A Comparative Study of Distribution System Parameter Estimation Methods

Abstract

In this paper, we compare two parameter estimation methods for distribution systems: residual sensitivity analysis and state-vector augmentation with a Kalman filter. These two methods were originally proposed for transmission systems, and are still the most commonly used methods for parameter estimation. Distribution systems have much lower measurement redundancy than transmission systems. Therefore, estimating parameters is much more difficult. To increase the robustness of parameter estimation, the two methods are applied with combined measurement snapshots (measurement sets taken at different points in time), so that the redundancy for computing the parameter values is increased. The advantages and disadvantages of both methods are discussed. The results of this paper show that state-vector augmentation is a better approach for parameter estimation in distribution systems. Simulation studies are done on a modified version of IEEE 13-Node Test Feeder with varying levels of measurement noise and non-zero error in the other system model parameters.

Explore related subjects

Keep this discovery

Explore connections, maps & timelines

BibTeXRIS

Sun, Yannan, Williams, Tess L., Gourisetti, Sri Nikhil Gup. 2016-07-17. A Comparative Study of Distribution System Parameter Estimation Methods. https://doi.org/10.1109/pesgm.2016.7741096

Cite the original work for its findings. Save a collection to share your selection of sources.

KEEP EXPLORING

Related reports

Data-Driven Global Sensitivity Analysis of Three-Phase Distribution System with PVs

Global sensitivity analysis (GSA) of distribution system with respect to stochastic PV variations plays an important role in designing optimal voltage control schemes. This paper proposes a Kriging, i.e., Gaussian process modeling enabled data-driven GSA method. The key idea is to develop a surrogate model that captures the hidden global relationship between voltage and real and reactive power injections from the historical data. With the surrogate model, the Sobol index can be conveniently calculated to assess the global sensitivity of voltage to various power injection variations. Comparison results with other model-based GSA methods on the IEEE 37-bus feeder, such as the polynomial chaos expansion and the Monte Carlo approaches demonstrate that the proposed method can achieve accurate GSA outcomes while maintaining high computational efficiency.

distribution system analysis↗