Abstract
As renewable resources displace traditional generation, there may be times when there is relatively less rotational inertia (H, MW-s) to stabilize power system frequency following a power system disturbance. This article outlines a method for the control of Battery Energy Storage System (BESS) to mitigate power system frequency disturbances. The control scheme discussed in the article leverages latest ‘smart grid’ technologies including PMU’s and advanced grid-supportive inverters. The authors’ screening-level analysis of this novel BESS control concept indicates the potential to increase the speed of recovery of disturbed power systems, i.e. return power system frequency to nominal value (60 Hz in N. America), following a system disturbance. Increasing power system stability by adding inertial-support from appropriately controlled BESS will help power systems accommodate more renewable generation before hitting stability limits.
Explore related subjects
Keep this discovery
Explore connections, maps & timelines
Vartanian, Charles K., Alam, Md Jan E., Hsieh, Eric. 2020-01-20. Active Damping With Energy Storage to Improve Power System Frequency Stability. https://www.osti.gov/biblio/1700529
Cite the original work for its findings. Save a collection to share your selection of sources.