Abstract
This document provides guidelines, whereby the physical parameters associated with postulated flammable/combustible liquid pool fires are determined (thermal analysis) in order to estimate the number of waste containers impacted. Pool fire damage to waste containers may occur due to a container being fully engulfed (within the periphery of the pool), partially engulfed, or within the critical heat flux distance. The methodology described here for estimating the size of the pool fire is developed using spill characteristics outlined in Chapter 65 of the SFPE Handbook (Ref. 7) and testing done by Hansen (Ref. 25). For exposures, the critical flux height is determined using the detailed method of Shokri and Beyler (Ref. 8) from the flame height, calculated as described by Heskestad (Ref. 7) and the average black body emissive power, determined using the method of Shokri and Beyler (Ref. 8). Three types of liquid pool fires should be considered; unconfined crash/instantaneous spill fires, unconfined continuously flowing (also called metered leak) spill fires, and confined spill fires. All fuel sources should be considered consistent with the facility Fire Hazard Analysis (FHA). However, the most likely liquid fuel sources present in TRU waste facilities are those present on TRU waste handling vehicles (forklifts, pallet movers, transport trucks, etc.). This method can also be used for assessing damage to items other than waste containers or other methods of analysis may be used with appropriate justification.
Explore related subjects
Keep this discovery
Explore connections, maps & timelines
Sprankle, Ray A., Schluszas, Victoria M.. 2020-06-16. Pool Fire Analysis Methodology for Assessing Damage to Waste Containers. https://doi.org/10.2172/1637912
Cite the original work for its findings. Save a collection to share your selection of sources.