412
Crew Quarters (CQ) and Electromagnetic Interference (EMI) Measurement Facility Combined Impedance Study
Abstract
This report documents an investigation into observed failures associated with conducted susceptibility testing of Crew Quarters (CQ) hardware in the Johnson Space Center (JSC) Electromagnetic Interference (EMI) Measurement Facility, and the work accomplished to identify the source of the observed behavior. Investigation led to the conclusion that the hardware power input impedance was interacting with the facility power impedance leading to instability at the observed frequencies of susceptibility. Testing performed in other facilities did not show this same behavior, pointing back to the EMI Measurement Facility power as the potential root cause. A LISN emulating the Station power bus impedance was inserted into the power circuit, and the susceptibility was eliminated from the measurements.
Keep this discovery
Explore connections, maps & timelines
Scully, Robert C.. 2011-01-01. Crew Quarters (CQ) and Electromagnetic Interference (EMI) Measurement Facility Combined Impedance Study. https://ntrs.nasa.gov/citations/20110011412
Cite the original work for its findings. Save a collection to share your selection of sources.