DOE OSTI · 1847892
Sequence Impedance Modeling of Grid-Forming Inverters
Abstract
Grid-forming control of inverter-based resources has been identified as a critical technology for operating power systems with high levels of inverter-based resources. This paper presents the sequence impedance modeling of a grid-forming inverter to evaluate its small-signal stability properties. Droop control structure is implemented to control the inverter in grid-forming mode, and the impact of individual controller on the inverter impedance characteristics is discussed. The developed sequence impedance model is compared with that of the grid-following inverter. It is found from the developed sequence impedance models that grid-forming inverters are less prone to harmonic resonance problems during operation with weaker grids. The developed models are validated using PSCAD simulations.
Explore related subjects
Keep this discovery
Explore connections, maps & timelines
Yan, Weihang, Shah, Shahil (ORCID:0000000230532863), Gevorgian, Vahan, Gao, David Wenzhong. 2021-12-20. Sequence Impedance Modeling of Grid-Forming Inverters. https://doi.org/10.1109/pesgm46819.2021.9638001
Cite the original work for its findings. Save a collection to share your selection of sources.