Abstract
We consider the problem of placing sensors in a municipal water network when we can choose both the location of sensors and the sensitivity and specificity of the contamination warning system. Sensor stations in a municipal water distribution network continuously send sensor output information to a centralized computing facility, and event detection systems at the control center determine when to signal an anomaly worthy of response. Although most sensor placement research has assumed perfect anomaly detection, signal analysis software has parameters that control the tradeoff between false alarms and false negatives. We describe a nonlinear sensor placement formulation, which we heuristically optimize with a linear approximation that can be solved as a mixed-integer linear program. We report the results of initial experiments on a real network and discuss tradeoffs between early detection of contamination incidents, and control of false alarms.
Explore related subjects
Keep this discovery
Explore connections, maps & timelines
Hart, William Eugene, McKenna, Sean Andrew, Phillips, Cynthia Ann, Murray, Regan Elizabeth, Hart, David Blaine. 2010-05-01. Integrating event detection system operation characteristics into sensor placement optimization.. https://www.osti.gov/biblio/1014639