DOE OSTI · 1558347
Diesel Generator Controller Evaluation via Controller-Hardware-in-the-Loop for Various Microgrid Operation Modes
Abstract
This paper presents the Controller-Hardware-in-the-Loop (CHIL) evaluation of a diesel generator controller for various microgrid operation modes. The model of the diesel generator (governor, exciter, and primary control) is simulated in real time, and the secondary control is implemented in a real hardware controller, Woodward easYgen, which is tested via CHIL with different microgrid configurations under microgrid transition operations. The experimental results demonstrate that the control settings and configuration of the Woodward controller work correctly for different microgrids under microgrid transition operations, which provides confidence for site commissioning.
Explore related subjects
Keep this discovery
Explore connections, maps & timelines
Wang, Jing, Miller, Brian R, Pratt, Annabelle, Fossum, John R, Bialek, Tom, Manson, Scott, Symko-Davies, Martha. 2019-08-08. Diesel Generator Controller Evaluation via Controller-Hardware-in-the-Loop for Various Microgrid Operation Modes. https://doi.org/10.1109/isgt.2019.8791660. https://searchnasa.com/record/osti%3A1558347/diesel-generator-controller-evaluation-via-controller-hardware-in-the-loop-for-various-microgrid-ope