DOE OSTI · 1718978
Substation Cable Layouts for EMP Coupling Analysis
Abstract
Direct coupling of early-time high-altitude electromagnetic pulse (HEMP) to substation control cables is simulated for cable layouts based on surveys of seven electrical substations in the United States. An analytic transmission line modeling code is used to estimate worst-case coupled current at the terminations of cable segments in or near the control shack. Where applicable, an induced voltage due to cable shield grounding is also estimated. Various configurations are simulated, including cables with different elevations, lengths, radii, and terminations. Plots of the coupled HEMP effects are given, and general relationships between these effects and the substations geometric and material parameters are highlighted and discussed.
Explore related subjects
Keep this discovery
Explore connections, maps & timelines
Pfeiffer, Robert Anthony, Llanes, Rodrigo Elias, Warne, Larry K., Halligan, Matthew. 2020-10-01. Substation Cable Layouts for EMP Coupling Analysis. https://doi.org/10.2172/1718978
Cite the original work for its findings. Save a collection to share your selection of sources.