Search NASA⌕ Search

DOE OSTI · 1869432

Evaluation of Optimal Net Load Management in Microgrids Using Hardware-in-the-Loop Simulation

Abstract

This presentation discusses the performance evaluation of a net load management (NLM) engine that balances load and generation in an isolated community to power a critical facility after a grid interruption event (e.g., the loss of a large generation unit). This NLM engine is particularly important for microgrid systems because it provides a high-speed, cost-optimal control solution to coordinate grid-forming inverters and to dispatch grid-following inverters and deferrable loads in microgrid systems to enhance grid resilience and reliability. The NLM algorithm cost-optimally dispatches the grid-following inverters and deferrable loads based on the demanded power and load priorities, and the grid-forming inverters use droop control to form system voltages and share active and reactive power. A controller-hardware-in-the-loop platform is developed to evaluate the control performance of the NLM algorithm with two sequential contingency events of lost generation units. The experimental results indicate that the NLM engine can maintain system stability, achieve the targeted system voltage and frequency, and balance load and generation to serve the critical facility with improved system resilience and reliability.

Explore related subjects

Keep this discovery

Explore connections, maps & timelines

BibTeXRIS

Wang, Jing, Chakraborty, Soham, Khatana, Vivek, Lundstrom, Blake, Saraswat, Govind, Salapaka, Murti. 2022-05-17. Evaluation of Optimal Net Load Management in Microgrids Using Hardware-in-the-Loop Simulation. https://www.osti.gov/biblio/1869432

Cite the original work for its findings. Save a collection to share your selection of sources.

KEEP EXPLORING

Related reports

Dispatching Grid-Forming Inverters in Grid-Connected and Islanded Mode: Preprint

This paper explores the dispatch-ability of grid-forming (GFM) inverters in grid-connected and islanded mode. Grid-forming (GFM) inverters usually use droop control to automatically share power with other GFM sources (inverters and synchronous generator (SG)) and follow the change of the load demand. However, they can be dispatched like their grid-following (GFL) counterparts to output the target active and reactive power. This will help the grid operator better manage their inverter-based resources (IBRs) for improved operation efficiency and reliability. Therefore, this paper proposes an innovative concept of dispatching GFM sources (inverters and SG) to output the target power for both grid-connected and islanded mode by adjusting their droop intercepts. The fundamental principle of doing so is that the GFM inverter's active and reactive power is dictated by its frequency and voltage, thus, dispatching active and reactve power of a GFM inverter can be achieved through dispatching its frequency and voltage. Moreover, the concept distinguishes the dispatch rules for grid-connected and islanded mode. Finally, the concept is validated with an example microgrid system with two GFM inverters, one diesel generator, one grid-following inverter and loads in both grid-connected and islanded mode. This pioneering work results in a practical guidance for power system energy management system (EMS) development to control a future grid with GFM and GFL inverters.

droop control↗

Droop Control-Based Dispatch of an Islanded Microgrid with Multiple Grid-Forming Sources

Before rotating, fossil fuel-based, synchronous generators (SGs) are phased out, in line with renewable generation goals, grid-forming (GFM) inverters are expected to parallel SGs. Primary droop control allows GFM inverters to share power without communication; however, it is necessary to dispatch GFM inverters and/or SGs with the desired output power for better energy management (e.g., one GFM inverter needs to charge the battery due to a low state of charge). Therefore, this paper develops an analytic approach to dispatching GFM inverters and SGs with the desired output power by shifting the droop intercept up/down while maintaining the same frequency operating point for improved transient stability. This concept is demonstrated through a pure hardware setup with two off-the-shelf inverters and one diesel generator under an islanded microgrid, and we provide insight on the real-world implementation of the proposed concept.

droop control↗

Droop Control-Based Dispatch of an Islanded Microgrid with Multiple Grid-Forming Sources: Preprint

Before rotating fossil-fuel based synchronous generators (SGs) are phased out in line with renewable goals, grid-forming (GFM) inverters are expected to parallel with SGs. Primary droop control allows them share power without communication, however, it is necessary to dispatch GFM inverters and/or SG with desired output power for better energy management (e.g., one GFM inverter needs to charge the battery due to low state-of-the charge). Therefore, this paper develops analytic approach to dispatch GFM inverters and SG with desired output power by shifting the droop intercept up/down while maintain the same frequency operating point for improved transient stability. This concept is demonstrated through pure hardware setup with two off-the-shelf inverters and one diesel generator under islanded microgrid, and we also provide insight on real-world implementation of the proposed concept.

droop control↗