DOE OSTI · 1848094
Pressurizer dynamic model and emulated programmable logic controllers for nuclear power plants cybersecurity investigations
Abstract
This work demonstrates the functionality of the pressurizer using a fast-running three regions, non-equilibrium model and control programs of emulated PLCs. The state variables from an integrated model of primary loop in a representative PWR plant are communicated to the pressurizer’s emulated PLCs using a synchronized data transfer function. In turn, the PLCs communicate back instructions to the pressurizer model to adjust the pressure and water level to remain within preprogramed setpoints. Pressurizer model simultaneously solves the coupled mass and energy conservation equations in the saturated vapor and saturated and subcooled liquid regions using fixed step solver. Results demonstrate the response of the pressurizer model linked to an emulated pressure and water level PLCs in a simulated transient involving surge-in and surge-out events. The 50 ms response delay time for the emulated PLC insignificantly affects operation and predictions of the pressurizer model.
Explore related subjects
Keep this discovery
Explore connections, maps & timelines
El-Genk, Mohamed S., Altamimi, Ragai, Schriener, Timothy M.. 2021-01-19. Pressurizer dynamic model and emulated programmable logic controllers for nuclear power plants cybersecurity investigations. https://doi.org/10.1016/j.anucene.2020.108121