DOE OSTI · 1260459
Enhanced Component Performance Study: Motor-Driven Pumps 1998–2014
Abstract
This report presents an enhanced performance evaluation of motor-driven pumps at U.S. commercial nuclear power plants. The data used in this study are based on the operating experience failure reports from fiscal year 1998 through 2014 for the component reliability as reported in the Institute of Nuclear Power Operations (INPO) Consolidated Events Database (ICES). The motor-driven pump failure modes considered for standby systems are failure to start, failure to run less than or equal to one hour, and failure to run more than one hour; for normally running systems, the failure modes considered are failure to start and failure to run. An eight hour unreliability estimate is also calculated and trended. The component reliability estimates and the reliability data are trended for the most recent 10-year period while yearly estimates for reliability are provided for the entire active period. Statistically significant increasing trends were identified in pump run hours per reactor year. Statistically significant decreasing trends were identified for standby systems industry-wide frequency of start demands, and run hours per reactor year for runs of less than or equal to one hour.
Explore related subjects
Keep this discovery
Explore connections, maps & timelines
Schroeder, John Alton. 2016-02-01. Enhanced Component Performance Study: Motor-Driven Pumps 1998–2014. https://doi.org/10.2172/1260459
Cite the original work for its findings. Save a collection to share your selection of sources.