Search NASA⌕ Search

DOE OSTI · 1765364

Modeling the Functional Forms of Grid Disturbances

Abstract

This report introduces a functional form that may be used to quantitatively predict the impacts of new grid tools and changing system qualities on the likelihoods, durations, and depths of various grid disturbances. Each disturbance scenario is modeled to have three component stages—avoidance, reactance and recovery, which together parametrically estimate one disturbance’s impacts. The modeled scenario is then placed and replicated within an analysis period to represent the likelihood or frequency of the scenario and its consequent impacts. Whereas analysts have struggled to define and apply metrics for grid resilience, the functional form introduced by this report shares units of measurement with accepted grid-status measures (e.g., numbers of customers currently experiencing a service outage). Furthermore, the integrated and averaged functional form over an analysis period provides a meaningful normalized performance metric (e.g., customer outage minutes per year) that is ultimately independent of the duration of the period of. The approach may be applied similarly regardless of the severity or frequency of the disturbances that are being analyzed. Because metrics can be chosen to be identical in both the hypothetical future and the actual historical past, the historical past eventually becomes the test of the future predictions, at least in a statistical sense. The authors originally developed this approach to facilitate analysis of the effects of transactive energy (TE) systems effects on electric power grid resilience. TE systems invite energy suppliers and consumers to actively collaborate toward the discovery of, and their responses to, the locational value of energy. The findings from this process are often embodied as energy prices, the dynamics of which indicate the locational value of energy and can further represent important grid service needs. While some academic papers claim to quantify the value of a specific TE system design toward grid resilience, the answer, in general, has been elusive. Not only do multiple and conflicting definitions of resilience and reliability exist, but countless TE systems are being invented. We conclude the following: (1) The ideal analysis should harmonize rather than differentiate resilience and reliability. Therefore, this report uses the more general term disturbance whenever the overloaded terms resilience and reliability can be avoided. (2) The effectiveness of TE systems must be mapped to underlying qualities of a TE system, thereby avoiding presumptions that every TE design offers similar advantages. The authors seek to evaluate the parametric effects of TE system qualities (e.g., spatial granularity, granularity of time steps, length of future prediction horizon) on avoiding, reacting to, and recovering from grid disturbances. Furthermore, any advantages (or disadvantages) must be fairly compared with the many alternative tools, systems, and strategies that might offer comparable benefits.

Explore related subjects

Keep this discovery

Explore connections, maps & timelines

BibTeXRIS

Hanif, Sarmad, Chalishazar, Vishvas H., Hammerstrom, Donald J.. 2020-10-30. Modeling the Functional Forms of Grid Disturbances. https://doi.org/10.2172/1765364

Cite the original work for its findings. Save a collection to share your selection of sources.

KEEP EXPLORING

Related reports

Nodal capacity expansion planning with flexible large-scale load siting

We propose explicitly incorporating large-scale load siting into a stochastic nodal power system capacity expansion planning model that concurrently co-optimizes generation, transmission, and storage expansion. The potential operational flexibility of some of these large loads is also taken into account by considering them as consisting of a set of tranches with different reliability requirements, which are modeled as a constraint on expected served energy across operational scenarios. We implement our model as a two-stage stochastic mixed-integer optimization problem with cross-scenario expectation constraints. To overcome the challenge of scalability, we build upon existing work to implement this model on a high performance computing platform and exploit scenario parallelization using an augmented Progressive Hedging Algorithm. The algorithm is implemented using the bounding features of mpisppy, which have shown to provide satisfactory provable optimality gaps despite the absence of theoretical guarantees of convergence. We test our approach and assess the value of this proactive planning framework on total system cost and reliability metrics using realistic testcases geographically assigned to San Diego and South Carolina, with datacenter and direct air capture facilities as large loads.

24 POWER TRANSMISSION AND DISTRIBUTION↗

From zonal to nodal capacity expansion planning: Spatial aggregation impacts on a realistic test-case

Solving power system capacity expansion planning (CEP) problems at realistic spatial resolutions is computationally challenging. Thus, a common practice is to solve CEP over zonal models with low spatial resolution rather than over full-scale nodal power networks. Due to improvements in solving large-scale stochastic mixed integer programs, these computational limitations are becoming less relevant, and the assumption that zonal models are realistic and useful approximations of nodal CEP is worth revisiting. Here, this work is the first to conduct a systematic computational study on the assumption that spatial aggregation can reasonably be used for ISO-scale CEP. By considering a realistic, large-scale test network based on the state of California with over 8000 buses, we find that well-designed small spatial aggregations can yield good approximations but that coarser zonal models may result in large distortions of investment decisions, e.g., capacity under-investment of up to 41% for the lowest resolution model considered.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Multi-facility analysis using metered power data to quantify MRI energy use and utility bill costs across scanner operating modes

This study quantifies the energy consumption of magnetic resonance imaging (MRI) scanners across discrete operating modes during routine clinical workflows, based solely on electrical power measurements. Although previous studies have investigated MRI energy consumption within single hospitals or specific clinical settings, this research provides a broader and more systematic analysis. Researchers analyzed electrical power data and applied a previously developed semi-automatic method for identifying MRI operating modes using load duration curves for 20 MRI scanners across four different U.S. healthcare facilities, encompassing outpatient, inpatient, and mixed-use clinical settings. A key innovation is the inclusion of localized hourly utility rates to estimate costs, a parameter absent in prior literature. Key findings indicate significant variability in energy and cost profiles between weekdays and weekends. Scanner characteristics, including magnet strength, manufacturer, vintage, location, and clinical setting, influenced average daily energy consumption and power thresholds for operating modes. Notably, the clinical setting of a scanner predominantly determines its energy use. For example, the scanners in outpatient facilities consumed more energy. The breakdown of energy usage and costs by operating modes showed scanners spend between 61% and 93% of their time in nonproductive modes, with one outlier spending 34%. Average daily energy use for the scanners in the study ranged from 160 to 1069 kWh, with energy costs ranging from $\$$9 to $\$$149. This study uses an existing framework to quantify MRI energy behavior, leading to insights that can enable improved performance and cost savings across different healthcare environments.

24 POWER TRANSMISSION AND DISTRIBUTION↗